  1. Symptoms

    On 19 August 2026 the first equipment-level signs in Nebius's us-central1 region appeared around 09:40 UTC: the InfiniBand fabric degraded and GPU over-temperature alerts began to accumulate. Customer reports followed shortly after 10:00. At 10:15 on-call engineers were paged on critical component temperature alerts, and the incident was declared at 10:21.

    Trigger

    A storm-related event at the data center building took the building management system offline and shut down the chilled-water cooling loop.

    Root cause
    Component
    Contributing factor
    Detection

    No facility-level alert fired, because the storm also disabled the building management system that monitors the facility. Engineers acted on component over-temperature alerts that paged on-call at 10:15 UTC, after InfiniBand degradation, GPU over-temperature alerts and customer reports; the temperature rise from about 09:15 was visible on dashboards but had no alert.

    Remediation
    • had the facility operator switch cooling to manual bypass mode and opened rack rear doors to vent heat
    • re-energised tripped racks, control-plane racks first
    • restored the regional infrastructure control plane by manual intervention
    • restarted block-storage host components to clear stale disk attachment state
    • raised the VM recovery rate limits by hand for the region-scale recovery
    • started the affected Managed Kubernetes control-plane instances by hand
    • applied a controlled stop and start to control-plane instances whose data disk had been left unattached
    • identified and started 104 customer VMs that the incident had stopped
    Action items
    • Complete a joint resilience review with the facility operator covering redundancy of facility-management and monitoring systems, cooling that keeps running when those fail, electrical protection of cooling equipment and on-site response
    • Add facility-level environmental alerting on cooling plant state and room temperature trend that pages on-call independently of the building management system
    • Set up a documented emergency escalation path with the facility operator, with an on-call contact tree and guaranteed response times
    • Define an emergency heat-load reduction procedure with criteria, ownership and mechanics for shutting down or degrading workloads during a cooling loss
    • Establish a dependency-ordered region cold-start procedure with clear ownership for each service layer
    • Run regular region-scale recovery drills that cover VMs, storage attachments and Managed Kubernetes clusters
    • Fix the disk-attachment bug that extended the Managed Kubernetes outage and deploy the fix to all production regions
    • Improve the recovery policies Compute users can configure, and move all Managed Kubernetes control-plane nodes to the improved policy
    • Automate reconciliation of stale storage attachment state after abrupt host failures
    • Remove in-region dependencies from monitoring startup and recovery, and extend cross-region monitoring
    • Make regional health checks used for global traffic management reflect real service availability
    Lessons

    Facility monitoring that runs on the same system it watches goes silent in exactly the failure it should report, and with no alert on the room temperature trend there was no practical window to shed heat load in a controlled way. A cold start of a whole region exercised recovery paths built for isolated failures: single-attempt VM recovery, conservative rate limits and stale disk attachments all needed manual work. The longest part of the outage was restoring customer resources, Managed Kubernetes control planes above all, so Nebius is extending its recovery drills to that layer.

  2. Symptoms

    Every service in the homelab Kubernetes cluster stopped answering: the V-Rising server, Grafana, Jellyfin and Linkding were all unreachable, and the Kubernetes API was down, so the cluster could not be managed at all. The outage was found by hand, about 3 hours after it began, when someone tried to use the services.

    Trigger

    A power outage forced the Kubernetes master node to reboot.

    Root cause
    Component
    Contributing factor
    Detection

    Manually, when someone tried to access the services; there were no automated alerts.

