Cases9 cases

1 to 5 of 9

  1. Symptoms

    At about 17:00 JST on Thursday 16 July 2026, Datadog alerted, and at almost the same time 5xx errors began to rise on the Amazon CloudFront distributions that used VPC Origins connections. Builder Work, ANDPAD's job and career service for the construction industry, became almost entirely unreachable.

    Trigger

    The Amazon CloudFront VPC Origins feature failed; AWS Health later reported a capacity constraint in an internal shared subsystem that manages connections for VPC Origins.

    Root cause
    Component
    Contributing factor
    Detection

    Datadog raised an alert, and at about the same time 5xx errors were seen rising on the CloudFront distributions that used VPC Origins.

    Remediation
    • Decided to route traffic temporarily through an internet-facing ALB without CloudFront
    • Recreated the internet-facing Ingress, attached it to the Argo Rollouts Rollout resource and promoted it
    • Created a regional WAF for the ALB with the security team
    • Created a new IngressClass with the ACM certificate, the WAF and access log settings
    • Added Ingresses for normal traffic, the admin screens and redirects, which restored routing
    Action items
    • Return to the CloudFront and VPC Origins layout while keeping a way to switch to internet-facing in code
    • Keep the internet-facing ALB, limited to approved CIDRs through spec.inboundCIDRs in IngressClassParams, so commenting out securityGroupInboundCidrs in values.yaml opens it to 0.0.0.0/0
    • Point the Terraform-managed Route53 A record back to CloudFront and keep the ALB alias commented out in code, so uncommenting and applying switches DNS to the ALB
    Lessons

    VPC Origins keeps the ALB off the internet and simplifies the traffic path, but it makes the service depend on an AWS-managed shared subsystem, and when that fails the service stops even though CloudFront is healthy. ANDPAD kept VPC Origins and instead prepared the escape route ahead of time, accepting the cost of an ALB that always runs, because recreating the Ingress and attaching it to the Rollout had taken so long during this incident.

  2. Symptoms

    On 4 March 2026 customers of the IONOS Container Registry got 504 Gateway Timeout errors when pushing or pulling container images, and deployments that relied on the registry were blocked. The status page first reported an increased error count on the registry at 09:23 UTC, saying customers might be unable to pull images.

    Trigger

    A migration combined with a temporary capacity constraint placed two critical control plane components on the same proxy instance, despite anti-affinity rules; the shared proxy then reached its concurrent connection limit.

    Root cause
    Component
    Contributing factor
    Remediation
    • Rolled back a component of the Kubernetes control plane to an earlier version
    • Provisioned additional proxy capacity
    • Moved the affected control plane components onto separate proxy instances
    Action items
    • Redesign registry-to-API connectivity so each node uses its own local proxy
    • Adjust alert thresholds to warn before proxy connection use approaches capacity
    • Deploy more infrastructure clusters and redistribute registries so no cluster exceeds safe capacity, with automation that keeps balancing load
  3. Symptoms

    On 21 October 2025 at 21:45 UTC a change to timeout handling was deployed to the feature flags service, and two minutes later automated monitoring reported higher error rates. The change was rolled back by 21:49, but error rates stayed high: about 38% of flag evaluation requests in the US datacenter returned errors. At 22:30 Redis metrics showed memory exhaustion on ElastiCache, at 22:35 Postgres connections spiked, and at 22:45 the team found a massive data transfer from Postgres into Redis. The main PostHog application was affected as well, because it shares the Redis instance with the flags service.

    Trigger

    On 21 October a deployment meant to reduce timeout errors (PR #39821); on 24 October the deployment of IP-based rate limiting (PR #40074) that saw all traffic as coming from the load balancer's IP; on 28 October an unrelated routine deployment that rolled the feature flag pods in the US region.

    Root cause
    Component
    Contributing factor
    Detection

    On 21 October automated monitoring detected higher error rates two minutes after the deploy. On 24 October no alert existed for 429 errors, and the team learned of the incident from customer reports that began at 18:10 UTC, a 62-minute detection delay. On 28 October on-call received a high error count alert. On 29 October the incident was reported with higher error rates and latency. No alert existed for CPU pressure, so the CPU saturation behind all three incidents was not seen directly.

