  1. Symptoms

    On 2 November 2020 the Cloudflare API and dashboard were degraded for six hours and 33 minutes. The success rate of API queries dropped at times to 75%, and the dashboard was up to 80 times slower than normal, while Cloudflare's edge network kept working.

    Trigger

    At 14:43 UTC a network switch in a control plane data center partly failed: it kept LACP and BGP running but stopped forwarding some packets, and it recovered on its own six minutes later.

    Root cause
    Component
    Contributing factor
    Detection

    At 14:43 UTC alerts fired because the misbehaving switch was unreachable to pings. Engineers then saw that the primary authentication database was overwhelmed.

    Remediation
    • Shed load from the primary authentication database by slowing SSL certificate pushes to the edge, emails and other features
    • Moved API traffic that could use read replicas to the secondary data center by hand
    • Sent authentication calls fully back to the primary data center when the dashboard got worse
    • Rebuilt the first database replica, which put itself back into service at 21:20 UTC and returned performance to normal
    • Ramped the turned-down services back up so asynchronous processing could catch up
    Action items
    • Remove the cluster management limitation that requires rebuilding all replicas after a primary is promoted
    • Redesign the user sessions system so dashboard traffic can be steered between data centers
    • Change the auto-remediation configuration so a database replica is not promoted so quickly
    • Tune each system involved to be more resilient to failures of its dependencies
    Lessons

    Every system in the chain had redundancy and none failed completely; each only degraded, which made the chain of events much harder to model and foresee. Automating replica promotion so that it could trigger on a minute's notice had been a point of pride, but for at least one database a fast promotion can do more harm than the failure it answers. Most general-purpose cluster managers use Raft or Paxos rather than Byzantine fault tolerant protocols, accepting a rare failure mode in exchange for a protocol that is simpler to implement correctly and debug.

  2. Symptoms

    At 18:40 UTC db1075, the primary database of section s3, stopped answering, and all s3 wikis went read-only because no writes could reach it. Reads kept working from the replicas. At 18:42:45 Icinga reported "PROBLEM - Host db1075 is DOWN: PING CRITICAL - Packet loss = 100%".

    Trigger

    The RAID battery backup unit (BBU) of db1075, the s3 primary database host, failed and the whole host crashed.

    Root cause
    Component
    Contributing factor
    Detection

    Icinga reported db1075 HOST DOWN on IRC at 18:42:45, but that alert does not page; replica Slave IO alerts followed, users reported problems on #wikimedia-operations, and the first SMS page went out at 18:56. Volunteers and staff noticed the failure before the alerts did.

    Remediation
    • Power-cycled db1075 from the iDRAC after finding the BBU problem
    • Let MySQL finish InnoDB recovery on db1075
    • Removed read_only=ON from db1075 by hand
    • Ran puppet by hand a second time so pt-heartbeat started
    Action items
    • Implement or refactor a script that moves replicas when the primary is unavailable
    • Fix the MediaWiki heartbeat model so pt-heartbeat does not use a super-user, avoids a single point of failure and follows the real primary without depending on puppet
    • Decide what to do with the batch of hosts that already had BBU issues
    • Buy a new BBU for db1075
    • Remove db1075 from the primary role
    • Address MediaWiki spam while the database is read-only or the primary is unavailable
    • Make primary database hosts page on HOST DOWN
    • Track hardware errors better in Netbox
    Lessons

    A BBU failure should not crash a whole host, yet it had happened before on HP hosts. HOST DOWN on a primary database should page instead of only alerting on IRC. Starting pt-heartbeat through puppet races with MySQL startup, and the unnoticed failure kept lag reported and made the outage 8 minutes longer.

  3. Symptoms

    At 2:39 AM PDT (9:39 UTC) on 18 July 2013, services that relied on the redis-master of Twilio's billing system began to fail because the load on its host had become extreme. At 2:42 AM PDT monitoring alerted the on-call engineers to a failure in the Redis cluster.

    Trigger

    At 1:35 AM PDT on 18 July a loss of network connectivity disconnected all billing redis-slaves from the redis-master at once, and all of them requested a full synchronization at the same time. On-call engineers then restarted the overloaded redis-master.

    Root cause
    Component
    Contributing factor
    Detection

    At 2:42 AM PDT monitoring alerted the on-call engineers to a failure in the Redis cluster. At 3:28 AM PDT the billing system monitoring reported the anomalous charges, and at 12:36 PM PDT monitoring detected the recurrence.

    Remediation
    • Restarted the redis-master to relieve the high load, which loaded a wrong configuration
    • Took the billing system offline to stop further credit card charges
    • Restored service to all suspended accounts
    • Restored the lost account balances from the independent double-bookkeeping record in the relational datastore
    • Took billing offline again after the recurrence and reactivated the newly suspended accounts
    • Refunded all erroneous credit card charges
    • Gave all affected accounts a credit of 10% of their last 30 days of spend
    • Replaced the original Redis cluster and corrected the redis-master configuration
    • Activated the billing system progressively for groups of customer accounts
    Action items
    • Disable Redis restarts on the redis-master and recover the master by pivoting a slave instead
    • Add fail-safes so the billing system neither suspends accounts nor charges cards when balances are missing or cannot be written
    • Validate the billing system against the double-bookkeeping databases in real time
    Lessons

    Losing the in-flight balances and the ability to write balances at the same time exposed a flaw in the auto-recharge system: it failed in a dangerous way, charging cards and suspending accounts instead of stopping.

Check your cluster for this