  1. Symptoms

    From about 10:30 UTC on 30 August 2023, customers had trouble accessing or using Azure, Microsoft 365 and Power Platform services in Australia East. The affected Azure services included Azure Kubernetes Service (AKS) along with storage, SQL Database, Cosmos DB, virtual machines and Azure Resource Manager.

    Trigger

    At 08:41 UTC a lightning strike on electrical infrastructure about 18 miles away caused a utility voltage sag that shut down the cooling chillers of datacenters in one Australia East availability zone; 13 chillers failed to restart automatically and five could not be restarted, so two data halls overheated and their infrastructure was shut down.

    Root cause
    Component
    Contributing factor
    Detection

    Cosmos DB impact was detected by monitoring at 10:47 UTC, first automated communications went to Azure Service Health at 10:48 UTC, the public Azure Status page was updated at 11:30 UTC, and all subscriptions in Australia East were sent portal communications at 11:36 UTC.

    Remediation
    • shut down the remaining networking, compute and storage in the two affected data halls so the chilled water loop could cool down
    • restarted the five chillers manually at 12:12 UTC
    • restored power to all hardware by 15:10 UTC and brought infrastructure back in phases
    • restored AKS operations through the recovery of the SQL Database operation queue, with no other mitigation
    Action items
    • AKS: convert all operation queue SQL Database databases to be zone redundant (estimated September 2023)
    • AKS: replace all cross-region SQL Database queue usage with zone-redundant Service Bus queues (estimated September 2023)
    • Change the control timing logic of the Chiller Management System so chillers do not fail to restart after voltage fluctuations
    • Change the emergency procedure for manual restarts of simultaneous chiller failures from an adjacent sequence to a load-based sequence per data hall
    • Increase technician staffing at the datacenter as a temporary measure for manual chiller restarts
    • Storage: optimise the large-scale recovery process and update troubleshooting guides (estimated December 2023)
    • Azure Service Fabric: improve reliability of SQL Database tenant ring recovery (estimated December 2023)
    • SQL Database: review the trigger criteria of auto-failover groups (estimated October 2023)
    • SQL Database: upgrade internal tooling to enable mass migration of databases (estimated December 2023)
    • Cosmos DB: optimise Service Managed Failover for single-region-write accounts (estimated November 2023)
    • ARM: complete the migration of its storage layer to the zonally redundant architecture (estimated December 2023)
    • Incident management: harden readiness, process and playbook for power-down scenarios (estimated October 2023)
    Lessons

    A control plane spread across availability zones still fails with a zone when one of its dependencies, here the SQL Database operation queue, is not zone redundant. When a second region uses the same database, the failure crosses into that region as well. Workloads already running were not expected to be affected; what stopped was everything that needs the managed service's control plane, such as scaling and cluster changes.

  2. Symptoms

    GitLab's monitoring and alerting fired at once. One of the alerts reported a Patroni failover, and users of GitLab.com received 5XX errors; the CDN counted about 13 million requests answered with 503 during the outage.

    Trigger

    An engineer ran a routine task with GitLab's tools in a local development environment; during a local deploy or rollback operation the tool's context changed from local development to production, and the change was applied to production.

    Root cause
    Component
    Contributing factor
    Detection

    GitLab's monitoring and alerting fired immediately; one of the alerts reported a Patroni failover.

    Remediation
    • re-applied the Consul release to the production Kubernetes cluster, with manual steps because the tooling did not support the redeploy directly
    Action items
    • Improve the Kubernetes deployment process to reduce the risk of running harmful deployment operations against production from local environments (https://gitlab.com/gitlab-com/gl-infra/reliability/-/issues/16875)
    • Integrate Teleport with the Kubernetes clusters, which could give SREs a read-only role by default (https://gitlab.com/gitlab-com/gl-infra/reliability/-/issues/16221)
    Lessons

    A tool that can switch its target from a local environment to production during a deploy or rollback turns routine local work into a production change. GitLab plans to improve its Kubernetes deployment process so that harmful deployment operations are less likely to be run against production from local environments, and to integrate Teleport with its clusters, which could give SREs a read-only role by default. Detection and diagnosis were fast because the alerts led straight from Patroni to its dependency, Consul. Bringing the deleted release back needed manual work, because the tooling did not make the redeploy straightforward, but it was still done relatively quickly.

