  1. Symptoms

    On 19 August 2026 the first equipment-level signs in Nebius's us-central1 region appeared around 09:40 UTC: the InfiniBand fabric degraded and GPU over-temperature alerts began to accumulate. Customer reports followed shortly after 10:00. At 10:15 on-call engineers were paged on critical component temperature alerts, and the incident was declared at 10:21.

    Trigger

    A storm-related event at the data center building took the building management system offline and shut down the chilled-water cooling loop.

    Root cause
    Component
    Contributing factor
    Detection

    No facility-level alert fired, because the storm also disabled the building management system that monitors the facility. Engineers acted on component over-temperature alerts that paged on-call at 10:15 UTC, after InfiniBand degradation, GPU over-temperature alerts and customer reports; the temperature rise from about 09:15 was visible on dashboards but had no alert.

    Remediation
    • had the facility operator switch cooling to manual bypass mode and opened rack rear doors to vent heat
    • re-energised tripped racks, control-plane racks first
    • restored the regional infrastructure control plane by manual intervention
    • restarted block-storage host components to clear stale disk attachment state
    • raised the VM recovery rate limits by hand for the region-scale recovery
    • started the affected Managed Kubernetes control-plane instances by hand
    • applied a controlled stop and start to control-plane instances whose data disk had been left unattached
    • identified and started 104 customer VMs that the incident had stopped
    Action items
    • Complete a joint resilience review with the facility operator covering redundancy of facility-management and monitoring systems, cooling that keeps running when those fail, electrical protection of cooling equipment and on-site response
    • Add facility-level environmental alerting on cooling plant state and room temperature trend that pages on-call independently of the building management system
    • Set up a documented emergency escalation path with the facility operator, with an on-call contact tree and guaranteed response times
    • Define an emergency heat-load reduction procedure with criteria, ownership and mechanics for shutting down or degrading workloads during a cooling loss
    • Establish a dependency-ordered region cold-start procedure with clear ownership for each service layer
    • Run regular region-scale recovery drills that cover VMs, storage attachments and Managed Kubernetes clusters
    • Fix the disk-attachment bug that extended the Managed Kubernetes outage and deploy the fix to all production regions
    • Improve the recovery policies Compute users can configure, and move all Managed Kubernetes control-plane nodes to the improved policy
    • Automate reconciliation of stale storage attachment state after abrupt host failures
    • Remove in-region dependencies from monitoring startup and recovery, and extend cross-region monitoring
    • Make regional health checks used for global traffic management reflect real service availability
    Lessons

    Facility monitoring that runs on the same system it watches goes silent in exactly the failure it should report, and with no alert on the room temperature trend there was no practical window to shed heat load in a controlled way. A cold start of a whole region exercised recovery paths built for isolated failures: single-attempt VM recovery, conservative rate limits and stale disk attachments all needed manual work. The longest part of the outage was restoring customer resources, Managed Kubernetes control planes above all, so Nebius is extending its recovery drills to that layer.

  2. Symptoms

    At 5:00 PM BST on 12 August 2025 a 2i2c engineer declared an incident. While deploying a new cluster called temple and running into NFS issues, the engineer had deleted the prod namespace; the deletion hung, and listing the pods showed many users from a different cluster. The engineer's first message suggested that the kubeconfig had somehow been mutated or corrupted and that some other cluster was being torn down.

    Trigger

    While working around a bug in the NFS deployment process for a new hub, an engineer ran a delete of the prod namespace with the kubeconfig context pointing at the LEAP cluster.

    Root cause
    Component
    Contributing factor
    Detection

    The engineer who ran the deletion noticed when it hung and the pod list showed users of another cluster, and declared the incident at 5:00 PM BST, before the uptime check on leap.2i2c.cloud failed at 5:32 PM.

    Remediation
    • deleted the single remaining user pod in prod so the namespace deletion completed
    • killed the nfs-share-creator job that was blocking the deployment
    • redeployed the prod hub with the updated NFS server IP address
    • deleted the prod ingress during the deployment so that users could not start servers mid-deployment
    Action items
    • Write an incident report
    • Write a short incident response document for the case "I deleted prod, what next?"
    • Upgrade jupyterhub-home-nfs and remove the nfs-share-creator job
    • Add opt-in hardening against nested kubeconfig contexts to the deployer system
    • Change the engineer's shell configuration to show distinct kubeconfig contexts more clearly
    Lessons

    Provisioning persistent storage outside Kubernetes with Terraform meant a deleted namespace cost an hour of downtime and no data. The engineer had no visible cue for which kubeconfig context was active, which turned a workaround on a new cluster into a deletion on a production one. The engineer knew the fix but did not feel confident redeploying without first confirming with the tech lead, in another time zone, that there was no risk of losing persistent data, and reaching the tech lead took time.

  3. Symptoms

    At around 09:33 UTC one of the three control plane nodes of the Kubernetes cluster that hosts Magic Pages went offline. Looking at the node showed that it had run out of memory.

    Trigger

    One of the three control plane nodes ran out of memory and went offline at about 09:33 UTC; the attempts to replace it with hetzner-k3s failed while the cluster's own components were exhausting the Hetzner API rate limit.

