  1. Symptoms

    On 19 August 2026 the first equipment-level signs in Nebius's us-central1 region appeared around 09:40 UTC: the InfiniBand fabric degraded and GPU over-temperature alerts began to accumulate. Customer reports followed shortly after 10:00. At 10:15 on-call engineers were paged on critical component temperature alerts, and the incident was declared at 10:21.

    Trigger

    A storm-related event at the data center building took the building management system offline and shut down the chilled-water cooling loop.

    Root cause
    Component
    Contributing factor
    Detection

    No facility-level alert fired, because the storm also disabled the building management system that monitors the facility. Engineers acted on component over-temperature alerts that paged on-call at 10:15 UTC, after InfiniBand degradation, GPU over-temperature alerts and customer reports; the temperature rise from about 09:15 was visible on dashboards but had no alert.

    Remediation
    • had the facility operator switch cooling to manual bypass mode and opened rack rear doors to vent heat
    • re-energised tripped racks, control-plane racks first
    • restored the regional infrastructure control plane by manual intervention
    • restarted block-storage host components to clear stale disk attachment state
    • raised the VM recovery rate limits by hand for the region-scale recovery
    • started the affected Managed Kubernetes control-plane instances by hand
    • applied a controlled stop and start to control-plane instances whose data disk had been left unattached
    • identified and started 104 customer VMs that the incident had stopped
    Action items
    • Complete a joint resilience review with the facility operator covering redundancy of facility-management and monitoring systems, cooling that keeps running when those fail, electrical protection of cooling equipment and on-site response
    • Add facility-level environmental alerting on cooling plant state and room temperature trend that pages on-call independently of the building management system
    • Set up a documented emergency escalation path with the facility operator, with an on-call contact tree and guaranteed response times
    • Define an emergency heat-load reduction procedure with criteria, ownership and mechanics for shutting down or degrading workloads during a cooling loss
    • Establish a dependency-ordered region cold-start procedure with clear ownership for each service layer
    • Run regular region-scale recovery drills that cover VMs, storage attachments and Managed Kubernetes clusters
    • Fix the disk-attachment bug that extended the Managed Kubernetes outage and deploy the fix to all production regions
    • Improve the recovery policies Compute users can configure, and move all Managed Kubernetes control-plane nodes to the improved policy
    • Automate reconciliation of stale storage attachment state after abrupt host failures
    • Remove in-region dependencies from monitoring startup and recovery, and extend cross-region monitoring
    • Make regional health checks used for global traffic management reflect real service availability
    Lessons

    Facility monitoring that runs on the same system it watches goes silent in exactly the failure it should report, and with no alert on the room temperature trend there was no practical window to shed heat load in a controlled way. A cold start of a whole region exercised recovery paths built for isolated failures: single-attempt VM recovery, conservative rate limits and stale disk attachments all needed manual work. The longest part of the outage was restoring customer resources, Managed Kubernetes control planes above all, so Nebius is extending its recovery drills to that layer.

  2. Symptoms

    On Adyen's production big data Kubernetes clusters, new pods on some nodes could not start because setting up their network through Cilium timed out. Once one pod had timed out, every other pod trying to start on the same node timed out as well.

    Trigger

    Heavy data workloads landed on nodes where the interval of Cilium's periodic garbage collection of expired connection tracking entries had grown, during a quiet period, toward its 12-hour maximum.

    Root cause
    Component
    Contributing factor
    Remediation
    • Set a fixed connection tracking garbage collection interval, conntrackGCInterval: 60s, and rolled it out to the Cilium DaemonSet
    Action items
    • Alert on the connection tracking garbage collection duration and table size metrics
    Lessons

    Scaling parameters can interact with other logic months later as traffic grows: the larger table that solved capacity limits on 512GB nodes interacted with the garbage collection auto-scaling on the 2TB nodes. Logs only showed symptoms, so profiling and tracing across the container runtime, the CNI plugin, the Cilium agent and the kernel were needed, and simple arithmetic with measured numbers pointed at the cause early. Auto-scaling algorithms need bounds, and the 12-hour maximum interval was too long for this workload. A timeout protects the caller but does not cancel the work behind it. Adyen recommends that Cilium deployments with dynamic workloads alert on cilium_datapath_conntrack_gc_duration_seconds and cilium_datapath_conntrack_gc_entries and set conntrackGCInterval: 60s.

  3. Symptoms

    From 20:01 UTC on 28 May 2026, Buildkite build and job notifications (GitHub commit status, email, Slack and webhook notifications) reached a subset of customers late. Internal queue latency monitoring showed the delay as queues grew while notification-processing workers stayed underprovisioned.

