  1. Symptoms

    On 19 August 2026 the first equipment-level signs in Nebius's us-central1 region appeared around 09:40 UTC: the InfiniBand fabric degraded and GPU over-temperature alerts began to accumulate. Customer reports followed shortly after 10:00. At 10:15 on-call engineers were paged on critical component temperature alerts, and the incident was declared at 10:21.

    Trigger

    A storm-related event at the data center building took the building management system offline and shut down the chilled-water cooling loop.

    Root cause
    Component
    Contributing factor
    Detection

    No facility-level alert fired, because the storm also disabled the building management system that monitors the facility. Engineers acted on component over-temperature alerts that paged on-call at 10:15 UTC, after InfiniBand degradation, GPU over-temperature alerts and customer reports; the temperature rise from about 09:15 was visible on dashboards but had no alert.

    Remediation
    • had the facility operator switch cooling to manual bypass mode and opened rack rear doors to vent heat
    • re-energised tripped racks, control-plane racks first
    • restored the regional infrastructure control plane by manual intervention
    • restarted block-storage host components to clear stale disk attachment state
    • raised the VM recovery rate limits by hand for the region-scale recovery
    • started the affected Managed Kubernetes control-plane instances by hand
    • applied a controlled stop and start to control-plane instances whose data disk had been left unattached
    • identified and started 104 customer VMs that the incident had stopped
    Action items
    • Complete a joint resilience review with the facility operator covering redundancy of facility-management and monitoring systems, cooling that keeps running when those fail, electrical protection of cooling equipment and on-site response
    • Add facility-level environmental alerting on cooling plant state and room temperature trend that pages on-call independently of the building management system
    • Set up a documented emergency escalation path with the facility operator, with an on-call contact tree and guaranteed response times
    • Define an emergency heat-load reduction procedure with criteria, ownership and mechanics for shutting down or degrading workloads during a cooling loss
    • Establish a dependency-ordered region cold-start procedure with clear ownership for each service layer
    • Run regular region-scale recovery drills that cover VMs, storage attachments and Managed Kubernetes clusters
    • Fix the disk-attachment bug that extended the Managed Kubernetes outage and deploy the fix to all production regions
    • Improve the recovery policies Compute users can configure, and move all Managed Kubernetes control-plane nodes to the improved policy
    • Automate reconciliation of stale storage attachment state after abrupt host failures
    • Remove in-region dependencies from monitoring startup and recovery, and extend cross-region monitoring
    • Make regional health checks used for global traffic management reflect real service availability
    Lessons

    Facility monitoring that runs on the same system it watches goes silent in exactly the failure it should report, and with no alert on the room temperature trend there was no practical window to shed heat load in a controlled way. A cold start of a whole region exercised recovery paths built for isolated failures: single-attempt VM recovery, conservative rate limits and stale disk attachments all needed manual work. The longest part of the outage was restoring customer resources, Managed Kubernetes control planes above all, so Nebius is extending its recovery drills to that layer.

  2. Symptoms

    At 14:10 an engineer deployed a change to a service that Monzo's current account needs to process payments, and every request to that service started to fail. Current account customers saw payment failures; the prepaid card was not affected at first because it does not use that service. The change was rolled back at 14:12, but the errors continued.

    Trigger

    At 14:10 an engineer deployed a change to a service needed to process current account payments. Two weeks earlier the etcd cluster had been upgraded and grown from three to nine nodes, and one day earlier another team had scaled a new service down to zero replicas while leaving its Kubernetes service in place.

    Root cause
    Component
    Contributing factor
    Detection

    Payment failures began right after the 14:10 deploy. The team rolled back at 14:12 and declared an outage internally at 14:16. At 15:13, when no service could serve requests, practically all automated alerts fired.

    Remediation
    • Rolled back the payments service change (the errors continued)
    • Activated internal backup processes so most customers could still use their card
    • Restarted all linkerd instances (this made the outage worse)
    • Restarted the three Kubernetes API server processes so replacement linkerd instances could start
    • Began deploying a newer linkerd version with the fix for empty services
    • Deleted the Kubernetes service that had no endpoints, which let linkerd load service discovery again
    Action items
    • Fix the bug in Kubernetes that can trigger timeouts after a cluster reconfiguration
    • Roll out a new version of linkerd that fixes the parsing error
    • Create better health checks, dashboards and alerts for the affected components so they give clearer signals about what is wrong and prevent human error
    • Improve procedures to communicate outages internally and externally as clearly and quickly as possible
    Lessons

    A large failure in a distributed system can be very hard to understand, and well-meant human action can compound it, as restarting every linkerd instance did here by exposing a second incompatibility. Because Monzo deploys often and its network changes constantly, the deployment and request-routing systems have to be trustworthy. Monzo committed to publishing a similar post-mortem for any incident of this severity.