  1. Symptoms

    Right after the primary datacenter was switched from EQIAD to CODFW at 14:00 UTC on 20 September 2023, on-wiki search on all Wikimedia wikis became delayed or unavailable for a subset of users. At 14:08 the alert "CirrusSearch codfw 95th percentile latency - more_like" fired and reached IRC and the Search Platform email list as "PROBLEM alert - graphite1005/CirrusSearch codfw 95th percentile latency - more_like is CRITICAL".

    Trigger

    At 14:00 UTC the primary datacenter was switched from EQIAD to CODFW. more_like queries that were expected to go to eqiad, the non-primary datacenter, went to codfw instead, apparently because RESTBase sent them as POST rather than GET.

    Root cause
    Component
    Contributing factor
    Detection

    Automated monitoring caught the problem, but not quickly enough to prevent user-facing impact: the Grafana alert "CirrusSearch codfw 95th percentile latency - more_like" went to IRC and the Search Platform email list at 14:08. No one was paged; SREs were already watching closely because of the datacenter switchover. At 14:14 Hashar pinged #wikimedia-search and engineers began troubleshooting.

    Remediation
    • Banned the overloaded node elastic2044 from the Elasticsearch cluster
    Action items
    • Work out which Elasticsearch steps are needed before a datacenter switchover
    • Update the Elasticsearch section of the datacenter switchover documentation
    • Review the suggested switchover improvements in T285347 and decide whether to implement them
    • Make the RESTBase /related/{article} endpoint send GET instead of POST so the CirrusSearch query cache stays warm in both datacenters
    • Review the shard balance of busy wikis, especially enwiki_content
    Lessons

    Monitoring caught the problem, but not quickly enough to prevent user-facing impact. The heightened attention during the switchover meant the impact was recognised immediately, and banning a single node was quick and easy. The mitigation was not guided by an existing runbook, and the shards on the overloaded host were not checked before it was banned.

  2. Symptoms

    On 15 February 2019 a slave node of the AWS ElastiCache Redis Cluster behind Apollo, Grab's driver-side state machine for transport bookings, failed and had to be replaced. For about one minute only roughly 1 in 21 calls to Apollo succeeded, a call failure rate above 95% against the Redis Cluster, and Grab rides were significantly down.

    Trigger

    A slave node of Apollo's Redis Cluster failed and needed to be replaced.

    Root cause
    Component
    Contributing factor
    Lessons

    Having several replicas did not protect Apollo, because the client side, not the Redis Cluster server, caused the failure. Grab suggests three ways to avoid it: a separate Redis Cluster client used only for pipelining with RouteByLatency set to true, so pipelined reads go through the master nodes when latency is under 1ms, watching master CPU because they take more load; checking the error of each command in a pipeline instead of failing the whole call, so successful queries are not affected; and changing the Go-Redis library so that the pipeline path reloads the nodes' state when an error happens, as defaultProcessor already does.

Check your cluster for this