Cases2 cases
1 to 2 of 2
IL-0138A failed Nvidia driver build left broken kernel packages on the only Kubernetes master node, which hit a kernel panic on reboot after a power outage and took the homelab cluster down for six daysBarush Mendez2025- Symptoms
Every service in the homelab Kubernetes cluster stopped answering: the V-Rising server, Grafana, Jellyfin and Linkding were all unreachable, and the Kubernetes API was down, so the cluster could not be managed at all. The outage was found by hand, about 3 hours after it began, when someone tried to use the services.
- Trigger
A power outage forced the Kubernetes master node to reboot.
- Root cause
- Component
- Contributing factor
- Detection
Manually, when someone tried to access the services; there were no automated alerts.
- Remediation
- Connected a monitor to the master node and read the boot logs, which showed the kernel panic
- Booted the previous kernel version, which brought the system back
- Removed the broken Nvidia packages with sudo apt-get remove --purge '^nvidia-.*' and ran sudo dpkg --configure -a
- Found remaining broken packages with dpkg -l | grep -v ^ii and removed them by hand
- Ran sudo apt-get install -f and reinstalled linux-headers-$(uname -r)
- Rebooted and confirmed the kernel panic was gone
- Action items
- Make sure GPU driver installations fully succeed, or revert immediately when they fail
- Move the cluster to a high-availability control plane
- Expose the Kubernetes API through a load balancer in the HA setup
- Set up a ticketing system to record incidents and their resolution
- Write predefined troubleshooting workflows to shorten response time
- Add infrastructure monitoring such as Prometheus and Grafana
- Add blackbox HTTP and TCP checks from outside the cluster for critical services
- Lessons
A driver installation that fails half-way can leave kernel packages broken without any visible effect until the next reboot, which may come weeks later and at the worst time. A failed DKMS build should be fixed or reverted at once. With a single master node and no monitoring from outside the cluster, one unbootable machine meant a total outage that nobody was told about; the fix itself was simple once the boot logs were seen.
IL-0025Failed boots, InfiniBand link flapping, NCCL hangs and throughput sags while bringing up a 4,088-GPU H100 training clusterImbue2024- Symptoms
When Imbue brought up a cluster of 4,088 H100 GPUs on 511 hosts, about 10% of the machines failed to boot, mostly from physical problems: unconnected or miswired Ethernet cables, iDRAC hardware issues, broken power supplies, bad NVMe drives, missing internal wires, and network cards or GPUs that did not show up. In single-node GPU tests, Ubuntu server logs showed links between the GPUs and the PCIe buses or network cards reporting "limited width: x4 < x16". A few hosts had NVMe drives that locked up the whole machine when touched, drives that appeared in random order and got the OS installed on the wrong one, wrong temperature readings that kept fans at 100%, and CPUs limited to 2 GHz.
- Trigger
Bringing a new InfiniBand-connected H100 cluster into service and running the first multi-node training jobs on it.
- Root cause
- Component
- Contributing factor
- Detection
Automated hardware checks during provisioning, UFM alerts on temperature, error rates and flapping ports, Prometheus node exporter and DCGM metrics, per-batch MFU monitoring, and live debugging of stalled processes with Py-Spy, GDB and NVIDIA Nsight.
- Remediation
- Automated checks for broken machines and sent faulty ones back to Dell or to data center staff
- Reseated GPUs and internal PCIe cables and applied firmware upgrades
- Downgraded the NVIDIA driver that caused wrong temperature readings
- Rewired the top tier of the InfiniBand fabric into a single network and added checks that the wiring matched the design
- Cleaned and reseated alerting ports and disabled the remaining alerting transceivers
- Ran a burn-in workload through every InfiniBand port and disabled the ports that did not survive it
- Enabled GPUDirect RDMA with an extra kernel module and PCIe ACS disabled
- Disabled automatic garbage collection and scheduled it at set intervals on all hosts
- Action items
- Release host-level health checks that confirm a host is free from known errors
- Release an NCCL patch that improves logging around errors and stalls
- Release a GPU stress test and NVLink and InfiniBand networking tests
- Release a script that parses the UFM event log and decides which network ports to disable
- Release a script that generates a burn-in workload exercising every InfiniBand link
- Relaunch crashed runs automatically from the last checkpoint on the machines that pass health checks
- Replace the disabled alerting transceivers
- Lessons
Keep 10 to 20% more machines than a run needs, and network them so any working subset can be used. On the newest hardware expect about 3% of machines to break each week, mostly the same few machines breaking in different ways, so growing a set of known reliable "golden" hosts works better than chasing random failures. Write tests and automation for every kind of failure met, because each one comes back, and write tools that make opaque errors readable. Change only one thing at a time, and double-check the claims of new tools and people before building on them.
These 2 cases involve GPU driver and InfiniBand fabric. kubegap audits a Kubernetes cluster for gaps like these, read-only, from Claude Code or Codex; its checks cite public reports like the ones in this library.
By root cause2
Software defect1 case
- Contributing factor
- Organisation
Dependency failure1 case
- Contributing factor
- Organisation