  1. Symptoms

    At about 13:40 UTC on 11 January 2023, alerts started firing for most SourceHut services being unavailable, along with one for remilia.sr.ht, the physical host that is SourceHut's main database server. The database server could not be reached remotely at all.

    Trigger

    remilia.sr.ht, the main database server, suffered a hardware failure at about 13:38 UTC.

    Root cause
    Component
    Contributing factor
    Detection

    Alerts fired at about 13:40 UTC for most services and for remilia.sr.ht itself, after Prometheus started failing to scrape remilia at 13:38.

    Remediation
    • Sent SourceHut's emergency on-call contact in the datacenter area to go on site
    • Moved remilia's disks into the chassis of build worker cirno1.sr.ht and brought it online as remilia
    Action items
    • Make the off-site database copy able to serve as a failover database host
    • Re-prioritize the migration to the EU
    • Set up new database failover
    • Add a new EU build worker to backfill build capacity
    • Record a better hardware inventory for future reference
  2. Symptoms

    At 08:30 UTC on 23 May 2022, every user Postgres database on one node in Render's Frankfurt region went completely down after the node, supplied by Render's external cloud provider, had a hardware issue and failed its status check. The database instances could not start on a healthy node because their disks were still attached to the failed node.

    Trigger

    A node supplied by Render's external cloud provider had a hardware issue and failed its status check at 08:30 UTC on 23 May 2022.

    Root cause
    Component
    Contributing factor
    Detection

    An alert that fires when databases have been stuck in one state while starting up for at least 15 minutes paged the on-call engineer automatically at 08:57 UTC.

    Remediation
    • Manually terminated the failed node at about 09:27 UTC so the disks could attach to healthy nodes
    Action items
    • Create an alert that fires sooner than the current 15-minute startup alert
    • Make it easier to identify the correct corrective action, and eventually automate it
    • Review incident procedures so the status page reflects reliability accurately
    • Build high availability for Postgres so a primary's node hardware failure causes minimal downtime
    Lessons

    Hardware issues are rare but expected, so Render's mitigations aim at detecting them sooner and shortening the time to resolve them.