    Trigger

    The Prometheus service used by Buildkite's EKS autoscaling path ran out of storage, so some EKS-based notification workers could not autoscale while their queues were growing.

    Root cause
    Component
    Contributing factor
    Detection

    Internal queue latency monitoring detected the rising notification delivery latency.

    Remediation
    • Moved the affected notification-processing workloads from EKS back to the ECS-based infrastructure
    • Adjusted scaling configuration and worker counts by hand
    • Completed the rollback and scaled the remaining affected ECS services
    • Increased Prometheus storage capacity and recorded the change in infrastructure as code
    Action items
    • Alert before Prometheus storage exhaustion can affect autoscaling
    • Fix GitHub notification retry behaviour for a class of errors that could cause repeated retries
    • Make the EKS-to-ECS rollback verify destination capacity, autoscaling configuration and traffic movement
    • Review the CPU, memory and storage allocations of EKS control-plane dependencies such as KEDA and Karpenter
    • Move customer-critical workloads to EKS more gradually, with clearer settling periods
    • Improve customer-level monitoring of notification delivery latency to detect customer-impacting regressions earlier
    • Review which notification types sit on customers' scheduling or CI hot path and need tighter latency, separate queueing or specific alerting
    • Update the status page earlier when notification latency is likely to affect customer workflows
    • Describe the customer-visible impact in status page updates, not only the affected internal service
    • Improve internal escalation for customers who report critical CI impact
    Lessons

    Buildkite said recovery took longer than expected because the rollback path from EKS to ECS did not fully handle this failure, and that its public status page did not show the customer-visible impact as quickly or clearly as it should have, since notification latency affects customers differently depending on how their CI and deployment workflows use notifications.

  4. Symptoms

    On 4 March 2026 customers of the IONOS Container Registry got 504 Gateway Timeout errors when pushing or pulling container images, and deployments that relied on the registry were blocked. The status page first reported an increased error count on the registry at 09:23 UTC, saying customers might be unable to pull images.

    Trigger

    A migration combined with a temporary capacity constraint placed two critical control plane components on the same proxy instance, despite anti-affinity rules; the shared proxy then reached its concurrent connection limit.

    Root cause
    Component
    Contributing factor
    Remediation
    • Rolled back a component of the Kubernetes control plane to an earlier version
    • Provisioned additional proxy capacity
    • Moved the affected control plane components onto separate proxy instances
    Action items
    • Redesign registry-to-API connectivity so each node uses its own local proxy
    • Adjust alert thresholds to warn before proxy connection use approaches capacity
    • Deploy more infrastructure clusters and redistribute registries so no cluster exceeds safe capacity, with automation that keeps balancing load
  5. Symptoms

    On 21 October 2025 at 21:45 UTC a change to timeout handling was deployed to the feature flags service, and two minutes later automated monitoring reported higher error rates. The change was rolled back by 21:49, but error rates stayed high: about 38% of flag evaluation requests in the US datacenter returned errors. At 22:30 Redis metrics showed memory exhaustion on ElastiCache, at 22:35 Postgres connections spiked, and at 22:45 the team found a massive data transfer from Postgres into Redis. The main PostHog application was affected as well, because it shares the Redis instance with the flags service.

    Trigger

    On 21 October a deployment meant to reduce timeout errors (PR #39821); on 24 October the deployment of IP-based rate limiting (PR #40074) that saw all traffic as coming from the load balancer's IP; on 28 October an unrelated routine deployment that rolled the feature flag pods in the US region.

    Root cause
    Component
    Contributing factor
    Detection

    On 21 October automated monitoring detected higher error rates two minutes after the deploy. On 24 October no alert existed for 429 errors, and the team learned of the incident from customer reports that began at 18:10 UTC, a 62-minute detection delay. On 28 October on-call received a high error count alert. On 29 October the incident was reported with higher error rates and latency. No alert existed for CPU pressure, so the CPU saturation behind all three incidents was not seen directly.

