  1. Symptoms

    On 19 August 2026 the first equipment-level signs in Nebius's us-central1 region appeared around 09:40 UTC: the InfiniBand fabric degraded and GPU over-temperature alerts began to accumulate. Customer reports followed shortly after 10:00. At 10:15 on-call engineers were paged on critical component temperature alerts, and the incident was declared at 10:21.

    Trigger

    A storm-related event at the data center building took the building management system offline and shut down the chilled-water cooling loop.

    Root cause
    Component
    Contributing factor
    Detection

    No facility-level alert fired, because the storm also disabled the building management system that monitors the facility. Engineers acted on component over-temperature alerts that paged on-call at 10:15 UTC, after InfiniBand degradation, GPU over-temperature alerts and customer reports; the temperature rise from about 09:15 was visible on dashboards but had no alert.

    Remediation
    • had the facility operator switch cooling to manual bypass mode and opened rack rear doors to vent heat
    • re-energised tripped racks, control-plane racks first
    • restored the regional infrastructure control plane by manual intervention
    • restarted block-storage host components to clear stale disk attachment state
    • raised the VM recovery rate limits by hand for the region-scale recovery
    • started the affected Managed Kubernetes control-plane instances by hand
    • applied a controlled stop and start to control-plane instances whose data disk had been left unattached
    • identified and started 104 customer VMs that the incident had stopped
    Action items
    • Complete a joint resilience review with the facility operator covering redundancy of facility-management and monitoring systems, cooling that keeps running when those fail, electrical protection of cooling equipment and on-site response
    • Add facility-level environmental alerting on cooling plant state and room temperature trend that pages on-call independently of the building management system
    • Set up a documented emergency escalation path with the facility operator, with an on-call contact tree and guaranteed response times
    • Define an emergency heat-load reduction procedure with criteria, ownership and mechanics for shutting down or degrading workloads during a cooling loss
    • Establish a dependency-ordered region cold-start procedure with clear ownership for each service layer
    • Run regular region-scale recovery drills that cover VMs, storage attachments and Managed Kubernetes clusters
    • Fix the disk-attachment bug that extended the Managed Kubernetes outage and deploy the fix to all production regions
    • Improve the recovery policies Compute users can configure, and move all Managed Kubernetes control-plane nodes to the improved policy
    • Automate reconciliation of stale storage attachment state after abrupt host failures
    • Remove in-region dependencies from monitoring startup and recovery, and extend cross-region monitoring
    • Make regional health checks used for global traffic management reflect real service availability
    Lessons

    Facility monitoring that runs on the same system it watches goes silent in exactly the failure it should report, and with no alert on the room temperature trend there was no practical window to shed heat load in a controlled way. A cold start of a whole region exercised recovery paths built for isolated failures: single-attempt VM recovery, conservative rate limits and stale disk attachments all needed manual work. The longest part of the outage was restoring customer resources, Managed Kubernetes control planes above all, so Nebius is extending its recovery drills to that layer.

  2. Symptoms

    From 16:18 UTC on 28 May 2026 the Lucidworks AI hosted LLMs in the us-southcarolina region were unavailable: queries to llama-3-8b-instruct, llama-3v2-3b-instruct and phi-4-multimodal-instruct returned 500 or 429 errors. Search, embedding models, the Lucidworks Platform UI and passthrough LLM calls kept working.

    Trigger

    A routine Kubernetes patch upgrade on a cluster in us-southcarolina cycled its node pools one after another in quick succession.

    Root cause
    Component
    Contributing factor
    Remediation
    • Deleted the degraded replacement head node that could not pull container images
    • Waited for the LLM image pulls to finish on the replacement nodes
    • Launched new nodes with the required LLM images and redirected Lucidworks AI traffic to them
    Action items
    • Upgrade clusters that host LLM workloads in sequence, with each node pool fully healthy before the next one is upgraded
    • Investigate image pre-loading, such as pre-baked disks or image streaming, for large ML model images
    • Open a support ticket with the cloud provider about the abnormal Docker pull times
    • Coordinate Kubernetes maintenance windows with LLM service owners so they do not clash with ongoing deployments
    • Build tooling to force a Ray cluster failover to the blue or green state instead of waiting for Ray to settle it
  3. Symptoms

    From 17 October 2024, packets through the vSwitch that joined Namespace's bare metal machines at one provider in the fra3 region were dropped at random. Retries in TCP, QUIC and the Namespace control plane hid most of it, but the SLO error budget for latency targets on key interactions began to burn.

    Trigger

    Random packet drops on the bare metal provider's vSwitch from 17 October 2024; for the second outage, a rate of Kubernetes changes that the slow NVMe on one control plane node could no longer keep up with.

    Root cause
    Component
    Contributing factor
    Detection

    SLO-based monitoring of latency targets showed the error budget burning while retries hid the individual packet drops.

    Remediation
    • diverted all customer traffic from fra3 to other regions
    • connected each provider machine to the zrh1 cluster over Wireguard instead of the vSwitch
    • repaved every fra3 machine with a new identity, certificates and encryption-at-rest keys, dropping regional caches to recover faster
    • cloned existing datasets in a more distributed way to speed up repaving the machines
    • added machines back to the new region in batches and returned the region to the compute pool
    • redirected workloads away from zrh1 during the second outage
    • cloned the failing control plane node's key state to a higher-capacity node that took over its role and IP address
    Action items
    • Credit all instances that ran during the outages back to customers
    • Build up backup regions and solutions so a similar event has options that do not affect customers
    Lessons

    Running hot with a delayed hardware delivery left no room to take a region out, so fixing a provider network fault turned into a global capacity shortage. After one outage the team was anchored on its cause and first looked for network problems in the second outage, which had a different cause: a control plane node whose disk could not keep up with the Kubernetes change rate.

