  1. Symptoms

    At about 20:00 on a weekday, one of DeNA's largest sites reported that terminals of a customer-facing system could not communicate and business was suffering. The network group's monitoring had raised no alert.

    Trigger

    During a routine change on 15 Cisco Catalyst 2960L access switches at the site, which tidied descriptions, added VLAN definitions and added allowed VLANs on trunk ports, `no switchport trunk allowed vlan` was applied to GigabitEthernet0/15 of switch SW3, only one of the two physical ports in the LACP bundle between SW3 and SW2.

    Root cause
    Component
    Contributing factor
    Detection

    The site reported the problem at about 20:00; no monitoring alert fired, because the affected port had no interface monitoring and LACP monitoring had been removed by an earlier monitoring change.

    Remediation
    • Rolled back the switch changes without knowing the cause; service recovered when the interface setting of one switch was restored
    • Found the faulty port and confirmed there was no other impact, completing the first response at about 22:00
    Action items
    • Fix the missing interface and LACP monitoring
    • Require a review for every monitoring change
    • Block merges to the alert rule repository without a reviewer's approval
    • Enable automatic AI review on pull requests
    • Announce every network change in advance, however minor
    • Agree the work date with the site's managers and avoid the site's event days
    • Prepare rollback procedures for high-impact maintenance and for work on several devices at once
    Lessons

    Any change can cause an outage, through a mistake, an unexpected event or a bug, so changes need to be scheduled with a maintenance window agreed in advance. A change on a downstream access switch can affect the whole site. Changing many devices at once made it slow both to find the faulty device and to roll back, and the parts that can be prevented by mechanisms rather than by people's care, such as reviews and monitoring, should be enforced that way.

  2. Symptoms

    On 15 January 2026, network services for VMware-based Private Clouds in IONOS Cloud's Berlin location stopped working: customers lost management VPN access and traffic to and from their virtual machines. Inside IONOS, several management interfaces in the Berlin region could no longer be reached.

    Trigger

    During a planned maintenance window to add a new VLAN to the management devices, a human error in the command replaced the existing VLANs on the trunk between the core and management devices instead of adding to them, so only the new VLAN stayed active.

    Root cause
    Component
    Contributing factor
    Remediation
    • Restarted the affected storage services in the final stage of recovery, which caused a brief second outage
    Action items
    • Audit the management device architecture to segment it better (target Q3 2026)
    • Evaluate and implement ways to prevent unintended VLAN changes, such as improved configuration safeguards or automation scripts (target Q1 2026)
  3. Symptoms

    On 18 October 2024, from 7:50 to 8:01 UTC, about 25% of the hypervisors in Scaleway's FR-PAR-1 availability zone lost VPC connectivity with the rest of the region, and products that use VPC failed with them. Public internet connectivity and Elastic Metal VPC connectivity were not affected.

    Trigger

    At 6:20 UTC a Top of Rack switch in FR-PAR-1 had a software crash. One of the two BGP route reflectors for VPC ran on a hypervisor in that rack and was left in an abnormal state.

    Root cause
    Component
    Contributing factor
    Detection

    Health-check monitoring on both route reflectors detected the anomaly, and the Scaleway Customer Excellence and SRE teams detected the customer impact and opened an incident.

    Remediation
    • Fixed both VPC route reflectors by manual action
    Action items
    • Fixed the autohealing mechanism that had failed to fix route reflectors stuck in a stale state; the fix is https://github.com/FRRouting/frr/pull/17163
    • Run different software versions on the route reflectors so a single bug cannot stop several instances
    • Investigate the software issue that left the route reflectors in a stale state
  4. Symptoms

    At about 00:05 UTC, Linode's monitoring systems alerted on reachability problems in the Dallas data center. About 80-90% of the Linodes there had intermittent latency and lost reachability from time to time.

    Root cause
    Component
    Contributing factor
    –
    Detection

    Monitoring systems alerted on reachability problems in the Dallas data center at about 00:05 UTC, and an incident was raised at 00:10.

    Remediation
    • Deployed a filter to the fleet that stemmed the broadcasts, so hosts regained CPU and answered ARP requests
    • Tested the temporary filter further and made it permanent
    Action items
    • Find the root cause of the broadcast storms, taking the other recent Dallas incidents into account
    • Put processes in place to keep the infrastructure stable while upgrades are applied to the active network
  5. Symptoms

    From 20:18 UTC on 11 June 2022, OpenStreetMap.org was unavailable: all of its services hosted in Amsterdam, including www, the API, the wiki and planet, had no connectivity to the Internet. The outage began 18 minutes into Equinix's planned maintenance of power feed A at the Amsterdam data centre.

    Trigger

    Equinix's planned 5-year maintenance of power feed A in Amsterdam, which started at 20:00 UTC on 11 June 2022.

    Root cause
    Component
    Contributing factor
    Remediation
    • Waited for the end of the Equinix power feed A maintenance window instead of failing over to Dublin or moving the uplink; connectivity returned at 03:45 UTC
    Action items
    • Acknowledge ongoing outages faster
    • Add monitoring and alerting of switch PSU and FAN states
    • Replace the Cisco SG550X-48 switches and the Redundant Power System with Juniper EX4300 switches with redundant power supplies
    • Install out-of-band access equipment with dual power feeds in Amsterdam
    • Install redundant uplinks
    • Make site failover easier, less manual and lower risk
    • Introduce an on-call pager system for the operations SRE
    • Expand the SRE team
    • Continue and formalise fail-over tests for power, network, upstream link and service outages
Check your cluster for this

These 6 cases involve Network switch and BGP routing. kubegap audits a Kubernetes cluster for gaps like these, read-only, from Claude Code or Codex; its checks cite public reports like the ones in this library.

By root cause4

Operator error2 cases

Organisation
  1. IL-0568 A layer 2 loop after an access switch change broke network traffic across a whole DeNA site, with mass MACFLAP logs
    DeNA2026
  2. IL-0349 IONOS Private Cloud in Berlin lost management access, storage and VM internet routing after a VLAN change

Software defect2 cases

Organisation
  1. IL-0347 About 25% of Scaleway FR-PAR-1 hypervisors lost VPC connectivity when both VPC BGP route reflectors got stuck
  2. IL-0263 GitHub was slow and erroring all day and down for 18 minutes as links between access and aggregation switches saturated
    GitHub2012

DNS or network fault1 case

Contributing factor
–
Organisation
  1. IL-0562 Most Linodes in Linode's Dallas data center had intermittent latency and reachability loss from broadcast storms
    Linode2022

Hardware failure1 case

  1. IL-0525 OpenStreetMap.org went offline for 7h 27m when its uplink switch lost power during a data-centre power feed maintenance