  1. Symptoms

    On 10 July 2019 the Stripe API failed a substantial majority of requests twice, from 16:35 to 17:02 UTC and from 21:14 to 22:47 UTC. In the first period automated monitoring detected within a minute that a database cluster had failed to elect a new primary.

    Trigger

    The primary node of a database cluster failed at 16:35 UTC while one shard had several stalled nodes. The second period was set off by rolling the election protocol back to the previous minor version at 20:42 UTC.

    Root cause
    Component
    Contributing factor
    Detection

    Automated monitoring detected the failed election within a minute, and the team was alerted at 16:36 UTC. The second period was announced at 21:14 UTC by automated alerts that some shards in the cluster were unavailable.

    Remediation
    • Restarted all nodes of the database cluster, which forced a successful primary election
    • Updated the production configuration and restarted the database cluster's nodes
    • Ramped traffic back up, putting services for user-initiated API requests first
    Action items
    • Alert when nodes stop reporting their replication lag
    • Alert when a shard enters a state that could trigger the election fault
    • Work with the database maintainers on a fix for the underlying fault
    • Add circuit breaking on failed operations to particular database clusters
    • Use fault isolation to contain the impact of a single failed shard
    • Limit the resources used by clients that keep retrying failed requests
    • Add procedures and tooling that make rapid configuration changes during incident response safer
  2. Symptoms

    At about 14:01 PDT on 13 October 2017, Discord engineers were alerted to anomalies by real-time metrics and monitoring. A Redis instance that was the primary of a highly available cluster used by the API services had dropped offline after Google Cloud Platform migrated it automatically, and some API instances did not handle the failover to the secondary node correctly.

    Trigger

    Google Cloud Platform automatically migrated the Redis instance that was the primary of a highly available cluster used by the API services, and the node incorrectly dropped offline.

    Root cause
    Component
    Contributing factor
    Detection

    Real-time metrics and monitoring alerted engineers at 14:01 PDT. The second phase was seen at 15:41 as another anomaly in monitoring, and end user reports of servers appearing offline were escalated at 15:42.

    Remediation
    • Ran a rolling restart of all API instances to clear the Redis connection issues
    • Corrected the misconfigured edge caching rule for the expensive API route
    • Disabled the problem API endpoint on the edge network
    • Recovered the Cassandra cluster
    • Ran a second rolling restart of all API instances for the latency left by the Cassandra issues
    • Removed the misbehaving guilds node from the service hashring
    • Forcefully restarted the misbehaving guilds node
    • Restarted the whole service, forcing all users to reconnect
    • Blocked traffic that relied on the failing push component to reduce its load
    • Corrected the API setting that lets users reconnect quickly and safely
    Action items
    • Fix the known issues with Redis failover within the coming weeks
    • Change the cached route so this type of error does not degrade other services
    • Monitor the signals that would have warned of the cascading failure
    • Improve the reliability and failure handling of the affected services
    • Roll out an update of the library with the suspected flaws
  3. Symptoms

    At 15:09 BST on 10 October 2017, GoCardless's monitoring detected a total outage of its API and Dashboard: every request failed and returned an error. By 15:11 engineers saw evidence of a disk array failure on the primary Postgres node, but the Pacemaker cluster had not failed over to the synchronous replica as it should have.

    Trigger

    The RAID controller of the primary Postgres node lost 3 disks of its array at once, so all reads and writes on the primary failed.

    Root cause
    Component
    Contributing factor
    Detection

    GoCardless's monitoring detected the total outage of the API and Dashboard at 15:09 BST, and engineers began investigating.

    Remediation
    • Powered off the broken primary Postgres node
    • Cleared the Pacemaker error counts with crm resource cleanup, which had no effect
    • Edited recovery.conf on the synchronous replica under maintenance mode several times, which Pacemaker reverted
    • Put the cluster into maintenance mode, configured the synchronous replica as primary and started Postgres by hand
    • Reconfigured the backend applications to connect to the new primary's actual IP address
    • Bootstrapped a third node as an asynchronous replica
    • Added a VIP managed by hand by the infrastructure team for manual failover
    • Verified data integrity and found no corruption
    • Migrated to a new Pacemaker-managed database cluster in a maintenance window and decommissioned the old one
    Action items
    • Express the Backup VIP rule as an INF preference for a replica instead of a -INF preference against the primary
    • Replace the VIPs with proxies on the application servers that route traffic by the state of the cluster
    • Run harsher fault injection tests of the Postgres cluster and consider automation that injects failures continually
    • Consider adding arbitrary restrictions to game day exercises, such as automation that has failed and a problem that cannot be diagnosed, so engineers practise bringing the service back another way
    Lessons

    A rule that two resources must not run together does not behave like the opposite of a rule that they must run together, and in some failure conditions the difference stopped Pacemaker from promoting a replica. A misconfiguration that shows only when two processes crash at almost the same time will not appear in basic tests or daily operations, only through fault injection. After two years in which the automation had handled every failure, the team's skill at controlling the cluster by hand had faded, and a runbook unused for years would likely have been out of date.

  4. Symptoms

    On Monday, September 10th, 2012, during a schema migration, the health checks on GitHub's MySQL master failed and Percona Replication Manager moved the 'active' role to another node of the new three-node cluster. That node's InnoDB buffer pool was cold and it performed poorly, its health checks failed in turn, and the role failed back to the original server. GitHub.com went down.

    Trigger

    A schema migration on Monday, September 10th put more load on the master database than earlier migrations had, and Percona Replication Manager's health checks on the master failed.

    Root cause
    Component
    Contributing factor
    Detection

    On the morning of September 11th, a developer told the operations team that the 'standby' node was returning incorrect query results.

    Remediation
    • Enabled Pacemaker's maintenance-mode so no health checks or automatic failovers ran, and let the buffer pool warm
    • Powered off the out-of-date node 'c' to end the partition
    • Stopped Pacemaker and Heartbeat on nodes 'a' and 'b' and started them on node 'a' only
    • Started MySQL on node 'a' in the active role
    • Removed the events leaked to wrong dashboards and audited the wrongly routed repositories
    • Contacted the owners of the exposed private repositories
    Action items
    • Change the Pacemaker configuration so the active database role fails over only when an operations engineer starts it
    • Find a way to warm the InnoDB buffer pool of slave databases so failovers do not hurt performance
    • Audit the Pacemaker and Heartbeat stack, focusing on the code path behind the segfault
    • Run hardware tests on the server where the segfault happened
    Lessons

    GitHub concluded that automated failover is not the right strategy for its primary production database: for every failover in this incident, any member of the operations team would have said it should not happen. Failovers that must happen, in an emergency or during maintenance, should not hurt performance.

Check your cluster for this