    Remediation
    • rolled back the timeout handling change within 2 minutes on 21 October, which did not stop the errors
    • throttled connections and Redis writes on 21 October
    • halted the rollout on 28 October, scaled the US flags pods to zero until Redis recovered, then scaled them back gradually
    • rolled back hardware changes on 30 October at 00:03 UTC, which removed most errors but not the latency
    • increased the pod resource requests and adjusted the Kubernetes fleet size so fewer pods ran on each node
    • added retry limits to Envoy between the load balancer and the service
    • moved database connection timeouts and other critical settings to runtime configuration and raised the timeout values
    • added per-node and per-pod CPU alerts at 80% sustained for 5 minutes that page on-call
    Action items
    • Form a strike team from the flags, ingestion and infrastructure teams to review the application and infrastructure for remaining bottlenecks
    • Investigate separating the flags Redis instance from the application Redis instance
    • Before re-enabling ArgoCD sync, align the flags service chart configuration with the values in ArgoCD and define the deployment and Redis strategy
    • Make the feature flags team hard code-owners for flags-related code
    • Build a dashboard of key flag metrics with runbook links and update the feature flag runbooks
    • Add missing alerts on existing service and infrastructure metrics
    • Make readiness checks validate dependencies that degrade under load, for example by pinging the database
    • Rate-limit cache population so it cannot overwhelm Redis
    • Monitor connection pools with automatic throttling near exhaustion and limit concurrent connections
    • Build a production-scale load testing framework
    • Build progressive rollout infrastructure to limit blast radius
    • Document Postgres-to-Redis data flows and write runbooks for data transfer storms
    Lessons

    Nodes that are small relative to pod requests let the scheduler pack many pods on each node, and the resulting CPU saturation showed up three different ways: excessive parallelism, connection pool exhaustion and slow queries. Treating each symptom separately let the problem return; right-sizing the pods and nodes fixed all three. CPU must be alerted on from the start. Unbounded Envoy retries and unbounded cache population amplified the overload, and a Redis instance shared with the main application spread a flags problem to the main application. A rollback did not end the incident, because the data transfer and resource exhaustion it had started kept running.

  4. Symptoms

    From about 10:30 UTC on 30 August 2023, customers had trouble accessing or using Azure, Microsoft 365 and Power Platform services in Australia East. The affected Azure services included Azure Kubernetes Service (AKS) along with storage, SQL Database, Cosmos DB, virtual machines and Azure Resource Manager.

    Trigger

    At 08:41 UTC a lightning strike on electrical infrastructure about 18 miles away caused a utility voltage sag that shut down the cooling chillers of datacenters in one Australia East availability zone; 13 chillers failed to restart automatically and five could not be restarted, so two data halls overheated and their infrastructure was shut down.

    Root cause
    Component
    Contributing factor
    Detection

    Cosmos DB impact was detected by monitoring at 10:47 UTC, first automated communications went to Azure Service Health at 10:48 UTC, the public Azure Status page was updated at 11:30 UTC, and all subscriptions in Australia East were sent portal communications at 11:36 UTC.

    Remediation
    • shut down the remaining networking, compute and storage in the two affected data halls so the chilled water loop could cool down
    • restarted the five chillers manually at 12:12 UTC
    • restored power to all hardware by 15:10 UTC and brought infrastructure back in phases
    • restored AKS operations through the recovery of the SQL Database operation queue, with no other mitigation
    Action items
    • AKS: convert all operation queue SQL Database databases to be zone redundant (estimated September 2023)
    • AKS: replace all cross-region SQL Database queue usage with zone-redundant Service Bus queues (estimated September 2023)
    • Change the control timing logic of the Chiller Management System so chillers do not fail to restart after voltage fluctuations
    • Change the emergency procedure for manual restarts of simultaneous chiller failures from an adjacent sequence to a load-based sequence per data hall
    • Increase technician staffing at the datacenter as a temporary measure for manual chiller restarts
    • Storage: optimise the large-scale recovery process and update troubleshooting guides (estimated December 2023)
    • Azure Service Fabric: improve reliability of SQL Database tenant ring recovery (estimated December 2023)
    • SQL Database: review the trigger criteria of auto-failover groups (estimated October 2023)
    • SQL Database: upgrade internal tooling to enable mass migration of databases (estimated December 2023)
    • Cosmos DB: optimise Service Managed Failover for single-region-write accounts (estimated November 2023)
    • ARM: complete the migration of its storage layer to the zonally redundant architecture (estimated December 2023)
    • Incident management: harden readiness, process and playbook for power-down scenarios (estimated October 2023)
    Lessons

    A control plane spread across availability zones still fails with a zone when one of its dependencies, here the SQL Database operation queue, is not zone redundant. When a second region uses the same database, the failure crosses into that region as well. Workloads already running were not expected to be affected; what stopped was everything that needs the managed service's control plane, such as scaling and cluster changes.

