IL-0240Cloudflare API requests failed and the dashboard slowed for hours after the authentication database lost its replicasCloudflare2020- Symptoms
On 2 November 2020 the Cloudflare API and dashboard were degraded for six hours and 33 minutes. The success rate of API queries dropped at times to 75%, and the dashboard was up to 80 times slower than normal, while Cloudflare's edge network kept working.
- Trigger
At 14:43 UTC a network switch in a control plane data center partly failed: it kept LACP and BGP running but stopped forwarding some packets, and it recovered on its own six minutes later.
- Root cause
- Component
- Contributing factor
- Detection
At 14:43 UTC alerts fired because the misbehaving switch was unreachable to pings. Engineers then saw that the primary authentication database was overwhelmed.
- Remediation
- Shed load from the primary authentication database by slowing SSL certificate pushes to the edge, emails and other features
- Moved API traffic that could use read replicas to the secondary data center by hand
- Sent authentication calls fully back to the primary data center when the dashboard got worse
- Rebuilt the first database replica, which put itself back into service at 21:20 UTC and returned performance to normal
- Ramped the turned-down services back up so asynchronous processing could catch up
- Action items
- Remove the cluster management limitation that requires rebuilding all replicas after a primary is promoted
- Redesign the user sessions system so dashboard traffic can be steered between data centers
- Change the auto-remediation configuration so a database replica is not promoted so quickly
- Tune each system involved to be more resilient to failures of its dependencies
- Lessons
Every system in the chain had redundancy and none failed completely; each only degraded, which made the chain of events much harder to model and foresee. Automating replica promotion so that it could trigger on a minute's notice had been a point of pride, but for at least one database a fast promotion can do more harm than the failure it answers. Most general-purpose cluster managers use Raft or Paxos rather than Byzantine fault tolerant protocols, accepting a rare failure mode in exchange for a protocol that is simpler to implement correctly and debug.
IL-0215Twilio's billing Redis master lost all balances and went read-only, and auto-recharge charged customer cards repeatedlyTwilio2013- Symptoms
At 2:39 AM PDT (9:39 UTC) on 18 July 2013, services that relied on the redis-master of Twilio's billing system began to fail because the load on its host had become extreme. At 2:42 AM PDT monitoring alerted the on-call engineers to a failure in the Redis cluster.
- Trigger
At 1:35 AM PDT on 18 July a loss of network connectivity disconnected all billing redis-slaves from the redis-master at once, and all of them requested a full synchronization at the same time. On-call engineers then restarted the overloaded redis-master.
- Root cause
- Component
- Contributing factor
- Detection
At 2:42 AM PDT monitoring alerted the on-call engineers to a failure in the Redis cluster. At 3:28 AM PDT the billing system monitoring reported the anomalous charges, and at 12:36 PM PDT monitoring detected the recurrence.
- Remediation
- Restarted the redis-master to relieve the high load, which loaded a wrong configuration
- Took the billing system offline to stop further credit card charges
- Restored service to all suspended accounts
- Restored the lost account balances from the independent double-bookkeeping record in the relational datastore
- Took billing offline again after the recurrence and reactivated the newly suspended accounts
- Refunded all erroneous credit card charges
- Gave all affected accounts a credit of 10% of their last 30 days of spend
- Replaced the original Redis cluster and corrected the redis-master configuration
- Activated the billing system progressively for groups of customer accounts
- Action items
- Disable Redis restarts on the redis-master and recover the master by pivoting a slave instead
- Add fail-safes so the billing system neither suspends accounts nor charges cards when balances are missing or cannot be written
- Validate the billing system against the double-bookkeeping databases in real time
- Lessons
Losing the in-flight balances and the ability to write balances at the same time exposed a flaw in the auto-recharge system: it failed in a dangerous way, charging cards and suspending accounts instead of stopping.
IL-0303GitHub's MySQL master failed over to a node with a cold buffer pool during a schema migration and GitHub.com went downGitHub2012- Symptoms
On Monday, September 10th, 2012, during a schema migration, the health checks on GitHub's MySQL master failed and Percona Replication Manager moved the 'active' role to another node of the new three-node cluster. That node's InnoDB buffer pool was cold and it performed poorly, its health checks failed in turn, and the role failed back to the original server. GitHub.com went down.
- Trigger
A schema migration on Monday, September 10th put more load on the master database than earlier migrations had, and Percona Replication Manager's health checks on the master failed.
- Root cause
- Component
- Contributing factor
- Detection
On the morning of September 11th, a developer told the operations team that the 'standby' node was returning incorrect query results.
- Remediation
- Enabled Pacemaker's maintenance-mode so no health checks or automatic failovers ran, and let the buffer pool warm
- Powered off the out-of-date node 'c' to end the partition
- Stopped Pacemaker and Heartbeat on nodes 'a' and 'b' and started them on node 'a' only
- Started MySQL on node 'a' in the active role
- Removed the events leaked to wrong dashboards and audited the wrongly routed repositories
- Contacted the owners of the exposed private repositories
- Action items
- Change the Pacemaker configuration so the active database role fails over only when an operations engineer starts it
- Find a way to warm the InnoDB buffer pool of slave databases so failovers do not hurt performance
- Audit the Pacemaker and Heartbeat stack, focusing on the code path behind the segfault
- Run hardware tests on the server where the segfault happened
- Lessons
GitHub concluded that automated failover is not the right strategy for its primary production database: for every failover in this incident, any member of the operations team would have said it should not happen. Failovers that must happen, in an emergency or during maintenance, should not hurt performance.
These 3 cases involve Database replication and Database. kubegap audits a Kubernetes cluster for gaps like these, read-only, from Claude Code or Codex; its checks cite public reports like the ones in this library.
By root cause3
DNS or network fault1 case
- Component
- Contributing factor
- Organisation
Configuration change1 case
- Component
- Contributing factor
- Organisation
Software defect1 case
- Contributing factor
- Organisation