  1. Symptoms

    At about 13:40 UTC on 11 January 2023, alerts started firing for most SourceHut services being unavailable, along with one for remilia.sr.ht, the physical host that is SourceHut's main database server. The database server could not be reached remotely at all.

    Trigger

    remilia.sr.ht, the main database server, suffered a hardware failure at about 13:38 UTC.

    Root cause
    Component
    Contributing factor
    Detection

    Alerts fired at about 13:40 UTC for most services and for remilia.sr.ht itself, after Prometheus started failing to scrape remilia at 13:38.

    Remediation
    • Sent SourceHut's emergency on-call contact in the datacenter area to go on site
    • Moved remilia's disks into the chassis of build worker cirno1.sr.ht and brought it online as remilia
    Action items
    • Make the off-site database copy able to serve as a failover database host
    • Re-prioritize the migration to the EU
    • Set up new database failover
    • Add a new EU build worker to backfill build capacity
    • Record a better hardware inventory for future reference
  2. Symptoms

    From 20:18 UTC on 11 June 2022, OpenStreetMap.org was unavailable: all of its services hosted in Amsterdam, including www, the API, the wiki and planet, had no connectivity to the Internet. The outage began 18 minutes into Equinix's planned maintenance of power feed A at the Amsterdam data centre.

    Trigger

    Equinix's planned 5-year maintenance of power feed A in Amsterdam, which started at 20:00 UTC on 11 June 2022.

    Root cause
    Component
    Contributing factor
    Remediation
    • Waited for the end of the Equinix power feed A maintenance window instead of failing over to Dublin or moving the uplink; connectivity returned at 03:45 UTC
    Action items
    • Acknowledge ongoing outages faster
    • Add monitoring and alerting of switch PSU and FAN states
    • Replace the Cisco SG550X-48 switches and the Redundant Power System with Juniper EX4300 switches with redundant power supplies
    • Install out-of-band access equipment with dual power feeds in Amsterdam
    • Install redundant uplinks
    • Make site failover easier, less manual and lower risk
    • Introduce an on-call pager system for the operations SRE
    • Expand the SRE team
    • Continue and formalise fail-over tests for power, network, upstream link and service outages