  1. Symptoms

    On 19 August 2026 the first equipment-level signs in Nebius's us-central1 region appeared around 09:40 UTC: the InfiniBand fabric degraded and GPU over-temperature alerts began to accumulate. Customer reports followed shortly after 10:00. At 10:15 on-call engineers were paged on critical component temperature alerts, and the incident was declared at 10:21.

    Trigger

    A storm-related event at the data center building took the building management system offline and shut down the chilled-water cooling loop.

    Root cause
    Component
    Contributing factor
    Detection

    No facility-level alert fired, because the storm also disabled the building management system that monitors the facility. Engineers acted on component over-temperature alerts that paged on-call at 10:15 UTC, after InfiniBand degradation, GPU over-temperature alerts and customer reports; the temperature rise from about 09:15 was visible on dashboards but had no alert.

    Remediation
    • had the facility operator switch cooling to manual bypass mode and opened rack rear doors to vent heat
    • re-energised tripped racks, control-plane racks first
    • restored the regional infrastructure control plane by manual intervention
    • restarted block-storage host components to clear stale disk attachment state
    • raised the VM recovery rate limits by hand for the region-scale recovery
    • started the affected Managed Kubernetes control-plane instances by hand
    • applied a controlled stop and start to control-plane instances whose data disk had been left unattached
    • identified and started 104 customer VMs that the incident had stopped
    Action items
    • Complete a joint resilience review with the facility operator covering redundancy of facility-management and monitoring systems, cooling that keeps running when those fail, electrical protection of cooling equipment and on-site response
    • Add facility-level environmental alerting on cooling plant state and room temperature trend that pages on-call independently of the building management system
    • Set up a documented emergency escalation path with the facility operator, with an on-call contact tree and guaranteed response times
    • Define an emergency heat-load reduction procedure with criteria, ownership and mechanics for shutting down or degrading workloads during a cooling loss
    • Establish a dependency-ordered region cold-start procedure with clear ownership for each service layer
    • Run regular region-scale recovery drills that cover VMs, storage attachments and Managed Kubernetes clusters
    • Fix the disk-attachment bug that extended the Managed Kubernetes outage and deploy the fix to all production regions
    • Improve the recovery policies Compute users can configure, and move all Managed Kubernetes control-plane nodes to the improved policy
    • Automate reconciliation of stale storage attachment state after abrupt host failures
    • Remove in-region dependencies from monitoring startup and recovery, and extend cross-region monitoring
    • Make regional health checks used for global traffic management reflect real service availability
    Lessons

    Facility monitoring that runs on the same system it watches goes silent in exactly the failure it should report, and with no alert on the room temperature trend there was no practical window to shed heat load in a controlled way. A cold start of a whole region exercised recovery paths built for isolated failures: single-attempt VM recovery, conservative rate limits and stale disk attachments all needed manual work. The longest part of the outage was restoring customer resources, Managed Kubernetes control planes above all, so Nebius is extending its recovery drills to that layer.

  2. Symptoms

    The day began with an alert that several instances of the Redis cluster were running out of disk space. That part was fixed quickly. The outage came an hour later: right after the Redis StatefulSet was deleted and recreated at 8:10 UTC, Kubernetes restarted every Redis pod within about five minutes, and problems started to appear.

    Trigger

    To make Git match the volumes that had been resized by hand, the Redis StatefulSet was deleted with orphan (non-cascading) deletion and recreated with the new storage template; Kubernetes reconciled the new spec by restarting the entire Redis cluster.

    Root cause
    Component
    Contributing factor
    Detection

    An alert about Redis instances running out of disk space started the work; the outage itself showed up as backend errors about Redis connections right after the StatefulSet was recreated.

    Remediation
    • made the Redis masters forget obsolete node identities, reset the affected replicas and rejoined them, then waited for replication to catch up
    • identified the component that was actually running out of memory, scaled the backend service and raised memory limits for that component
    • temporarily relaxed probes so backend instances took traffic immediately instead of flapping between ready and not ready
    • reverted the temporary workarounds at 10:00 UTC
    Action items
    • Add startup probes so a Redis pod is not marked ready until its dataset is loaded
    • Build an own control plane for Redis that handles restarted pods stuck to an old master address
    • Reduce dependence on the single Redis cluster: move some important data to other stores, such as a separate Redis cluster per server, and use Kafka for some backend components
    Lessons

    The disk resize was not the problem; the cleanup afterwards was. An immutable field pushes operators toward deleting and recreating the controller, and that can set off a full reconcile. Startup and readiness probes are what slow a rolling restart down to a safe pace; without them a distributed store restarts in the most fragile way. Recovery plans must expect a cluster to heal slowly, and dependent services need to degrade gracefully while it does.