  4. Symptoms

    At 16:40 UTC on 19 April 2024 CoW Protocol's mainnet production environment stopped producing settlements; the outage officially began then.

    Trigger

    During a cluster capacity expansion, the Infrastructure as Code automation updated the AWS VPC CNI plugin, because the CNI version was not hardcoded in the IaC and the IaC library version had recently changed.

    Root cause
    Component
    Contributing factor
    Detection

    The CNI version mismatch was identified as the cause at 17:03 UTC, 23 minutes after settlements stopped.

    Remediation
    • upgraded the Kubernetes cluster
    • set up new node groups with a new version of the networking plugin
    Lessons

    Versions in IaC scripts should be specified explicitly so an automation run cannot update a component such as the CNI plugin unintentionally. Changes in production need change management that is easy to revert.

  5. Symptoms

    At 18:56 PDT on 23 June 2022 (01:56 UTC on 24 June) several models went offline at once: some fine-tuned curie and davinci models, the Codex beta models code-davinci-001 and code-cushman-001, the legacy GPT models curie, babbage and ada, and all Embeddings models.

    Trigger

    A destructive operation on one of the three production clusters, caused by human error that the existing safeguards did not catch, took the whole cluster offline.

    Root cause
    Component
    Contributing factor
    Remediation
    • re-allocated the models from the lost cluster to the remaining two clusters
    • rebuilt the VPN link with Azure support after losing the connection to AKS during cluster setup
    • built workarounds with Azure support after losing the connection to Azure Private Link
    • tore down the cluster and rebuilt it from scratch after the upgraded Kubernetes version broke the ingress
    • moved traffic back into the rebuilt cluster between 05:30 and 06:30 PDT
    Action items
    • Add checks and locks so that this and similar production-critical infrastructure cannot be modified by accident
    • Add better visibility into the operations being performed and make parts of the system more lexicographically distinct
    • Keep working with Azure on the AKS network connectivity issues so they do not disrupt new cluster operations
    • Update playbooks with the new cluster failure modes and change the setup steps for new clusters and infrastructure
    • Upgrade Kubernetes systematically and set aside time so the clusters do not fall behind again
    • Shard fine-tuned models across multiple clusters and work towards more automatic cross-cluster replication
    • Distribute and replicate Azure Blob Storage so fine-tuned models load faster and more reliably
    • Finish rolling out node-to-node caching to relieve Azure Blob Storage bottlenecks
    • Change how model weights are stored so they are more efficient and faster to load
    Lessons

    Losing one of three clusters exhausted the GPU headroom, and GPUs could not be added on short notice, so full recovery depended on bringing the same cluster back. Rebuilding it exposed a deferred Kubernetes upgrade: the newer version broke the ingress, and because AKS cannot downgrade there was no way back except a full rebuild. Recovering many large models at once is limited by the bandwidth of the storage they load from, and the caches that normally hide this do not help when everything moves to a different cluster.

Check your cluster for this

These 9 cases involve Node pool and etcd. kubegap audits a Kubernetes cluster for gaps like these, read-only, from Claude Code or Codex; its checks cite public reports like the ones in this library.

By root cause7

Dependency failure1 case

Organisation
  1. IL-0133 A storm shut down cooling at Nebius's us-central1 data center, and a disk hot-plug bug kept Managed Kubernetes control planes down for hours after power returned
    Nebius2026

Faulty deployment1 case

Organisation
  1. IL-0237 A Kubernetes patch upgrade evicted every Ray Serve head and worker pod at once, and Lucidworks hosted LLMs went down

Cloud provider outage3 cases

  1. IL-0084 Packet drops on a bare metal provider's vSwitch forced Namespace to rebuild its fra3 region and left global capacity short, and the next day slow NVMe writes on a control plane node drove the Kubernetes API server to very high CPU
  2. IL-0193 A GCP persistent disk degradation took down a Cassandra StatefulSet whose OrderedReady policy blocked recovery, and Metrictank could not reconnect to the recreated pods, causing a 23-hour Graphite query outage
  3. IL-0014 A GKE upgrade to a withdrawn version stalled on slow drains and a stuck node pool, then broke an ingress and confused the HPA

Configuration change1 case

Organisation
  1. IL-0114 An unpinned AWS VPC CNI plugin was updated automatically during a capacity expansion, leaving new pods Pending without IP addresses and stopping CoW Protocol settlements for about 3.5 hours

Operator error1 case

Organisation
  1. IL-0115 One of OpenAI's three production AKS clusters went offline through a human error, and rebuilding it took 10½ hours because an AKS Kubernetes upgrade broke the ingress and AKS cannot be downgraded
    OpenAI2022

DNS or network fault1 case

Organisation
  1. IL-0199 A non-essential container exceeding its memory limit made GitHub's production pods unavailable, and their restarts failed because a DNS maintenance change had left the clusters unable to reach the image registry
    GitHub2020

Software defect1 case

Organisation
  1. IL-0003 linkerd lost Kubernetes service discovery after an etcd reconfiguration, and restarting every linkerd instance turned failed payments into a full platform outage
    Monzo2017