A misbehaving back-end node in Linode's Newark Object Storage slowed the service and caused 504 gateway timeouts
Linode Object Storage in Newark had two related incidents, on 10 and 16 October 2022, the second while the first was still under investigation. Linode found a hardware problem on one back-end Object Storage node. Because the hardware had not failed outright, the back-end node kept going up and down, and that instability set off excessive recovery operations in the cluster. The recovery work degraded performance across the service and in some cases made the front-end gateways return 504 gateway timeouts. At 10:31 UTC on 16 October the hardware failed outright and Linode removed it from the cluster; the cluster then recovered, client IO stopped bottlenecking and the gateways served clients normally again. Linode said the incidents showed gaps in its internal monitoring.
- Severity
- –
- Scope
- Linode Object Storage in Newark: reduced performance and availability, with 504 gateway timeouts in some cases
- Users affected
- –
- Region
- Newark
- Time to detect
- –
- Time to resolve
- –
Symptoms
In the week of 10 October 2022, Linode Object Storage in Newark had two incidents of reduced performance and availability, on 10 and 16 October, and in some cases the front-end gateways returned 504 gateway timeouts to customers. The second incident began while the first was still being investigated.
Root cause
Root cause Hardware failure
- Trigger
- One back-end Object Storage node had a hardware problem that was not an outright failure, so the node kept going up and down.
Detection
–
Remediation
- Removed the failed back-end infrastructure from the Object Storage cluster
Action items
- Improve detection so subtle problems with failing or misbehaving hardware are found and triaged before they affect the wider cluster
- Describe Ceph-related events more accurately to on-call administrators and define alerts more clearly
Lessons
Hardware that misbehaves without failing outright can cause service-wide problems, and Linode's internal monitoring had gaps in spotting such subtle issues before they affected the wider cluster.
Sources
- https://status.linode.com/incidents/5wgmd45h7h1j · official-status · archived copy
Related cases
IL-0239LLM pretraining jobs on Shanghai AI Laboratory's A100 clusters kept failing midway, mostly from NVLink and GPU errorsShanghai AI Laboratory · 2024same root cause · shared Object storage
Check your cluster for this
For AI tools and scripts
- This case as JSON: https://incidentlib-api.benchlet.com/cases/IL-0381
- The cases most like it: https://incidentlib-api.benchlet.com/cases/IL-0381/similar
- MCP server (Streamable HTTP, no key):
https://incidentlib-mcp.benchlet.com/mcp
The API needs no key. The MCP server offers search_incidents, get_incident, list_incidents, get_topic and vocab; both are explained on API and MCP.