  3. Symptoms

    Nodes that already existed kept running, but every new node, spot or standard, on either v1.32 or v1.33, failed to initialise and could not join the cluster. Spot nodes that were preempted and recreated never came back, so services degraded progressively: background workers on spot instances, reporting services and order allocation stopped completely, and the APIs on existing nodes kept answering but could not scale for load spikes.

    Trigger

    Google upgraded the GKE control plane from v1.32.x to v1.33.2 at the version deprecation deadline, although auto-upgrade was disabled on the node pools.

    Root cause
    Component
    Contributing factor
    Remediation
    • Created a new GKE cluster at v1.33, the version of the forced upgrade
    • Upgraded Istio to 1.27.1 for Kubernetes 1.33 compatibility
    • Updated the cert-manager configuration for Kubernetes 1.33
    • Migrated all production workloads to the new cluster and verified pod scheduling, DNS resolution, PVC mounting and external integrations
    • Decommissioned the broken cluster
    Action items
    • Configure all clusters to use the GKE stable release channel
    • Implement a separate management cluster for Argo CD, monitoring and other control components (Q4 2025)
    • Review spot instance usage for critical workloads and add on-demand fallback pools
    • Document the SRE upgrade procedure: management cluster first, production after a monitoring period of several days
    • Document a Kubernetes, Istio and cert-manager compatibility matrix
    • Create an automated upgrade testing pipeline
    • Reserve static IPs for quick migrations
    • Pin versions of Istio, cert-manager, CSI and DNS addons
    • Stay current with stable releases and regularly check GKE alerts and announcements to avoid deprecation deadlines
    Lessons

    GKE upgrades the control plane at a version's deprecation deadline even when auto-upgrade is disabled, so staying inside the supported version window is how to avoid a forced upgrade. A control plane upgrade can leave existing nodes healthy while every new node fails, and spot nodes that cannot rejoin after preemption turn this into cascading failures. Relying heavily on spot instances for critical workers turned a node join failure into a progressive outage. Kubernetes upgrades have to be planned together with dependent components such as Istio and cert-manager, and without a standby cluster on the same provider there was no immediate failover; the only recovery left was building a new cluster.

  4. Symptoms

    During peak hours, when Mercari's GKE clusters handle very high request rates, the platform team saw kube-dns reaching its limits. DNS query rates were high enough to overwhelm the kube-dns service.

    Trigger

    Peak-hour traffic on the GKE clusters produced more DNS queries than the few kube-dns pods could answer.

    Root cause
    Component
    Contributing factor
    Detection

    During peak hours the team saw frequent NXDOMAIN and truncated-response errors and recurring "failed to refresh DNS cache" errors on the clusters, which showed that kube-dns had reached its limits.

    Remediation
    • deployed NodeLocal DNSCache on the Laboratory GKE cluster with a specific nodeAffinity to measure its effect
    • rolled NodeLocal DNSCache out gradually to the Dev and Prod environments by labelling node pools so its pods could be deployed there
    Lessons

    When every pod in a busy cluster resolves names through a few central kube-dns pods, DNS becomes a shared bottleneck, and a DNS failure quickly turns into higher latency, timeouts and cascading outages across microservices. A cache on each node takes most of that load off kube-dns and keeps resolution local to the node. Rolling the cache out first to an internal test cluster with nodeAffinity, and then node pool by node pool through labels, kept the blast radius of the change small.

  5. Symptoms

    During a Lunar New Year event in January 2024, a developer posted a message in Slack suspecting an outage. While several people were checking it, the problem grew into a full outage of Backpackr's web and app services, and the company decided to stop the event.

    Trigger

    An unexpected traffic surge, more than three times normal, during the Lunar New Year event in January 2024.

    Root cause
    Component
    Contributing factor
    Detection

    A developer reported a suspected outage in Slack; the outage became total while several people were still confirming it.