  3. Symptoms

    On 31 October 2022 at 6:27 PM Pacific time, users of the UToronto JupyterHub run by 2i2c could no longer log in or start their servers, and the hub answered with 500 errors. Users who were already logged in could keep using the hub.

    Trigger

    The JupyterHub log file, written to the same 10G disk as the hub's sqlite database, grew until the disk was completely full.

    Root cause
    Component
    Contributing factor
    Detection

    A user emailed 2i2c support at 7:13 PM that users could not log in; the team acknowledged the issue at 8:33 PM. There was no alert for the problem.

    Remediation
    • Compressed the hub log file into /tmp from a shell in the hub pod, because it could not be compressed in place on the full disk
    • Copied the compressed log to a local machine so the hub pod could be restarted without losing it
    • Resized the hub database disk (the hub-db-dir PVC) from 10G to 60G
    • Restarted the hub pod, which came back with the larger disk and restored service
    Action items
    • Stop keeping hub logs on the same disk as the hub database
    • Add a Grafana graph of free space on the JupyterHub database disk
    • Alert on elevated error rates
    Lessons

    Kubernetes dynamic volume resizing let the hub database disk grow from 10G to 60G without much effort. The risk of keeping logs on the database disk had been identified during the earlier migration, but the team had no solid process for following it through, and because no alert existed the team had to wait for a person to report the outage.

  4. Symptoms

    On 2022-04-25 the Sidekiq Apdex (the share of background jobs that finish within a target time) dropped, and an engineer declared an incident in Slack at 15:13 UTC. Users saw intermittent slowness across GitLab.com, and asynchronous work such as pipeline creation and import and export took unusually long.

    Trigger

    The Consul agent in GitLab.com's GKE pods had memory demand spikes that did not fit in the pods' 500MB memory limit, and the agent was killed again and again.

    Root cause
    Component
    Contributing factor
    –
    Detection

    An engineer declared the incident in Slack at 15:13 UTC after the Sidekiq Apdex dropped; the second event was found when monitoring detected an elevated error rate at 01:21 UTC on 2022-04-26.

    Remediation
    • planned at 16:13 to raise the per-user connection limit for the gitlab database user and the pgbouncer backend pools for the main database; changes were applied at 17:26 and confirmed at 17:47
    • raised the pod memory limits from 500MB to 1GB so the Consul agents survive memory spikes
    Action items
    • Monitor the Consul agents on GKE pods to see whether the 1GB memory limit keeps them healthy
    • Investigate the Consul memory demand spikes and what can be done beyond raising the hard memory limit
    Lessons

    When the local Consul agent that Rails uses for database service discovery keeps dying, Rails does not fail; it sends every query to the last known primary. What engineers saw was database saturation and slow background jobs, which pointed the investigation first at a recent pgbouncer pool change. The memory limit of the Consul agent in every pod therefore decided the load on the primary database.

  5. Symptoms

    In 2021 Shopify's KateSQL, a database-as-a-service platform that runs several hundred production MySQL instances on GKE, found that some MySQL pods started and shut down much more slowly than similar pods with the same data set. Instance replacement, the procedure that creates a new MySQL replica pod and stops the old one, showed pod creation times ranging from 10 to 30 minutes, which held up maintenance such as configuration changes and upgrades.

    Root cause
    Component
    Contributing factor
    Detection

    KateSQL's instance replacement operations showed inconsistent MySQL pod creation times, and the team then measured the mysql-init container and MySQL startup times across pods.

    Remediation
    • Cordoned older nodes, moved MySQL pods to new nodes through instance replacement and drained the old nodes
    • Forced the kubepods memory cgroup to empty its dead cgroups on an affected node to test the fix
    • Created new GKE 1.18 clusters and started creating MySQL pods on them
    Lessons

    The investigation was one of the longest the Database Platform group had carried out, because of the nature of the problem, how hard it was to reproduce and the lack of an established method to follow; once the cause was known, there were several ways to fix it.

Check your cluster for this

These 24 cases involve Database and Persistent volumes and stateful sets. kubegap audits a Kubernetes cluster for gaps like these, read-only, from Claude Code or Codex; its checks cite public reports like the ones in this library.