    Remediation
    • Connected a monitor to the master node and read the boot logs, which showed the kernel panic
    • Booted the previous kernel version, which brought the system back
    • Removed the broken Nvidia packages with sudo apt-get remove --purge '^nvidia-.*' and ran sudo dpkg --configure -a
    • Found remaining broken packages with dpkg -l | grep -v ^ii and removed them by hand
    • Ran sudo apt-get install -f and reinstalled linux-headers-$(uname -r)
    • Rebooted and confirmed the kernel panic was gone
    Action items
    • Make sure GPU driver installations fully succeed, or revert immediately when they fail
    • Move the cluster to a high-availability control plane
    • Expose the Kubernetes API through a load balancer in the HA setup
    • Set up a ticketing system to record incidents and their resolution
    • Write predefined troubleshooting workflows to shorten response time
    • Add infrastructure monitoring such as Prometheus and Grafana
    • Add blackbox HTTP and TCP checks from outside the cluster for critical services
    Lessons

    A driver installation that fails half-way can leave kernel packages broken without any visible effect until the next reboot, which may come weeks later and at the worst time. A failed DKMS build should be fixed or reverted at once. With a single master node and no monitoring from outside the cluster, one unbootable machine meant a total outage that nobody was told about; the fix itself was simple once the boot logs were seen.

  3. Symptoms

    From about 10:30 UTC on 30 August 2023, customers had trouble accessing or using Azure, Microsoft 365 and Power Platform services in Australia East. The affected Azure services included Azure Kubernetes Service (AKS) along with storage, SQL Database, Cosmos DB, virtual machines and Azure Resource Manager.

    Trigger

    At 08:41 UTC a lightning strike on electrical infrastructure about 18 miles away caused a utility voltage sag that shut down the cooling chillers of datacenters in one Australia East availability zone; 13 chillers failed to restart automatically and five could not be restarted, so two data halls overheated and their infrastructure was shut down.

    Root cause
    Component
    Contributing factor
    Detection

    Cosmos DB impact was detected by monitoring at 10:47 UTC, first automated communications went to Azure Service Health at 10:48 UTC, the public Azure Status page was updated at 11:30 UTC, and all subscriptions in Australia East were sent portal communications at 11:36 UTC.

    Remediation
    • shut down the remaining networking, compute and storage in the two affected data halls so the chilled water loop could cool down
    • restarted the five chillers manually at 12:12 UTC
    • restored power to all hardware by 15:10 UTC and brought infrastructure back in phases
    • restored AKS operations through the recovery of the SQL Database operation queue, with no other mitigation
    Action items
    • AKS: convert all operation queue SQL Database databases to be zone redundant (estimated September 2023)
    • AKS: replace all cross-region SQL Database queue usage with zone-redundant Service Bus queues (estimated September 2023)
    • Change the control timing logic of the Chiller Management System so chillers do not fail to restart after voltage fluctuations
    • Change the emergency procedure for manual restarts of simultaneous chiller failures from an adjacent sequence to a load-based sequence per data hall
    • Increase technician staffing at the datacenter as a temporary measure for manual chiller restarts
    • Storage: optimise the large-scale recovery process and update troubleshooting guides (estimated December 2023)
    • Azure Service Fabric: improve reliability of SQL Database tenant ring recovery (estimated December 2023)
    • SQL Database: review the trigger criteria of auto-failover groups (estimated October 2023)
    • SQL Database: upgrade internal tooling to enable mass migration of databases (estimated December 2023)
    • Cosmos DB: optimise Service Managed Failover for single-region-write accounts (estimated November 2023)
    • ARM: complete the migration of its storage layer to the zonally redundant architecture (estimated December 2023)
    • Incident management: harden readiness, process and playbook for power-down scenarios (estimated October 2023)
    Lessons

    A control plane spread across availability zones still fails with a zone when one of its dependencies, here the SQL Database operation queue, is not zone redundant. When a second region uses the same database, the failure crosses into that region as well. Workloads already running were not expected to be affected; what stopped was everything that needs the managed service's control plane, such as scaling and cluster changes.

  4. Symptoms

    At 12:00 EST the health check system reported that the backend APIs, the frontend and the tunnels in the EU region were down. The team first took it for a transient error, such as an interrupted client request or a server evicted for memory or CPU pressure, but the main dashboard was offline as well.