    Remediation
    • rolled back the timeout handling change within 2 minutes on 21 October, which did not stop the errors
    • throttled connections and Redis writes on 21 October
    • halted the rollout on 28 October, scaled the US flags pods to zero until Redis recovered, then scaled them back gradually
    • rolled back hardware changes on 30 October at 00:03 UTC, which removed most errors but not the latency
    • increased the pod resource requests and adjusted the Kubernetes fleet size so fewer pods ran on each node
    • added retry limits to Envoy between the load balancer and the service
    • moved database connection timeouts and other critical settings to runtime configuration and raised the timeout values
    • added per-node and per-pod CPU alerts at 80% sustained for 5 minutes that page on-call
    Action items
    • Form a strike team from the flags, ingestion and infrastructure teams to review the application and infrastructure for remaining bottlenecks
    • Investigate separating the flags Redis instance from the application Redis instance
    • Before re-enabling ArgoCD sync, align the flags service chart configuration with the values in ArgoCD and define the deployment and Redis strategy
    • Make the feature flags team hard code-owners for flags-related code
    • Build a dashboard of key flag metrics with runbook links and update the feature flag runbooks
    • Add missing alerts on existing service and infrastructure metrics
    • Make readiness checks validate dependencies that degrade under load, for example by pinging the database
    • Rate-limit cache population so it cannot overwhelm Redis
    • Monitor connection pools with automatic throttling near exhaustion and limit concurrent connections
    • Build a production-scale load testing framework
    • Build progressive rollout infrastructure to limit blast radius
    • Document Postgres-to-Redis data flows and write runbooks for data transfer storms
    Lessons

    Nodes that are small relative to pod requests let the scheduler pack many pods on each node, and the resulting CPU saturation showed up three different ways: excessive parallelism, connection pool exhaustion and slow queries. Treating each symptom separately let the problem return; right-sizing the pods and nodes fixed all three. CPU must be alerted on from the start. Unbounded Envoy retries and unbounded cache population amplified the overload, and a Redis instance shared with the main application spread a flags problem to the main application. A rollback did not end the incident, because the data transfer and resource exhaustion it had started kept running.

Check your cluster for this

These 19 cases involve Node pool and JupyterHub. kubegap audits a Kubernetes cluster for gaps like these, read-only, from Claude Code or Codex; its checks cite public reports like the ones in this library.

By root cause6

Dependency failure1 case

Organisation
  1. IL-0133 A storm shut down cooling at Nebius's us-central1 data center, and a disk hot-plug bug kept Managed Kubernetes control planes down for hours after power returned
    Nebius2026

Configuration change3 cases

  1. IL-0246 New pods on Adyen's big data Kubernetes nodes could not start, failing with "Cilium API client timeout exceeded"
    Adyen2026
  2. IL-0019 An EKS Terraform module upgrade shrank node root disks from 100 GB to 20 GB and image pulls failed with no space left on device
  3. IL-0035 Worker nodes went NotReady after a new ElastAlert rule without memory limits used up node memory
    NU.nl2019

Capacity exhaustion9 cases

  1. IL-0470 Buildkite notifications were delayed after Prometheus storage filled and EKS notification workers could not autoscale
  2. IL-0465 IONOS Container Registry image pushes and pulls failed with 504 Gateway Timeout
  3. IL-0100 PostHog's feature flags pods were packed onto Kubernetes nodes that were too small for their CPU requests, and CPU saturation above 90% caused three outages in ten days through Redis overload, connection pool exhaustion and slow queries
  4. IL-0042 Application logs stopped reaching Elasticsearch and OpenSearch for hours and were lost when OpenSearch ran out of disk space
  5. IL-0043 Application logs missing in Kibana after a newer Fluent Bit version changed its chunk drop strategy
  6. IL-0016 Prometheus on the live cluster ran out of memory and was OOMKilled, and the monitoring node it ran on went NotReady
  7. IL-0500 UToronto JupyterHub logins and server starts returned 500 errors when the hub's sqlite database disk filled up
    2i2c2022
  8. IL-0013 The conntrack table filled up on downsized GKE nodes and a high-traffic aggregation proxy saw climbing connection resets
  9. IL-0503 mybinder.org launches failed after a GKE node ran out of memory and its nginx-ingress proxy pod crash-looped

Faulty deployment3 cases

  1. IL-0020 During an EKS 1.30 upgrade the descheduler tried to reschedule every pod on the cordoned nodes at once and production workloads went down
  2. IL-0530 Virtual router controllers in us-central1 ran out of memory in a loop, cutting networking for new and migrated VMs
  3. IL-0467 Boskos crash-looped after a node drain started it from a buggy StatefulSet image, failing Kubernetes PR jobs for 9 hours

Software defect2 cases

  1. IL-0077 EKS cluster went read-only for over seven hours after Kyverno ephemeralreports filled the etcd database past its size limit
  2. IL-0504 mybinder.org launches failed for about five hours as undeleted user pods piled up and filled the cluster

Certificate or credential expiry1 case

Organisation
  1. IL-0184 JupyterHub's KubeSpawner could not create containers and kubectl was refused because the API server and other internal certificates of a kubeadm cluster had expired
    dbhang2021