  1. Symptoms

    On May 31, 2018 from 21:53 UTC the metrics APIs of AppOptics and Librato returned a 5xx for a majority of incoming metric data. APM metrics and traces sent from AppOptics APM were affected, and many alert notifications were delayed.

    Trigger

    A power event in one of AWS's availability zones in us-east-1 cut off nodes in several critical parts of the AppOptics and Librato infrastructure, including the ZooKeeper node that was then the leader of the ensemble coordinating the Kafka brokers.

    Root cause
    Component
    Contributing factor
    Remediation
    • Restarted one ZooKeeper node by hand to force a leader election, after which the ensemble regained quorum
    • Restarted every Kafka broker in a rolling restart until all partitions were back online
    • Worked through the backlog, including the backlog of alerts, and resumed normal operations
    Action items
    • Isolate the Kafka clusters better across availability zones and regions
    • Stop sharing one ZooKeeper ensemble across Kafka clusters
    • Run game days on this failure and check whether newer Kafka versions fix it
    • Put in place more checks that notify the team earlier about subsystems that need extra help to recover
    Lessons

    Running services across several availability zones and more than one Kafka cluster did not isolate the pipeline from the failure of one zone, because partitions of different clusters sat in the same zones and the clusters shared one ZooKeeper ensemble. More operational monitoring of the subsystems that needed help to recover would have led to a faster recovery.

  2. Symptoms

    On Saturday 13 April 2013 at 8:11am Pacific Time, PagerDuty's on-call engineer was paged about one node of the notification dispatch system, and an attempt at 8:13 to bring the node back failed. Customers saw delayed notifications and 500 errors on PagerDuty's API endpoints.

    Trigger

    At 7:57am Pacific Time, according to AWS, a peering point in Northern California began to degrade, causing connectivity problems for the two AWS regions that PagerDuty used as two of its three datacenters.

    Root cause
    Component
    Contributing factor
    Detection

    The PagerDuty on-call engineer was paged at 8:11am about an issue with one node of the notification dispatch system, and at 8:18 monitoring detected multiple-provider failures for notifications.

    Remediation
    • Restarted most of the failed coordinator processes by hand
    • The notification dispatch system reached quorum again and processed all queued notifications
    Action items
    • Add more logging and aggregate logs into a single searchable source
    • Add a process watcher that restarts failed coordinator processes automatically
    • Build a dashboard that shows inter-host connectivity
    • Train engineering staff on Cassandra and ZooKeeper
    • Investigate moving off one of the AWS regions to a new hosting provider and datacenter that avoids a single point of failure
    Lessons

    Datacenters chosen to be independent and physically separate can still share a network peering point, and a design built to survive the loss of one datacenter did not survive losing two at once.

Check your cluster for this