    Root cause
    Component
    Contributing factor
    Detection

    The health check system sent a notification that the service was down; the team then found the main dashboard offline.

    Remediation
    • recreated the node pools by hand after the credential rotation failed to recreate them
    • duplicated the main cluster's services into a newly created GKE cluster
    • deleted the Kubernetes Service records in the old cluster so its load balancers could be attached to the new cluster
    • detached the StatefulSet from the old cluster and switched all writes to the main disk
    • exported the data from the temporary ClickHouse instance and inserted it into the main instance
    Action items
    • Change the deployment manifests so services can be switched between clusters quickly without a complicated persistent disk migration
    Lessons

    Recovery of existing infrastructure needs a time limit. Throughout the outage the old cluster looked about to recover, and the reluctance to give up on the salvage effort kept the team from starting over with a new cluster much sooner, which would have been the right call. On older GKE clusters, check the validity of the cluster CA certificate, for example by decoding masterAuth.clusterCaCertificate from gcloud container clusters describe and reading it with openssl x509. GKE's multiple availability zones made no difference in this failure.

  5. Symptoms

    Customers were affected, and Zalando's IAM service answered requests with HTTP 404. The talk shows this on slides titled "Customer impact" and "IAM returning 404", followed by a slide on the number of pods in the cluster.

    Trigger

    A CronJob (apiVersion batch/v2alpha1, schedule "*/15 9-19 * * Mon-Fri") whose concurrencyPolicy: Forbid and job history limits sat inside the pod template spec instead of the CronJob spec. The talk shows it right after the slides on the number of pods and the API server being OOM-killed, and the lessons add a quota on the number of pods.

    Root cause
    Component
    Contributing factor
    Remediation
    • fixed the CronJob manifest: moved concurrencyPolicy: Forbid and the job history limits to the CronJob spec, added activeDeadlineSeconds: 120 and changed the schedule to "7 8-18 * * Mon-Fri"
    Action items
    • Make the ingress stay healthy during API server problems
    • Make the ingress keep the last known set of routes
    • Use a ResourceQuota on the number of pods (the example sets pods: "1500")
    Lessons

    An AWS ALB routes traffic to all hosts when all hosts report unhealthy, so the ingress should stay healthy during API server problems. An ingress controller that reads routes from the API server should keep its last known set of routes. Use a quota for the number of pods.

Check your cluster for this

These 6 cases involve Kubernetes API server and etcd. kubegap audits a Kubernetes cluster for gaps like these, read-only, from Claude Code or Codex; its checks cite public reports like the ones in this library.

By root cause6

Dependency failure1 case

Organisation
  1. IL-0133 A storm shut down cooling at Nebius's us-central1 data center, and a disk hot-plug bug kept Managed Kubernetes control planes down for hours after power returned
    Nebius2026

Software defect1 case

Organisation
  1. IL-0138 A failed Nvidia driver build left broken kernel packages on the only Kubernetes master node, which hit a kernel panic on reboot after a power outage and took the homelab cluster down for six days

Cloud provider outage1 case

Organisation
  1. IL-0145 A power sag and chiller failure in one Australia East availability zone took down the AKS control plane's compute and its non-zone-redundant SQL Database operation queue, blocking AKS create, update and delete operations in Australia East and Australia Southeast

Certificate or credential expiry1 case

Organisation
  1. IL-0113 The managed GKE control plane of Webhook Relay's main cluster failed because its API server certificates had never been rotated, and a manual credential rotation reported success without taking effect

Capacity exhaustion1 case

Organisation
  1. IL-0031 Kubernetes API server OOM-killed, leaving the Skipper ingress without routes; the talk points to a misconfigured CronJob manifest

unknown1 case

Organisation
  1. IL-0059 Single-master Kubernetes control plane kept dying because the kubelet restarted a healthy etcd on a failing kubeadm liveness probe