  1. Symptoms

    On 19 August 2026 the first equipment-level signs in Nebius's us-central1 region appeared around 09:40 UTC: the InfiniBand fabric degraded and GPU over-temperature alerts began to accumulate. Customer reports followed shortly after 10:00. At 10:15 on-call engineers were paged on critical component temperature alerts, and the incident was declared at 10:21.

    Trigger

    A storm-related event at the data center building took the building management system offline and shut down the chilled-water cooling loop.

    Root cause
    Component
    Contributing factor
    Detection

    No facility-level alert fired, because the storm also disabled the building management system that monitors the facility. Engineers acted on component over-temperature alerts that paged on-call at 10:15 UTC, after InfiniBand degradation, GPU over-temperature alerts and customer reports; the temperature rise from about 09:15 was visible on dashboards but had no alert.

    Remediation
    • had the facility operator switch cooling to manual bypass mode and opened rack rear doors to vent heat
    • re-energised tripped racks, control-plane racks first
    • restored the regional infrastructure control plane by manual intervention
    • restarted block-storage host components to clear stale disk attachment state
    • raised the VM recovery rate limits by hand for the region-scale recovery
    • started the affected Managed Kubernetes control-plane instances by hand
    • applied a controlled stop and start to control-plane instances whose data disk had been left unattached
    • identified and started 104 customer VMs that the incident had stopped
    Action items
    • Complete a joint resilience review with the facility operator covering redundancy of facility-management and monitoring systems, cooling that keeps running when those fail, electrical protection of cooling equipment and on-site response
    • Add facility-level environmental alerting on cooling plant state and room temperature trend that pages on-call independently of the building management system
    • Set up a documented emergency escalation path with the facility operator, with an on-call contact tree and guaranteed response times
    • Define an emergency heat-load reduction procedure with criteria, ownership and mechanics for shutting down or degrading workloads during a cooling loss
    • Establish a dependency-ordered region cold-start procedure with clear ownership for each service layer
    • Run regular region-scale recovery drills that cover VMs, storage attachments and Managed Kubernetes clusters
    • Fix the disk-attachment bug that extended the Managed Kubernetes outage and deploy the fix to all production regions
    • Improve the recovery policies Compute users can configure, and move all Managed Kubernetes control-plane nodes to the improved policy
    • Automate reconciliation of stale storage attachment state after abrupt host failures
    • Remove in-region dependencies from monitoring startup and recovery, and extend cross-region monitoring
    • Make regional health checks used for global traffic management reflect real service availability
    Lessons

    Facility monitoring that runs on the same system it watches goes silent in exactly the failure it should report, and with no alert on the room temperature trend there was no practical window to shed heat load in a controlled way. A cold start of a whole region exercised recovery paths built for isolated failures: single-attempt VM recovery, conservative rate limits and stale disk attachments all needed manual work. The longest part of the outage was restoring customer resources, Managed Kubernetes control planes above all, so Nebius is extending its recovery drills to that layer.

  2. Symptoms

    On 10 September 2019 the Kubernetes API server of Wikimedia's Toolforge cluster did not come back after the maintain-kubeusers process restarted it at 18:30. To monitoring and to users the whole cluster looked down: Toolforge users could not launch tools with the webservice command on the Kubernetes backend or use kubectl, and an Icinga check against the "All k8s nodes healthy" endpoint started alerting at 18:45.

    Trigger

    At 18:30 the maintain-kubeusers process restarted the Kubernetes API server, which forced it to reconnect to etcd with a CA certificate that Puppet changes the night before had left mismatched with the etcd servers.

    Root cause
    Component
    Contributing factor
    Detection

    Automated monitoring: an Icinga alert on the toolschecker check http://checker.tools.wmflabs.org/k8s/nodes/ready, about "All k8s nodes healthy", fired at 18:45.

    Remediation
    • Rebooted the Kubernetes master and the etcd cluster, which did not help
    • Took a backup of etcd and reduced the etcd cluster to one node to rule out raft election flaps
    • Brought etcd back to full capacity through a full disaster recovery from the backup
    • Swapped the API server's CA certificate for the one from the etcd servers, which restored services until Puppet reverted it
    • Placed the etcd Puppet CA certificate in /var/lib/puppet/client/ssl/certs/ca.pem so Puppet kept the right CA
    Action items
    • Document the etcd cluster processes
    • Upgrade Toolforge Kubernetes to improve etcd and Kubernetes error reporting and stop needing an API server restart to add a tool
    • Make kube2proxy more resilient to API server failures
    • Audit the Puppet CA certificates so the tools project has no more than one
    • Make the Kubernetes control plane highly available
    Lessons

    Components that often misbehave, such as etcd, drew the responders to the wrong fix, and working on etcd instead of the CA certificates made the outage worse. Puppet-managed certificates are risky, and very old Kubernetes versions log errors that are hard to read. The failure was hard to find because it surfaced at an API server restart rather than at the Puppet change, because the etcd cluster had long-standing undocumented quirks, and because no disaster recovery or node replacement procedure was written down for etcd.