    Root cause
    Component
    Contributing factor
    Detection

    The founder found the control plane node offline at about 09:33 UTC. Monitoring alerts about unreachable customer websites started around the time the replacement attempts failed, and about half an hour of investigation identified the exhausted Hetzner API rate limit.

    Remediation
    • powered off all servers of the Kubernetes cluster to stop the API requests so the Hetzner rate limit could recover
    • waited until ratelimit-remaining had built up a buffer before starting recovery
    • restarted the control plane servers
    • started the essential Longhorn components by hand so Longhorn could heal and make storage volumes available
    • restarted the remaining websites by hand
    Action items
    • Monitor the Hetzner API call rate coming from the Kubernetes cluster nodes themselves to get early warning of high usage
    • Get a higher Hetzner API rate limit; Hetzner support was contacted
    • Investigate how to reduce the cluster's reliance on a single API, including alternatives to hetzner-k3s
    • Document and test a procedure for recovering Longhorn after a full cluster shutdown
    Lessons

    The running cluster, not only the deployment tooling, consumed the cloud provider's API quota, and in a failure it consumed it fast enough that the quota never recovered. The default limit of 3600 requests per hour was not enough for failure and recovery scenarios, and API usage from inside the cluster was not monitored. A tool that hides the provider's API errors slows diagnosis. After a full, non-graceful shutdown, Longhorn needed manual intervention to come back, which lengthened the outage.

  4. Symptoms

    At 10:23 on 6 June 2023 a user of the Cloud Platform reported that all of their production pods had been deleted at the same moment. Several users received Pingdom alerts that their applications were down for a few minutes.

    Trigger

    The team changed the instance type of the cluster's worker nodes through Terraform.

    Root cause
    Component
    Contributing factor
    Detection

    Users reported that their production pods had been deleted at once and that Pingdom alerts showed their applications down; the incident was declared at 11:00.

    Action items
    • Ask AWS, through a support ticket, for the steps to change the node instance type without an outage
    • Plan how to make instance type changes through Terraform without downtime and add a runbook with the steps for changing the node instance type
  5. Symptoms

    At 09:33 UTC on 14 February 2023 end users told the platform team that Kubernetes logs were not arriving in CloudWatch as expected. The investigation went through fluentd and found that the nodes were running containerd as their container runtime instead of docker-shim. A scheduled node rollover the day before, at 07:30 UTC on 13 February, had set containerd as the default runtime by accident.

    Trigger

    A scheduled node rollover had accidentally made containerd the default container runtime, which stopped log shipping to CloudWatch; the unscheduled rollover to revert it timed out, and the pipeline run that followed reduced the Auto Scaling group from 30 to 15 instances.

    Root cause
    Component
    Contributing factor
    Detection

    End users reported the missing CloudWatch logs that started the work. The postmortem lists 2 minutes as the time to detection of the node failure.

    Remediation
    • ran the node rollover script to add new nodes, which failed on a timeout from Docker Hub
    • ran the node rollover script a second time, which added new nodes that the load balancer marked healthy at 11:01 UTC
    Action items
    • Document the rollover process, especially what can be done when it goes wrong
    • Investigate options for improving the rollover process
    • Add fluentd log collection to the QA test suite so logs are covered end to end
    • Add alarms for fluentd when too little or no log data is sent
    • Implement a staging environment
    • Implement guards against selecting an invalid container runtime
    Lessons

    When a change goes wrong, rolling back to a known working configuration is safer than rushing a fix, which can make the damage worse. Launching new worker nodes depends on the cloud-init script not failing in any way. The QA configuration differed from production, there was no staging environment, the QA tests did not cover fluentd log collection, and the rollover process had no documentation for when it fails.

Check your cluster for this

These 7 cases involve Persistent volumes and stateful sets and Terraform. kubegap audits a Kubernetes cluster for gaps like these, read-only, from Claude Code or Codex; its checks cite public reports like the ones in this library.

By root cause5

Dependency failure1 case

Organisation
  1. IL-0133 A storm shut down cooling at Nebius's us-central1 data center, and a disk hot-plug bug kept Managed Kubernetes control planes down for hours after power returned
    Nebius2026

Operator error1 case

Organisation
  1. IL-0095 An engineer deleted the prod namespace of the LEAP JupyterHub while believing the kubeconfig pointed at a new cluster, and the hub was down for about an hour
    2i2c2025

Capacity exhaustion1 case

Organisation
  1. IL-0085 A control plane node of Magic Pages' Kubernetes cluster on Hetzner Cloud ran out of memory, the cluster's own calls then used up the Hetzner API rate limit, and all customer websites were down for about 7.5 hours

Configuration change3 cases

  1. IL-0091 Changing the worker node instance type through Terraform recycled all nodes at once and deleted users' production pods together
  2. IL-0109 A retried node rollover on a DFDS EKS cluster set the Auto Scaling group back to 15 instances, and the default termination policy removed every healthy worker node, leaving the cluster with no nodes
    DFDS2023
  3. IL-0009 A duplicated generated name made Argo CD replace the InfluxDB Cloud production Application and delete the whole production environment

Faulty deployment1 case

Organisation
  1. IL-0086 A deployment meant for a CircleCI test Kubernetes cluster also removed Traefik and Calico resources from the production cluster, taking down the CircleCI UI and runner.circleci.com