IL-0350Hosts in an IONOS TXL cluster lost connectivity when an InfiniBand fabric resweep failed on a full multicast tableIONOS Cloud2026- Symptoms
On 3 March 2026, during a scheduled maintenance to replace a faulty switch in a cluster in IONOS Cloud's TXL data center, monitoring alerts fired and the hosts in that cluster lost network connectivity. Customers saw intermittent network degradation or outages, and the Data Center Designer (DCD) web frontend and the AI Model Hub became unreachable.
- Trigger
During a scheduled maintenance to replace a faulty switch, Topology 2 of 2 in the affected cluster was disabled as planned, and a link flap on a switch in Topology 1 then flooded the InfiniBand control plane with alerts and started a fabric resweep.
- Root cause
- Component
- Contributing factor
- Detection
IONOS began investigating monitoring alerts in TXL; the first status update was posted at 11:36 UTC.
- Remediation
- Switched from the affected control plane to its standby
- Rebooted the locked-up gateways
- Recovered Topology 1 from the scheduled maintenance
- Paused provisioning in the cluster that had a backlog of queued jobs
- Re-enabled provisioning once network connectivity improved and watched job execution
- Re-established connectivity for the systems that support the DCD
- Action items
- Adjusted the control-plane configuration to use less aggressive failover timers and reduced heavy sweep activity, lowering the load on the forwarding table
- Reduced the number of multicast group memberships to relieve the forwarding table
- Set up continuous monitoring of forwarding table use and control-plane memory with alerts before capacity limits are reached
- Move the control plane to dedicated high-performance servers, separate from data-plane traffic
- Audit IPv6 configurations and IPoIB driver settings
- Modernise the interconnect fabric, including switches, gateways and drivers
- Hardened IAM maintenance protocols so that critical identity services keep working when the primary Cloud APIs are temporarily unavailable
- Move IAM to a dedicated platform without a dependency on the standard managed Kubernetes clusters
- Introduce a dedicated provisioning provider for DBaaS and Managed Kubernetes
- Add automated circuit breakers to the provisioning engine against overload and queue buildup from self-healing services
- Improve visibility and control over job execution and prioritisation in the provisioning queue
- Change the provisioning queue architecture to decouple services and reduce spillover
- Lessons
IONOS identified the linking of services through the shared provisioning queue as a key reason the degradation lasted as long as it did. Alongside making each service more robust, it is decoupling the provisioning queue and addressing dependencies between services to reduce the blast radius of future incidents.
IL-0564Linode's Miami, Milan and Sao Paulo data centers had packet loss as traffic moved onto congested alternate pathsLinode2025- Symptoms
Customers using Linode's US-MIA (Miami) and IT-MIL (Milan) data centers saw packet loss and brief performance problems on 14 September 2025 from 17:42 to 18:43 UTC. BR-GRU (Sao Paulo) had the same packet loss on 15 September 2025 from 01:44 to 04:22 UTC.
- Trigger
A gradual increase in prefixes pushed the routing between the core router and the edge router past the maximum number of permitted prefixes.
- Root cause
- Component
- Contributing factor
- –
- Remediation
- Raised the prefix limit on all the data center routers
- Action items
- Raise the thresholds of the sessions between Akamai's backbone and the data center ECOR routers
- Improve the existing alerting and check its severity before limits are reached, with escalation to the right team for immediate action
IL-0341Traffic between Cloudflare and AWS us-east-1 had high latency, packet loss and origin failures for almost four hoursCloudflare2025- Symptoms
From 16:27 UTC on 21 August 2025, users connecting to Cloudflare from servers in AWS us-east-1, or receiving connections from Cloudflare there, saw high latency, packet loss and failures to reach origins. Cloudflare's network team was alerted to internal congestion in Ashburn (IAD) at 16:44 UTC.
- Trigger
At about 16:27 UTC a single customer began sending many requests from AWS us-east-1 to Cloudflare for objects in Cloudflare's cache, doubling the total traffic from Cloudflare to AWS.
- Root cause
- Component
- Contributing factor
- Detection
Cloudflare's network team was alerted to internal congestion in Ashburn (IAD) at 16:44 UTC, and an incident was raised for customer impact at 17:45 UTC.
- Remediation
- Rate limited the single customer whose traffic caused the surge
- Took further traffic engineering actions that fully resolved the congestion
- Asked AWS to revert its BGP prefix withdrawals, which AWS finished at 20:07 UTC
- Action items
- Build a mechanism to deprioritise a customer's traffic when it congests the network enough to affect others
- Speed up the Data Center Interconnect upgrades to add network capacity
- Work with AWS so the two companies' BGP traffic engineering actions do not conflict
- Build a traffic management system that gives each customer a network resource budget and automates the manual actions used here
- Lessons
Cloudflare concludes that it must isolate customers better so that no single customer can take over shared network resources and degrade the platform for others, and that its network needs enough capacity to meet demand. It describes the outage as the result of insufficient network congestion management during an unusual high-traffic event.
These 3 cases involve BGP routing and Backbone network (WAN). kubegap audits a Kubernetes cluster for gaps like these, read-only, from Claude Code or Codex; its checks cite public reports like the ones in this library.
By root cause1
Capacity exhaustion3 cases
- Component
- Contributing factor
- Organisation
IL-0350Hosts in an IONOS TXL cluster lost connectivity when an InfiniBand fabric resweep failed on a full multicast tableIONOS Cloud2026IL-0564Linode's Miami, Milan and Sao Paulo data centers had packet loss as traffic moved onto congested alternate pathsLinode2025IL-0341Traffic between Cloudflare and AWS us-east-1 had high latency, packet loss and origin failures for almost four hoursCloudflare2025