IL-0273A power disruption took GitHub's Redis clusters offline, the app could not boot, and GitHub served 503s for 2 hoursGitHub2016- Symptoms
At 00:23 UTC on 28 January 2016 GitHub became unavailable and returned HTTP 503 responses with the unicorn error page. On-call engineers received alerts for unreachable servers and a spike in exceptions related to Redis connectivity, after slightly over 25% of the servers and several network devices in the primary data center rebooted.
- Trigger
At 00:23 UTC a brief disruption in the systems that supply power to the servers and equipment of GitHub's primary data center rebooted slightly over 25% of the servers and several network devices.
- Root cause
- Component
- Contributing factor
- Detection
The reboots generated alerts to several on-call engineers, starting with notifications for unreachable servers and a spike in exceptions related to Redis connectivity.
- Remediation
- Worked with on-site facilities technicians to drain flea power from the failed servers and start them cold so their disks were visible
- Rebuilt the affected Redis clusters on alternate hardware
- Restored the Redis cluster data onto standby equipment and brought the Redis-server processes back online
- Removed the maintenance page after the HAProxy load balancers returned the recovered application servers to the pool
- Action items
- Update the server firmware with the known issue across the fleet
- Make tooling open issues automatically when new firmware updates are available, so their changelogs are reviewed
- Add tests that make sure application processes start even when certain external systems are unavailable
- Improve circuit breakers so functionality degrades gracefully when backend services are down
- Review the availability requirements of internal systems such as server provisioning so they are on par with user-facing systems
- Strengthen communication between teams during incidents
- Predefine escalation strategies for all-hands incidents
- Improve status messaging to users during incidents
- Lessons
Dependencies between components fail in new ways unless they are tested, and a power loss cannot be fully prevented, so the goal is fast and reliable recovery. The application should start without non-essential backends, and internal systems needed to recover from an outage, such as server provisioning, must be as reliable as the system being recovered.
This case involves In-memory cache and Data center power and cooling. kubegap audits a Kubernetes cluster for gaps like these, read-only, from Claude Code or Codex; its checks cite public reports like the ones in this library.