    Remediation
    • stopped the Lunar New Year event
    Action items
    • Raise net.netfilter.nf_conntrack_max on all nodes to memory bytes/16384/2, and three times that on Istio nodes, applied by the nodeOptimizer DaemonSet
    • Configure Istio mesh networking so sidecars communicate directly instead of through the ingressGateway
    • Upgrade the Istio nodes from c6.xlarge (12.5 Gbps) to n-type instances with up to 25 Gbps of network bandwidth
    • Strengthen monitoring with ENA network bandwidth and packet drops, detailed Istio ingressGateway and sidecar metrics, and CPU, memory and saturation
    Lessons

    When every request in a cluster goes through one ingress gateway node, that node's connection tracking table and network bandwidth set the limit for the whole service. The default nf_conntrack table size was too small for three times normal traffic, and once it filled, packets were dropped. After the outage Backpackr strengthened its monitoring of network bandwidth, packet drops and the Istio components.

Check your cluster for this

These 20 cases involve Kubernetes API server and Application database. kubegap audits a Kubernetes cluster for gaps like these, read-only, from Claude Code or Codex; its checks cite public reports like the ones in this library.

By root cause9

Dependency failure2 cases

  1. IL-0133 A storm shut down cooling at Nebius's us-central1 data center, and a disk hot-plug bug kept Managed Kubernetes control planes down for hours after power returned
    Nebius2026
  2. IL-0135 A power source switch during UPS maintenance cut power to a row of GPU servers and shut down Crusoe Cloud VMs in us-northcentral1

Configuration change1 case

Organisation
  1. IL-0063 VPN outage after recreating a Redis StatefulSet restarted the whole Redis cluster without readiness checks

Breaking change in an upgrade2 cases

Organisation
  1. IL-0101 After Google forced a GKE control plane upgrade to 1.33.2 at a deprecation deadline, no new node could initialise, so autoscaling and spot node replacement stopped for 15 hours
  2. IL-0060 Kubernetes 1.24 upgrade removed the master node label that Calico route reflectors selected on, dropping all pod routes and taking Reddit down for 314 minutes
    Reddit2023

Capacity exhaustion7 cases

  1. IL-0080 kube-dns on Mercari's GKE clusters could not keep up with peak-hour DNS query rates, and a Sev1 production outage followed when several services failed DNS resolution
  2. IL-0170 During a Lunar New Year event, traffic more than three times normal filled the nf_conntrack table on the EKS node running the Istio ingress gateway, dropping packets and taking down Backpackr's web and app services
  3. IL-0027 All CoreDNS pods landed on one node, the node ran out of memory, and DNS for the whole service went down
  4. IL-0085 A control plane node of Magic Pages' Kubernetes cluster on Hetzner Cloud ran out of memory, the cluster's own calls then used up the Hetzner API rate limit, and all customer websites were down for about 7.5 hours
  5. IL-0037 Image registry rate-limited a whole region after a crash-looping DaemonSet with imagePullPolicy Always pulled through three NAT instances
  6. IL-0064 CPU-heavy pods packed onto one Google Cloud node drove it to kernel panics, and the crash moved from node to node until the site was down
  7. IL-0040 Parallel Helm installs saturated small gp2 root volumes on a kops cluster and left all three workers NotReady with the kubelet or Docker down

Software defect3 cases

  1. IL-0138 A failed Nvidia driver build left broken kernel packages on the only Kubernetes master node, which hit a kernel panic on reboot after a power outage and took the homelab cluster down for six days
  2. IL-0196 Adding a second Redis replica and lowering memory limits in one RedisFailover change restarted the only Redis pod that held data, and Sentinel promoted the empty new replica, erasing the data
    Palark2020
  3. IL-0003 linkerd lost Kubernetes service discovery after an etcd reconfiguration, and restarting every linkerd instance turned failed payments into a full platform outage
    Monzo2017

Cloud provider outage2 cases

  1. IL-0145 A power sag and chiller failure in one Australia East availability zone took down the AKS control plane's compute and its non-zone-redundant SQL Database operation queue, blocking AKS create, update and delete operations in Australia East and Australia Southeast
  2. IL-0096 A GKE node pool pinned to the europe-west2-b zone could not scale for 6.5 hours because Google ran out of resources in that zone (ZONE_RESOURCE_POOL_EXHAUSTED)
    2i2c2022

Certificate or credential expiry1 case

Organisation
  1. IL-0113 The managed GKE control plane of Webhook Relay's main cluster failed because its API server certificates had never been rotated, and a manual credential rotation reported success without taking effect

DNS or network fault1 case

Organisation
  1. IL-0199 A non-essential container exceeding its memory limit made GitHub's production pods unavailable, and their restarts failed because a DNS maintenance change had left the clusters unable to reach the image registry
    GitHub2020

unknown1 case

Organisation
  1. IL-0059 Single-master Kubernetes control plane kept dying because the kubelet restarted a healthy etcd on a failing kubeadm liveness probe