Cases2 cases
1 to 2 of 2
- Symptoms
Over six months from March to August 2023, LLM pretraining jobs on the Seren and Kalos clusters of Shanghai AI Laboratory's Acme datacenter, 4,704 A100 GPUs in total, failed again and again partway through and had to be restarted from the last checkpoint. Jobs that failed on infrastructure problems were only 11% of failed jobs by count but used over 82% of the GPU time of failed jobs.
- Root cause
- Component
- Contributing factor
- –
- Detection
Failures were found in the framework's runtime logs, later by a diagnosis system that combines rules with an LLM; the pretraining framework detects loss spikes automatically. Jobs that stalled without an error were noticed only when users inspected them by hand.
- Remediation
- Restarted interrupted pretraining jobs by hand from the last checkpoint, with developers on call in turn
- Saved checkpoints at shorter intervals and let jobs terminate gracefully to keep their current state
- Improved the cluster's cooling after GPU overheating caused NVLink and ECC errors
- Found faulty nodes with a two-round NCCL allgather test and cordoned them off
- Restarted from an earlier healthy checkpoint and skipped the following data batches after a loss spike
- Fixed the garbage collection interval on each rank in InternEvo V2
- Set num_worker=0 and enabled garbage collection in the dataloader to stop the memory leak
- Action items
- Move failure diagnosis from GPT-4 to Shanghai AI Laboratory's own LLMs
- Upgrade the infrastructure, with a particular focus on the NICs, and expand the computing cluster for larger-scale pretraining
- Lessons
Infrastructure failures are rare by count but cost the most GPU time, so diagnosing them and recovering quickly matters most for training efficiency. Matching error logs with regular-expression rules alone is often inaccurate because the logs are diverse and one failure can print several errors. Jobs that stall without an error or that are paused for loss spikes waste resources until someone looks, which calls for a failure-handling system that finds and fixes faulty jobs by itself.
IL-0381A misbehaving back-end node in Linode's Newark Object Storage slowed the service and caused 504 gateway timeoutsLinode2022- Symptoms
In the week of 10 October 2022, Linode Object Storage in Newark had two incidents of reduced performance and availability, on 10 and 16 October, and in some cases the front-end gateways returned 504 gateway timeouts to customers. The second incident began while the first was still being investigated.
- Trigger
One back-end Object Storage node had a hardware problem that was not an outright failure, so the node kept going up and down.
- Root cause
- Component
- Contributing factor
- Remediation
- Removed the failed back-end infrastructure from the Object Storage cluster
- Action items
- Improve detection so subtle problems with failing or misbehaving hardware are found and triaged before they affect the wider cluster
- Describe Ceph-related events more accurately to on-call administrators and define alerts more clearly
- Lessons
Hardware that misbehaves without failing outright can cause service-wide problems, and Linode's internal monitoring had gaps in spotting such subtle issues before they affected the wider cluster.
These 2 cases involve Object storage and Data center power and cooling. kubegap audits a Kubernetes cluster for gaps like these, read-only, from Claude Code or Codex; its checks cite public reports like the ones in this library.