  1. Symptoms

    From about 21:00 UTC on March 4, 2026, customers using Linodes backed by NVIDIA RTX 4000 Ada GPUs saw the GPUs lock up. At first the problem seemed limited to worker nodes of the Linode Kubernetes Engine (LKE); later Linode confirmed that every Linode with this hardware was affected, while Standard Compute and other GPU instances were not.

    Trigger

    Deployment of a repaired legacy GPU monitoring script, fixed during a routine improvement effort to restore a missing metric on internal observability dashboards.

    Root cause
    Component
    Contributing factor
    Detection

    Customers saw the lockups from about 21:00 UTC; the first status post went up at 02:07 UTC on March 5, about 5 hours after the lockups began.

    Remediation
    • Disabled the monitoring script across the GPU fleet
    • Rebooted the affected nodes
    Action items
    • Take improvement and prevention measures to stop a recurrence; the postmortem does not list them
    Lessons

    A monitoring script can take down the hardware it watches. A fix meant only to restore a missing metric brought back a firmware query written for an earlier GPU generation, and on the RTX 4000 Ada architecture that query against an active GPU triggers a lockup. The script ran across the GPU fleet, so every Linode with this GPU was affected in several regions, and the investigation first suspected a regression in the host hypervisor or the GPU firmware.

  2. Symptoms

    At 21:06 UTC on 14 February 2026 every GPU node in Lambda's AUS01 data center rebooted at the same moment, without warning or plan, affecting multiple customers. The nodes came back online quickly, but the storage they used had disconnected, and customer workloads failed.

    Trigger

    A power event at the AUS01 data center caused a loss of power.

    Root cause
    Component
    Contributing factor
    –
    Remediation
    • restored the compute fabric and InfiniBand connectivity, bringing all spine switches and most leaf switches back online
    • restored part of the UPS redundancy
    • powered up all nodes in AUS01, completed physical checks and started the storage back up
    • restored Starbase and the other storage-dependent services in us-west-3
    • told affected customers to reboot their VMs, or the hypervisor if needed, to clear stale or empty NFS mounts
    Lessons

    A power loss that reboots the network spine and the shared storage together with the GPU nodes takes longer to recover than the nodes themselves. The GPU nodes were back quickly, but the fabric was restored first, storage was started only after physical checks, and some VMs were left with stale NFS mounts that customers were told to fix with a VM reboot or, if that was not enough, a hypervisor reboot.

  3. Symptoms

    GPU nodes for an AI video upscaling job were created normally and reached Ready, and then about 10 to 11 minutes later Karpenter treated each one as unhealthy and replaced it. Every new node went the same way, so the GPU pods kept restarting and the upscaling work could not make progress.

    Trigger

    Enabling Karpenter's node auto-repair feature gate (nodeRepair: true) and then running GPU pods on nodes from the Bottlerocket NVIDIA AMI.

    Root cause
    Component
    Contributing factor
    Detection

    The team noticed GPU nodes being replaced repeatedly after running GPU pods, then found the DCGMError message in the node events.

    Remediation
    • Disabled Karpenter node auto-repair by setting the nodeRepair feature gate to false
    Lessons

    Automatic node repair acts on every unhealthy node condition, including AcceleratedHardwareReady, so an image defect that only breaks GPU health monitoring is enough to have every GPU node terminated and recreated in a loop. Before turning on auto-repair, check which conditions it watches and whether the node image reports them correctly. Disabling auto-repair stops the loop at once but is only a temporary measure; installing the missing library or changing the AMI address the cause but cost more on an immutable OS such as Bottlerocket.

  4. Symptoms

    At 11:36 PM PDT on 9 June, alerts fired across multiple OpenAI services as a large number of cloud-hosted GPU nodes lost network connectivity, and the engineering team was escalated to immediately. Losing those nodes cut the capacity available to serve ChatGPT and the API.

    Trigger

    A routine daily scheduled update of the host operating system on the cloud-hosted GPU servers restarted systemd-networkd on the affected nodes.

    Root cause
    Component
    Contributing factor
    Detection

    Alerts fired immediately across multiple services when the infrastructure began losing network connectivity at 11:36 PM PDT, and the engineering team was escalated to at once.

