Azure A100 InfiniBand all-reduce bandwidth dropped when over half of ToR switches' redundant uplinks were down
The SuperBench paper by Microsoft describes how hardware redundancy in Azure's AI infrastructure hides gradual degradation, which the authors call gray failure. Azure A100 clusters use over-provisioned InfiniBand networks with several redundant links between ToR switches and aggregation switches, and Microsoft found that more than half of those redundant links must work to avoid a performance regression from congestion, so at most half can be broken. Figure 3 of the paper plots the cumulative distribution of 2-node all-reduce bandwidth at different redundancy ratios for a real case on a 24-node, 192-NIC fat-tree testbed whose ToR switches each had 25% redundant uplinks. When some edge switches had over half of their redundant links down, multiple 2-node pairs running traffic together lost much of their all-reduce bus bandwidth, and the bandwidth of every pair returned to normal only after operators repaired the redundant links of all involved ToR switches to at least 50%.
The paper adds that troubleshooting usually repairs only enough redundancy to unblock the current workload, for example replacing one of several broken links, which leaves the infrastructure more likely to have the next incident when any single link fails. In Azure's A100 clusters the mean time between incidents was 17.5 hours, 38.1% of incidents took more than a day to recover, and troubleshooting started only when customers raised incidents. SuperBench, deployed in Azure for more than two years, runs benchmarks before incidents to find defective components such as these links.
- Severity
- –
- Scope
- 24-node A100 testbed with 192 InfiniBand NICs: all-reduce bus bandwidth of multiple 2-node pairs dropped significantly
- Users affected
- –
- Region
- –
- Time to detect
- –
- Time to resolve
- –
Symptoms
On a 24-node Azure A100 testbed with 192 InfiniBand NICs in a fat-tree topology, several 2-node pairs that ran traffic at the same time showed a significant drop in all-reduce bus bandwidth. Some edge switches had more than half of their redundant uplinks down.
Microsoft describes this as gradual degradation rather than a binary good or bad state. In Azure A100 clusters each InfiniBand top-of-rack (ToR) switch has several redundant uplinks, and when part of them break only some traffic patterns, such as all-to-all collective communication, lose throughput to congestion. Workloads that barely use the A100 GPUs or the network, such as ResNet training, do not trigger the problem early on, so monitoring the workloads already running does not reveal the lost redundancy in time.
Symptom Throughput degradation
Root cause
Root cause Dependency failure
- Trigger
- Some edge (ToR) switches of the testbed had more than half of their redundant uplinks to the aggregation switches down.
Detection
The drop showed in the 2-node all-reduce bandwidth measured across node pairs on the testbed. In production, Azure's troubleshooting began only when customers raised incidents.
Remediation
- Repaired the redundant links of every involved ToR switch to at least 50%, which brought all 2-node pairs back to normal all-reduce bandwidth
Action items
- Validate infrastructure components proactively with SuperBench benchmarks before incidents instead of relying on reactive troubleshooting
Lessons
Redundant links let the network keep working while degradation builds up, and only some traffic patterns slow down, so the loss is not a simple failure that monitoring of running workloads catches. Repairing just enough links to unblock the current workload does not restore the redundancy and makes the next incident more likely; Microsoft argues for stressing the hardware with standalone tests before incidents.
Sources
References
Related cases
IL-0133A storm shut down cooling at Nebius's us-central1 data center, and a disk hot-plug bug kept Managed Kubernetes control planes down for hours after power returnedNebius · 2026same root cause · shared InfiniBand fabric
IL-0023A training run crashed with an NCCL timeout after one InfiniBand port went down once and recoveredDatabricks · 2026same root cause · shared InfiniBand fabric
IL-0134A power event at Lambda's AUS01 data center rebooted 246 GPU nodes, all spine switches and the VAST storage, failing customer workloads and leaving stale NFS mounts on VMsLambda · 2026 · sev1same root cause · shared InfiniBand fabric
IL-0412InfiniBand link errors and flapping links cost Meta's RSC-1 fabric as much as 50-75% of its bandwidth during bring-upMeta · 2024same root cause · shared InfiniBand fabric
IL-0025Failed boots, InfiniBand link flapping, NCCL hangs and throughput sags while bringing up a 4,088-GPU H100 training clusterImbue · 2024same root cause · shared InfiniBand fabric
IL-0126The OPT-175B training run restarted more than 40 times in two weeks as cloud GPU nodes failed with ECC errors, replacement nodes came back faulty, and checkpoint downloads hungMeta AI · 2021same root cause · shared InfiniBand fabric
Check your cluster for this
For AI tools and scripts
- This case as JSON: https://incidentlib-api.benchlet.com/cases/IL-0475
- The cases most like it: https://incidentlib-api.benchlet.com/cases/IL-0475/similar
- MCP server (Streamable HTTP, no key):
https://incidentlib-mcp.benchlet.com/mcp
The API needs no key. The MCP server offers search_incidents, get_incident, list_incidents, get_topic and vocab; both are explained on API and MCP.