IL-0133A storm shut down cooling at Nebius's us-central1 data center, and a disk hot-plug bug kept Managed Kubernetes control planes down for hours after power returnedNebius2026- Symptoms
On 19 August 2026 the first equipment-level signs in Nebius's us-central1 region appeared around 09:40 UTC: the InfiniBand fabric degraded and GPU over-temperature alerts began to accumulate. Customer reports followed shortly after 10:00. At 10:15 on-call engineers were paged on critical component temperature alerts, and the incident was declared at 10:21.
- Trigger
A storm-related event at the data center building took the building management system offline and shut down the chilled-water cooling loop.
- Root cause
- Component
- Contributing factor
- Detection
No facility-level alert fired, because the storm also disabled the building management system that monitors the facility. Engineers acted on component over-temperature alerts that paged on-call at 10:15 UTC, after InfiniBand degradation, GPU over-temperature alerts and customer reports; the temperature rise from about 09:15 was visible on dashboards but had no alert.
- Remediation
- had the facility operator switch cooling to manual bypass mode and opened rack rear doors to vent heat
- re-energised tripped racks, control-plane racks first
- restored the regional infrastructure control plane by manual intervention
- restarted block-storage host components to clear stale disk attachment state
- raised the VM recovery rate limits by hand for the region-scale recovery
- started the affected Managed Kubernetes control-plane instances by hand
- applied a controlled stop and start to control-plane instances whose data disk had been left unattached
- identified and started 104 customer VMs that the incident had stopped
- Action items
- Complete a joint resilience review with the facility operator covering redundancy of facility-management and monitoring systems, cooling that keeps running when those fail, electrical protection of cooling equipment and on-site response
- Add facility-level environmental alerting on cooling plant state and room temperature trend that pages on-call independently of the building management system
- Set up a documented emergency escalation path with the facility operator, with an on-call contact tree and guaranteed response times
- Define an emergency heat-load reduction procedure with criteria, ownership and mechanics for shutting down or degrading workloads during a cooling loss
- Establish a dependency-ordered region cold-start procedure with clear ownership for each service layer
- Run regular region-scale recovery drills that cover VMs, storage attachments and Managed Kubernetes clusters
- Fix the disk-attachment bug that extended the Managed Kubernetes outage and deploy the fix to all production regions
- Improve the recovery policies Compute users can configure, and move all Managed Kubernetes control-plane nodes to the improved policy
- Automate reconciliation of stale storage attachment state after abrupt host failures
- Remove in-region dependencies from monitoring startup and recovery, and extend cross-region monitoring
- Make regional health checks used for global traffic management reflect real service availability
- Lessons
Facility monitoring that runs on the same system it watches goes silent in exactly the failure it should report, and with no alert on the room temperature trend there was no practical window to shed heat load in a controlled way. A cold start of a whole region exercised recovery paths built for isolated failures: single-attempt VM recovery, conservative rate limits and stale disk attachments all needed manual work. The longest part of the outage was restoring customer resources, Managed Kubernetes control planes above all, so Nebius is extending its recovery drills to that layer.
IL-0233A VPC control plane release broke IP alias routes in Nebius eu-west1, and Managed Kubernetes pods lost connectivityNebius2025- Symptoms
On 13 March 2025 practically every pod of Nebius Managed Services for Kubernetes in the eu-west1 region lost network connectivity for at least some time between 13:36 and 18:11 UTC. Packets for the affected IP alias routes were not processed by the data plane. The eu-north1 region was not affected.
- Trigger
A release of a VPC control plane component in eu-west1, deployed to canaries from 13:36 UTC and to all other nodes from 14:35 UTC, changed route distinguisher values for a new feature. The change made a long-standing bug in the handling of route announcements take effect for the update messages of Managed Kubernetes pods.
- Root cause
- Component
- Contributing factor
- Remediation
- Restarted the host VPC component on the affected nodes one node at a time
- Restarted the host VPC component on the remaining nodes in parallel once the restart was known to fix the problem
- Action items
- Fix the bug in the VPC host component itself
- Add an alert on a diverging number of routes
- Add an alert on the number of drops in the data plane
- Develop a way to reset endpoints without restarting the host VPC component
- Move the VPC's persistent e2e test virtual machines to canary hosts
- Add persistent e2e tests for Managed Services for Kubernetes
- Run e2e tests more often
- Add a deployment stage in which non-critical internal services receive updates first
- Lessons
The failure needed both an existing IP alias at release time and a particular order of node updates, and neither the testing installation nor the canaries met both, so neither caught it. Missing alerts on technical metrics that deviate from normal, here the number of routes and the number of drops, made the response much slower.
These 2 cases involve BGP routing and Cloud block storage. kubegap audits a Kubernetes cluster for gaps like these, read-only, from Claude Code or Codex; its checks cite public reports like the ones in this library.
By root cause2
Dependency failure1 case
- Contributing factor
- Organisation
Software defect1 case
- Contributing factor
- Organisation