  5. Symptoms

    About two minutes after an engineer started the Kubernetes 1.23 to 1.24 upgrade of the cluster running Reddit's legacy stack, just after 19:00 UTC, the site stopped. The CDN edge request graph, which is kept separate from the cluster, showed traffic by status collapsing. Users saw the error page, a homepage with no posts, or plain errors.

    Trigger

    An in-place upgrade of the legacy cluster from Kubernetes 1.23 to 1.24; in 1.24 the node-role.kubernetes.io/master label is removed even from running clusters.

    Root cause
    Component
    Contributing factor
    Detection

    The site broke about two minutes into the upgrade; an incident was opened immediately and responders were on the call within three minutes, working from CDN edge graphs because the cluster's own metrics were gone.

    Remediation
    • deleted the Open Policy Agent webhook configurations to stop API server timeouts
    • terminated all worker nodes of the cluster
    • restored the control plane from the pre-upgrade backup onto the first control plane node
    • switched off the cluster autoscaler until the control plane was stable
    • generated new TLS certificates so replacement control plane nodes could join etcd
    • brought traffic back in steps from 1% to 100%
    • restarted legacy services that had been stopped by hand
    Action items
    • Codify cluster configuration so every choice has a record, and document in detail what cannot be codified
    • Standardise components across clusters and replace bespoke configurations
    • Build tooling to manage the lifecycle of whole clusters so they can be recreated or replicated
    • Add pre-production clusters that can be tested with confidence
    • Improve the backup restore process and make cluster upgrades safe
    Lessons

    Configuration that exists only in a live cluster, edited by hand through a special tool, can be forgotten, as the route reflector setup was, and then break on an upgrade nobody connects it to. A Kubernetes upgrade cannot be reverted without a restore, so the restore procedure has to be kept current and practised. Consistent, codified clusters are what make upgrades testable; bespoke clusters keep producing outages.

Check your cluster for this

These 9 cases involve Kubernetes API server and Database. kubegap audits a Kubernetes cluster for gaps like these, read-only, from Claude Code or Codex; its checks cite public reports like the ones in this library.

By root cause4

Cloud provider outage2 cases

  1. IL-0438 Builder Work became almost entirely unreachable with 504 errors when the Amazon CloudFront VPC Origins feature failed
    ANDPAD2026
  2. IL-0145 A power sag and chiller failure in one Australia East availability zone took down the AKS control plane's compute and its non-zone-redundant SQL Database operation queue, blocking AKS create, update and delete operations in Australia East and Australia Southeast

Capacity exhaustion5 cases

  1. IL-0465 IONOS Container Registry image pushes and pulls failed with 504 Gateway Timeout
  2. IL-0100 PostHog's feature flags pods were packed onto Kubernetes nodes that were too small for their CPU requests, and CPU saturation above 90% caused three outages in ten days through Redis overload, connection pool exhaustion and slow queries
  3. IL-0002 CI builder pods could not get AWS IAM credentials because kubelet fell minutes behind its API rate limit
  4. IL-0064 CPU-heavy pods packed onto one Google Cloud node drove it to kernel panics, and the crash moved from node to node until the site was down
  5. IL-0031 Kubernetes API server OOM-killed, leaving the Skipper ingress without routes; the talk points to a misconfigured CronJob manifest

Breaking change in an upgrade1 case

Organisation
  1. IL-0060 Kubernetes 1.24 upgrade removed the master node label that Calico route reflectors selected on, dropping all pod routes and taking Reddit down for 314 minutes
    Reddit2023

Software defect1 case

Organisation
  1. IL-0003 linkerd lost Kubernetes service discovery after an etcd reconfiguration, and restarting every linkerd instance turned failed payments into a full platform outage
    Monzo2017