IL-0233A VPC control plane release broke IP alias routes in Nebius eu-west1, and Managed Kubernetes pods lost connectivityNebius2025- Symptoms
On 13 March 2025 practically every pod of Nebius Managed Services for Kubernetes in the eu-west1 region lost network connectivity for at least some time between 13:36 and 18:11 UTC. Packets for the affected IP alias routes were not processed by the data plane. The eu-north1 region was not affected.
- Trigger
A release of a VPC control plane component in eu-west1, deployed to canaries from 13:36 UTC and to all other nodes from 14:35 UTC, changed route distinguisher values for a new feature. The change made a long-standing bug in the handling of route announcements take effect for the update messages of Managed Kubernetes pods.
- Root cause
- Component
- Contributing factor
- Remediation
- Restarted the host VPC component on the affected nodes one node at a time
- Restarted the host VPC component on the remaining nodes in parallel once the restart was known to fix the problem
- Action items
- Fix the bug in the VPC host component itself
- Add an alert on a diverging number of routes
- Add an alert on the number of drops in the data plane
- Develop a way to reset endpoints without restarting the host VPC component
- Move the VPC's persistent e2e test virtual machines to canary hosts
- Add persistent e2e tests for Managed Services for Kubernetes
- Run e2e tests more often
- Add a deployment stage in which non-critical internal services receive updates first
- Lessons
The failure needed both an existing IP alias at release time and a particular order of node updates, and neither the testing installation nor the canaries met both, so neither caught it. Missing alerts on technical metrics that deviate from normal, here the number of routes and the number of drops, made the response much slower.
IL-0222Google Cloud US regions had heavy packet loss and some went unreachable after the network control plane was descheduledGoogle Cloud2019- Symptoms
On Sunday 2 June 2019, with user impact beginning between 11:47 and 11:49 US/Pacific, Google Cloud projects in several US regions saw elevated packet loss from network congestion, and some regions became unreachable. Customers saw higher latency, intermittent errors and lost connectivity to instances in us-central1, us-east1, us-east4, us-west2, northamerica-northeast1 and southamerica-east1, while us-west1, Europe and Asia had no regional congestion.
- Trigger
At 11:45 US/Pacific a relatively rare type of datacenter maintenance event started in one physical location, and the automation that runs it descheduled logical clusters that also held network control plane jobs in other physical locations.
- Root cause
- Component
- Contributing factor
- Detection
Google engineers were alerted to the failure two minutes after it began and started the incident process used for the most serious production incidents. The first customer notice appeared on the status page at 12:53 US/Pacific.
- Remediation
- Lowered the priority of less critical network traffic classes to reduce congestion
- Halted the datacenter automation software responsible for the maintenance event
- Rescheduled the network control plane and its supporting infrastructure in each location
- Rebuilt and redistributed the lost network control plane configuration, rolling it out from 14:03
- Directed service traffic away from the affected regions
- Moved the Cloud VPN control plane in three regions out of its fail-safe state
- Action items
- Keep the maintenance automation off until safeguards stop it descheduling jobs in several physical locations at once
- Harden the cluster management software to reject such requests whatever their origin
- Reconfigure the network control plane to reject maintenance requests of the type involved
- Make the network control plane in each location persist its configuration
- Let the network stay in fail static mode longer when the control plane is lost
- Review, update and test emergency response tooling and procedures, including customer communication tooling, for such network failures
- Extend continuous disaster recovery testing to this and similarly catastrophic failures