Cases6 cases

5 to 6 of 6

  1. Symptoms

    From 20:18 UTC on 11 June 2022, OpenStreetMap.org was unavailable: all of its services hosted in Amsterdam, including www, the API, the wiki and planet, had no connectivity to the Internet. The outage began 18 minutes into Equinix's planned maintenance of power feed A at the Amsterdam data centre.

    Trigger

    Equinix's planned 5-year maintenance of power feed A in Amsterdam, which started at 20:00 UTC on 11 June 2022.

    Root cause
    Component
    Contributing factor
    Remediation
    • Waited for the end of the Equinix power feed A maintenance window instead of failing over to Dublin or moving the uplink; connectivity returned at 03:45 UTC
    Action items
    • Acknowledge ongoing outages faster
    • Add monitoring and alerting of switch PSU and FAN states
    • Replace the Cisco SG550X-48 switches and the Redundant Power System with Juniper EX4300 switches with redundant power supplies
    • Install out-of-band access equipment with dual power feeds in Amsterdam
    • Install redundant uplinks
    • Make site failover easier, less manual and lower risk
    • Introduce an on-call pager system for the operations SRE
    • Expand the SRE team
    • Continue and formalise fail-over tests for power, network, upstream link and service outages
  2. Symptoms

    On Friday, 30 November 2012, GitHub had sporadic bursts of slow responses and intermittent errors for the whole day and was completely unavailable for 18 minutes. One fileserver pair was offline for a large part of the day, which affected a small percentage of repositories; this was a side effect of the network problems on the high-availability clustering between the fileserver nodes.

    Trigger

    On the morning of 30 November GitHub moved the A switches in its server cabinets onto the new aggregation switches, the second half of a migration whose B-switch half had been done the day before.

    Root cause
    Component
    Contributing factor
    Detection

    Engineers saw the problems during the maintenance itself: connectivity to the B switch was lost as the last A switch was connected, and afterwards performance stayed low and the links between access and aggregation switches showed as completely saturated.

    Remediation
    • Fixed the bridge-loop problem and returned the affected B switch to service
    • Removed the partial link failure detection setting from the access switches
    • Escalated to the network vendor, which raised the case to its highest severity level
    • Restarted core processes on the aggregation switches in a Saturday 0600 Pacific maintenance window so they learned MAC addresses again
    Action items
    • Deploy the vendor's software update that fixes the MAC learning issue to the switches
    • Closely monitor aggregation-to-access capacity and keep a workaround process ready if the problem returns
    • Build a duplicate of the network stack, from the routers through the access switches, as a staging environment for testing such changes
    • Add automated network monitoring that alerts sooner on similar issues
    • Run scheduled incident response exercises with scenarios that counter tunnel vision
    • Contact the network vendor's support at the first sign of trouble in the network
    Lessons

    GitHub had designed the maintenance to have no impact on customers and clearly failed, so it plans to invest in a staging copy of its network to test such changes and catch bugs like this one. During the response the team fixated for a long time on a bridge loop, which kept it from considering other causes. GitHub had a very positive experience with the vendor's support staff, so it will contact that support team at the first sign of network trouble.

Check your cluster for this

These 6 cases involve Network switch and BGP routing. kubegap audits a Kubernetes cluster for gaps like these, read-only, from Claude Code or Codex; its checks cite public reports like the ones in this library.

By root cause4

Operator error2 cases

Organisation
  1. IL-0568 A layer 2 loop after an access switch change broke network traffic across a whole DeNA site, with mass MACFLAP logs
    DeNA2026
  2. IL-0349 IONOS Private Cloud in Berlin lost management access, storage and VM internet routing after a VLAN change

Software defect2 cases

Organisation
  1. IL-0347 About 25% of Scaleway FR-PAR-1 hypervisors lost VPC connectivity when both VPC BGP route reflectors got stuck
  2. IL-0263 GitHub was slow and erroring all day and down for 18 minutes as links between access and aggregation switches saturated
    GitHub2012

DNS or network fault1 case

Contributing factor
–
Organisation
  1. IL-0562 Most Linodes in Linode's Dallas data center had intermittent latency and reachability loss from broadcast storms
    Linode2022

Hardware failure1 case

  1. IL-0525 OpenStreetMap.org went offline for 7h 27m when its uplink switch lost power during a data-centre power feed maintenance