  1. Symptoms

    On Friday 17 November 2023, the local government administrative computer services in Korea stopped working, and the Government24 service of the National Information Resources Service was down until the next morning.

    Root cause
    Component
    Contributing factor
    Remediation
    • Replaced the two malfunctioning L4 devices with higher-performance devices, tested them and resumed Government24 at 09:00 on 18 November
    • Moved the connection on the defective port of the Daejeon center router to another port at 07:00 on 19 November
    • Swapped out the module of the router that had the fault
    Action items
    • Inspect all old equipment that may have similar port defects
    • Revise the incident handling manual so the public is told about an outage quickly
    • Announce the status of service recovery quickly through various means
    • Build integrated monitoring of critical service systems and related equipment to catch signs of failure early
    • Form a standing incident response team to send into major outages
    • Prepare administrative measures and a response manual so administrative services can still be provided when core digital government services stop
    • Name a paralysis of the national computer network as a type of disaster and accident, managed from prevention to recovery
    • Build a government-wide crisis response system for linked information systems and strengthen the control tower for outage prevention and response
    • Improve how public IT projects are run and managed, replace hardware and software past their service life quickly and make project pricing realistic
    • Reduce the reliance on outsourcing for developing and operating information systems and bring digital talent into government
    • Review the redundancy, recovery systems and network configuration of the systems in the National Information Resources Service, and its organisation
    • Work with manufacturers on a way to find and monitor failures of internal parts earlier
    Lessons

    The team said that hardware faults like this defective port also happen in the private sector, and that failures of parts inside a device are hard to catch in advance with basic monitoring and daily visual checks. Redundancy did not help because it takes over only when a whole device stops working, and a module that failed only in part did not make the device count as abnormal. The impact was wide because the defective port carried traffic for all the services.

  2. Symptoms

    On 2 November 2020 the Cloudflare API and dashboard were degraded for six hours and 33 minutes. The success rate of API queries dropped at times to 75%, and the dashboard was up to 80 times slower than normal, while Cloudflare's edge network kept working.

    Trigger

    At 14:43 UTC a network switch in a control plane data center partly failed: it kept LACP and BGP running but stopped forwarding some packets, and it recovered on its own six minutes later.

    Root cause
    Component
    Contributing factor
    Detection

    At 14:43 UTC alerts fired because the misbehaving switch was unreachable to pings. Engineers then saw that the primary authentication database was overwhelmed.

    Remediation
    • Shed load from the primary authentication database by slowing SSL certificate pushes to the edge, emails and other features
    • Moved API traffic that could use read replicas to the secondary data center by hand
    • Sent authentication calls fully back to the primary data center when the dashboard got worse
    • Rebuilt the first database replica, which put itself back into service at 21:20 UTC and returned performance to normal
    • Ramped the turned-down services back up so asynchronous processing could catch up
    Action items
    • Remove the cluster management limitation that requires rebuilding all replicas after a primary is promoted
    • Redesign the user sessions system so dashboard traffic can be steered between data centers
    • Change the auto-remediation configuration so a database replica is not promoted so quickly
    • Tune each system involved to be more resilient to failures of its dependencies
    Lessons

    Every system in the chain had redundancy and none failed completely; each only degraded, which made the chain of events much harder to model and foresee. Automating replica promotion so that it could trigger on a minute's notice had been a point of pride, but for at least one database a fast promotion can do more harm than the failure it answers. Most general-purpose cluster managers use Raft or Paxos rather than Byzantine fault tolerant protocols, accepting a rare failure mode in exchange for a protocol that is simpler to implement correctly and debug.