By root cause7

Configuration change1 case

Organisation
  1. IL-0179 With DEBUG logging and synchronous log output, a high-traffic service filled the 64 KB stdout pipe, so request threads blocked in write() while holding database connections and HikariCP ran dry, failing requests in 30-second bursts

Capacity exhaustion10 cases

  1. IL-0435 Error rates rose as Aurora MySQL killed connections and declined queries to avoid OOM while load metrics stayed flat
  2. IL-0350 Hosts in an IONOS TXL cluster lost connectivity when an InfiniBand fabric resweep failed on a full multicast table
  3. IL-0100 PostHog's feature flags pods were packed onto Kubernetes nodes that were too small for their CPU requests, and CPU saturation above 90% caused three outages in ten days through Redis overload, connection pool exhaustion and slow queries
  4. IL-0110 A Grafana Agent pod's high memory use and crash-looping Hangfire pods drove a Kubernetes node into system OOM and NotReady, twice in one day
    DFDS2024
  5. IL-0202 A burst of queries and database writes exhausted connection pools and memory on Honeycomb's ingest hosts, and Kubernetes crash-loop back-off kept failed hosts offline so ingest capacity stayed too low to recover
  6. IL-0386 After a move to Google Cloud, Postgres connection timeouts and memcached i/o timeouts spiked on GKE nodes
  7. IL-0500 UToronto JupyterHub logins and server starts returned 500 errors when the hub's sqlite database disk filled up
    2i2c2022
  8. IL-0206 Consul agents in GitLab.com's GKE pods were repeatedly OOM-killed, so the Rails pods lost database replica discovery and sent every query to the primary
    GitLab2022
  9. IL-0037 Image registry rate-limited a whole region after a crash-looping DaemonSet with imagePullPolicy Always pulled through three NAT instances
  10. IL-0064 CPU-heavy pods packed onto one Google Cloud node drove it to kernel panics, and the crash moved from node to node until the site was down

Software defect4 cases

  1. IL-0150 A latent race condition in DynamoDB's DNS automation left an empty DNS record for dynamodb.us-east-1.amazonaws.com, and the DynamoDB and EC2 launch failures that followed caused EKS, ECS and Fargate container launch failures and cluster scaling delays in us-east-1
  2. IL-0347 About 25% of Scaleway FR-PAR-1 hypervisors lost VPC connectivity when both VPC BGP route reflectors got stuck
  3. IL-0462 Some MySQL pods on Shopify's GKE clusters took up to 30 minutes to start, slowing instance replacement
  4. IL-0196 Adding a second Redis replica and lowering memory limits in one RedisFailover change restarted the only Redis pod that held data, and Sentinel promoted the empty new replica, erasing the data
    Palark2020

Dependency failure2 cases

  1. IL-0162 LKE users could not reach their cluster control planes or the LKE Dashboard because an earlier database update made the internal LKE DNS service hang
    Linode2025
  2. IL-0489 Rejoining a failed node of Magic Pages' three-node MySQL cluster broke its metadata and took customer websites down

Faulty deployment1 case

  1. IL-0324 Three MediaWiki deployments lost Memcached after a PHP 8.1 rollout and overloaded the External Storage database cluster

Cloud provider outage4 cases

  1. IL-0119 ChatGPT web service pods crash-looped on failing health checks after a Cosmos DB failure, leaving too few healthy pods to serve the web layer
    OpenAI2025
  2. IL-0145 A power sag and chiller failure in one Australia East availability zone took down the AKS control plane's compute and its non-zone-redundant SQL Database operation queue, blocking AKS create, update and delete operations in Australia East and Australia Southeast
  3. IL-0172 An AWS Tokyo data centre cooling failure took down 6 of 60 CockroachDB nodes on Kubernetes within 22 minutes, and ranges lost quorum because the Helm-deployed cluster had no availability zone locality configured
  4. IL-0193 A GCP persistent disk degradation took down a Cassandra StatefulSet whose OrderedReady policy blocked recovery, and Metrictank could not reconnect to the recreated pods, causing a 23-hour Graphite query outage

Operator error2 cases

  1. IL-0207 A routine task run from an engineer's local environment switched to production and deleted GitLab.com's Consul release, so Patroni lost Consul and GitLab.com returned 5xx errors to all traffic
    GitLab2022
  2. IL-0506 UC Berkeley DataHub logins failed and students got empty home directories after the JupyterHub database was overwritten