Cases2 cases
1 to 2 of 2
IL-0481RoCEv2 GIDs changed after RNIC port flaps, collapsing the communication collective and crashing LLM training jobsInfrawaves2026- Symptoms
In Infrawaves' RoCEv2 GPU training clusters, LLM training jobs crashed because their communication collective collapsed after an RNIC port flapped. The Global Identifier (GID) of the RDMA network card's port, which in RoCEv2 is expected to stay the same after initialisation, had changed: with the default OS network manager, NetworkManager, the port briefly lost its IP address while it was down, and the GID number was incremented even though the original IP address came back. The paper describes the GID shift as non-deterministic.
- Trigger
Ports of the RDMA network cards (RNICs) on the GPU servers flapped and were briefly down.
- Root cause
- Component
- Contributing factor
- Remediation
- Configured the IP addresses with the Ubuntu Networking service instead of NetworkManager, so a port down no longer removed the address or changed the GID
- Lessons
Host networking configuration is critical to the reliability of the collective communication library. In RoCEv2 a GID is expected to stay fixed after initialisation, but an IP configuration method that briefly drops the address when an RNIC port goes down can change it and bring down the training job. Changing the IP configuration method avoided the GID shift without the compatibility risks that driver-level patches carry in virtualised networks.
IL-0256Basecamp was fully down twice in two days as hardware load balancers crashed and routers lost sync after failover37signals2020- Symptoms
On Tuesday 1 September 2020 Basecamp could not be loaded at all for 17 minutes, from 9:51am to 10:08am Central Time (14:51–15:08 UTC), and nothing seemed to work. On Wednesday 2 September it happened again for 15 minutes, from 10:50am to 11:05am Central Time (15:50–16:05 UTC).
- Trigger
On 1 September the network links between the data centers went offline, and during the recovery a hardware load balancer crashed. On 2 September the primary load balancer in Virginia crashed again, and later its secondary crashed too.
- Root cause
- Component
- Contributing factor
- Remediation
- On 1 September, intervened by hand to get the network routers working with the standby load balancer
- On 2 September, fixed the same router and load balancer desynchronization by hand
- Action items
- Find the cause of the load balancer crash with the vendor and apply its bugfix
- Replace the hardware load balancers
- Reroute the redundant cross-datacenter network paths for proper circuit diversity
- Evaluate moving from hardware to software load balancers, which can be deployed in minutes
- Evaluate decentralizing the load balancer architecture to limit the impact of one failure
- Assess the systems for resilience, fragility and risk, and review the assessment process itself
- Lessons
Basecamp plans for failures like these and practises responses to catastrophic failures in its live systems, but three obscure issues in five days chained into overlapping failures. What caught the team by surprise were cascading failures that exposed unexpected fragility and hard paths to recovery, which Basecamp says it can prepare for.
These 2 cases involve Backbone network (WAN) and Host routes and routing rules. kubegap audits a Kubernetes cluster for gaps like these, read-only, from Claude Code or Codex; its checks cite public reports like the ones in this library.
By root cause1
Software defect2 cases
- Component
- Contributing factor
- Organisation