IL-0133A storm shut down cooling at Nebius's us-central1 data center, and a disk hot-plug bug kept Managed Kubernetes control planes down for hours after power returnedNebius2026- Symptoms
On 19 August 2026 the first equipment-level signs in Nebius's us-central1 region appeared around 09:40 UTC: the InfiniBand fabric degraded and GPU over-temperature alerts began to accumulate. Customer reports followed shortly after 10:00. At 10:15 on-call engineers were paged on critical component temperature alerts, and the incident was declared at 10:21.
- Trigger
A storm-related event at the data center building took the building management system offline and shut down the chilled-water cooling loop.
- Root cause
- Component
- Contributing factor
- Detection
No facility-level alert fired, because the storm also disabled the building management system that monitors the facility. Engineers acted on component over-temperature alerts that paged on-call at 10:15 UTC, after InfiniBand degradation, GPU over-temperature alerts and customer reports; the temperature rise from about 09:15 was visible on dashboards but had no alert.
- Remediation
- had the facility operator switch cooling to manual bypass mode and opened rack rear doors to vent heat
- re-energised tripped racks, control-plane racks first
- restored the regional infrastructure control plane by manual intervention
- restarted block-storage host components to clear stale disk attachment state
- raised the VM recovery rate limits by hand for the region-scale recovery
- started the affected Managed Kubernetes control-plane instances by hand
- applied a controlled stop and start to control-plane instances whose data disk had been left unattached
- identified and started 104 customer VMs that the incident had stopped
- Action items
- Complete a joint resilience review with the facility operator covering redundancy of facility-management and monitoring systems, cooling that keeps running when those fail, electrical protection of cooling equipment and on-site response
- Add facility-level environmental alerting on cooling plant state and room temperature trend that pages on-call independently of the building management system
- Set up a documented emergency escalation path with the facility operator, with an on-call contact tree and guaranteed response times
- Define an emergency heat-load reduction procedure with criteria, ownership and mechanics for shutting down or degrading workloads during a cooling loss
- Establish a dependency-ordered region cold-start procedure with clear ownership for each service layer
- Run regular region-scale recovery drills that cover VMs, storage attachments and Managed Kubernetes clusters
- Fix the disk-attachment bug that extended the Managed Kubernetes outage and deploy the fix to all production regions
- Improve the recovery policies Compute users can configure, and move all Managed Kubernetes control-plane nodes to the improved policy
- Automate reconciliation of stale storage attachment state after abrupt host failures
- Remove in-region dependencies from monitoring startup and recovery, and extend cross-region monitoring
- Make regional health checks used for global traffic management reflect real service availability
- Lessons
Facility monitoring that runs on the same system it watches goes silent in exactly the failure it should report, and with no alert on the room temperature trend there was no practical window to shed heat load in a controlled way. A cold start of a whole region exercised recovery paths built for isolated failures: single-attempt VM recovery, conservative rate limits and stale disk attachments all needed manual work. The longest part of the outage was restoring customer resources, Managed Kubernetes control planes above all, so Nebius is extending its recovery drills to that layer.
- Symptoms
At 09:33 UTC on 14 February 2023 end users told the platform team that Kubernetes logs were not arriving in CloudWatch as expected. The investigation went through fluentd and found that the nodes were running containerd as their container runtime instead of docker-shim. A scheduled node rollover the day before, at 07:30 UTC on 13 February, had set containerd as the default runtime by accident.
- Trigger
A scheduled node rollover had accidentally made containerd the default container runtime, which stopped log shipping to CloudWatch; the unscheduled rollover to revert it timed out, and the pipeline run that followed reduced the Auto Scaling group from 30 to 15 instances.
- Root cause
- Component
- Contributing factor
- Detection
End users reported the missing CloudWatch logs that started the work. The postmortem lists 2 minutes as the time to detection of the node failure.
- Remediation
- ran the node rollover script to add new nodes, which failed on a timeout from Docker Hub
- ran the node rollover script a second time, which added new nodes that the load balancer marked healthy at 11:01 UTC
- Action items
- Document the rollover process, especially what can be done when it goes wrong
- Investigate options for improving the rollover process
- Add fluentd log collection to the QA test suite so logs are covered end to end
- Add alarms for fluentd when too little or no log data is sent
- Implement a staging environment
- Implement guards against selecting an invalid container runtime
- Lessons
When a change goes wrong, rolling back to a known working configuration is safer than rushing a fix, which can make the damage worse. Launching new worker nodes depends on the cloud-init script not failing in any way. The QA configuration differed from production, there was no staging environment, the QA tests did not cover fluentd log collection, and the rollover process had no documentation for when it fails.
These 2 cases involve Cloud block storage and Container runtime. kubegap audits a Kubernetes cluster for gaps like these, read-only, from Claude Code or Codex; its checks cite public reports like the ones in this library.
By root cause2
Dependency failure1 case
- Contributing factor
- Organisation
Configuration change1 case
- Contributing factor
- Organisation