    Remediation
    • re-imaged the affected GPU virtual machines
    • deployed recovery automation to restart the remaining impacted nodes
    • halted the background update mechanisms on the GPU VMs
    Action items
    • Disable automatic daily updates on GPU VMs so updates run in a controlled, scheduled way
    • Update system configurations to prevent conflicts between systemd-networkd and the networking service
    • Audit VM configurations across the fleet to find and reduce similar risks
    • Improve recovery speed for critical infrastructure such as GPU VMs and clusters
    • Run regular disaster recovery drills
    Lessons

    An unattended operating system update that restarts systemd-networkd can wipe the routes another networking agent manages, and it hits every node that takes the update at about the same time. Without break-glass tooling to restore connectivity, nodes that lost their network had to be re-imaged, which stretched recovery over many hours.

  5. Symptoms

    Over a 54-day snapshot of Llama 3 405B pre-training the training job was interrupted 466 times. 47 interruptions were planned: automated maintenance such as firmware upgrades, or operator actions such as configuration or dataset updates. The other 419 were unexpected. Because training is synchronous, a failure on a single GPU can force a restart of the whole job.

    Root cause
    Component
    Contributing factor
    Detection

    The communication library's state is monitored and a stalled collective is timed out automatically; on an NCCLX watchdog or heartbeat timeout the PyTorch NCCL flight recorder dumps its tracing data, including collective metadata and stack traces.

    Remediation
    • handled almost every interruption through automation, with significant manual intervention only three times in 54 days
    Action items
    • Reduce job startup and checkpointing time
    • Use the PyTorch NCCL flight recorder to record every communication event and collective duration and to dump traces on NCCLX watchdog or heartbeat timeouts
    • Turn on heavier tracing and metadata collection in production through online configuration changes, without a code release or job restart
    • Give PyTorch access to NCCLX internal state so stalls are detected and localised faster, with a snapshot of the failing collective's finished and pending transfers
    Lessons

    Training on 16K GPUs has more failure modes than Meta's much larger CPU clusters, and because training is synchronous a single GPU failure can force a restart of the whole job. Meta raised effective training time by cutting job startup and checkpoint time and by building tools for fast diagnosis, and kept it above 90% while automated firmware and kernel maintenance caused at least one interruption a day.

Check your cluster for this

These 10 cases involve GPU driver and NCCL. kubegap audits a Kubernetes cluster for gaps like these, read-only, from Claude Code or Codex; its checks cite public reports like the ones in this library.

By root cause5

Faulty deployment1 case

Organisation
  1. IL-0160 A repaired legacy GPU monitoring script sent a firmware query that triggers a race condition in the GPU System Processor of NVIDIA RTX 4000 Ada GPUs, locking up GPU Linodes and LKE worker nodes in several regions
    Linode2026

Dependency failure5 cases

  1. IL-0134 A power event at Lambda's AUS01 data center rebooted 246 GPU nodes, all spine switches and the VAST storage, failing customer workloads and leaving stale NFS mounts on VMs
    Lambda2026
  2. IL-0025 Failed boots, InfiniBand link flapping, NCCL hangs and throughput sags while bringing up a 4,088-GPU H100 training cluster
    Imbue2024
  3. IL-0021 GKE GPU nodes on Container-Optimized OS could not download NVIDIA drivers (403 Forbidden) and came up without working GPUs
  4. IL-0135 A power source switch during UPS maintenance cut power to a row of GPU servers and shut down Crusoe Cloud VMs in us-northcentral1
  5. IL-0126 The OPT-175B training run restarted more than 40 times in two weeks as cloud GPU nodes failed with ECC errors, replacement nodes came back faulty, and checkpoint downloads hung

Software defect1 case

Organisation
  1. IL-0171 Karpenter node auto-repair replaced EKS GPU nodes about 10 minutes after they became Ready, in a loop, because the Bottlerocket NVIDIA AMI lacked libdcgm.so and set AcceleratedHardwareReady to False
    Inflab2025

Breaking change in an upgrade1 case

Organisation
  1. IL-0120 A daily scheduled OS update restarted systemd-networkd on cloud-hosted GPU nodes, which conflicted with OpenAI's networking agent and removed all routes, cutting capacity for ChatGPT and the API
    OpenAI2025

Hardware failure2 cases

Organisation
  1. IL-0127 Llama 3 405B pre-training on 16K H100 GPUs was interrupted 419 times unexpectedly in 54 days, mostly by faulty GPUs, HBM3 memory and other hardware
    Meta2024
  2. IL-0125 A GPU died about once a week during a 176B-parameter training run, and sometimes the job hung instead of exiting, so SLURM never restarted it