  1. Symptoms

    On 19 August 2026 the first equipment-level signs in Nebius's us-central1 region appeared around 09:40 UTC: the InfiniBand fabric degraded and GPU over-temperature alerts began to accumulate. Customer reports followed shortly after 10:00. At 10:15 on-call engineers were paged on critical component temperature alerts, and the incident was declared at 10:21.

    Trigger

    A storm-related event at the data center building took the building management system offline and shut down the chilled-water cooling loop.

    Root cause
    Component
    Contributing factor
    Detection

    No facility-level alert fired, because the storm also disabled the building management system that monitors the facility. Engineers acted on component over-temperature alerts that paged on-call at 10:15 UTC, after InfiniBand degradation, GPU over-temperature alerts and customer reports; the temperature rise from about 09:15 was visible on dashboards but had no alert.

    Remediation
    • had the facility operator switch cooling to manual bypass mode and opened rack rear doors to vent heat
    • re-energised tripped racks, control-plane racks first
    • restored the regional infrastructure control plane by manual intervention
    • restarted block-storage host components to clear stale disk attachment state
    • raised the VM recovery rate limits by hand for the region-scale recovery
    • started the affected Managed Kubernetes control-plane instances by hand
    • applied a controlled stop and start to control-plane instances whose data disk had been left unattached
    • identified and started 104 customer VMs that the incident had stopped
    Action items
    • Complete a joint resilience review with the facility operator covering redundancy of facility-management and monitoring systems, cooling that keeps running when those fail, electrical protection of cooling equipment and on-site response
    • Add facility-level environmental alerting on cooling plant state and room temperature trend that pages on-call independently of the building management system
    • Set up a documented emergency escalation path with the facility operator, with an on-call contact tree and guaranteed response times
    • Define an emergency heat-load reduction procedure with criteria, ownership and mechanics for shutting down or degrading workloads during a cooling loss
    • Establish a dependency-ordered region cold-start procedure with clear ownership for each service layer
    • Run regular region-scale recovery drills that cover VMs, storage attachments and Managed Kubernetes clusters
    • Fix the disk-attachment bug that extended the Managed Kubernetes outage and deploy the fix to all production regions
    • Improve the recovery policies Compute users can configure, and move all Managed Kubernetes control-plane nodes to the improved policy
    • Automate reconciliation of stale storage attachment state after abrupt host failures
    • Remove in-region dependencies from monitoring startup and recovery, and extend cross-region monitoring
    • Make regional health checks used for global traffic management reflect real service availability
    Lessons

    Facility monitoring that runs on the same system it watches goes silent in exactly the failure it should report, and with no alert on the room temperature trend there was no practical window to shed heat load in a controlled way. A cold start of a whole region exercised recovery paths built for isolated failures: single-attempt VM recovery, conservative rate limits and stale disk attachments all needed manual work. The longest part of the outage was restoring customer resources, Managed Kubernetes control planes above all, so Nebius is extending its recovery drills to that layer.

  2. Symptoms

    Every service in the homelab Kubernetes cluster stopped answering: the V-Rising server, Grafana, Jellyfin and Linkding were all unreachable, and the Kubernetes API was down, so the cluster could not be managed at all. The outage was found by hand, about 3 hours after it began, when someone tried to use the services.

    Trigger

    A power outage forced the Kubernetes master node to reboot.

    Root cause
    Component
    Contributing factor
    Detection

    Manually, when someone tried to access the services; there were no automated alerts.

    Remediation
    • Connected a monitor to the master node and read the boot logs, which showed the kernel panic
    • Booted the previous kernel version, which brought the system back
    • Removed the broken Nvidia packages with sudo apt-get remove --purge '^nvidia-.*' and ran sudo dpkg --configure -a
    • Found remaining broken packages with dpkg -l | grep -v ^ii and removed them by hand
    • Ran sudo apt-get install -f and reinstalled linux-headers-$(uname -r)
    • Rebooted and confirmed the kernel panic was gone
    Action items
    • Make sure GPU driver installations fully succeed, or revert immediately when they fail
    • Move the cluster to a high-availability control plane
    • Expose the Kubernetes API through a load balancer in the HA setup
    • Set up a ticketing system to record incidents and their resolution
    • Write predefined troubleshooting workflows to shorten response time
    • Add infrastructure monitoring such as Prometheus and Grafana
    • Add blackbox HTTP and TCP checks from outside the cluster for critical services
    Lessons

    A driver installation that fails half-way can leave kernel packages broken without any visible effect until the next reboot, which may come weeks later and at the worst time. A failed DKMS build should be fixed or reverted at once. With a single master node and no monitoring from outside the cluster, one unbootable machine meant a total outage that nobody was told about; the fix itself was simple once the boot logs were seen.

  3. Symptoms

    Alerts fired at 3:13 PM PST on 11 December 2024, and from 3:16 PM every OpenAI service was significantly degraded or completely unavailable, including ChatGPT, the API and Sora. The status page reported API calls returning errors and difficulties logging in to platform.openai.com and ChatGPT. Customer impact peaked at 3:40 PM.

    Trigger

    At 2:23 PM PST a change introducing a new telemetry service, which collects detailed Kubernetes control plane metrics, was merged and the deployment pipeline started. Between 2:51 PM and 3:20 PM the change was applied to all clusters.

    Root cause
    Component
    Contributing factor
    Detection

    OpenAI's detection tools worked: alerts fired at 3:13 PM PST, a few minutes before customer impact began at 3:16 PM, and the root cause was identified at 3:16 PM.

    Remediation
    • Scaled clusters down to reduce the total Kubernetes API load
    • Blocked network access to the Kubernetes admin APIs so no new expensive requests arrived
    • Scaled up the Kubernetes API servers
    • Removed the telemetry service once enough control was back
    • Moved traffic from impacted clusters to healthy ones
    • Intervened manually in clusters where simultaneous resource downloads saturated resource limits
    Action items
    • Put every infrastructure configuration change through a phased rollout with continuous monitoring of both the service workloads and the clusters, including the Kubernetes control plane
    • Run fault injection tests in which the data plane runs without the control plane for longer, and tests that roll out bad changes on purpose to check detection and rollback
    • Build break-glass mechanisms so engineers can reach the Kubernetes API servers in any circumstances
    • Decouple the Kubernetes data plane from the control plane so that service discovery for critical workloads does not depend on the control plane
    • Speed up recovery with better caching and dynamic rate limiters for resources needed at cluster startup, and regular drills that rapidly replace an entire cluster
    Lessons

    Several systems and processes failed at once and interacted in unexpected ways: tests did not catch the change's effect on the Kubernetes control plane, DNS caching put a delay between the change and the failures, and being locked out of the control plane made remediation very slow. Because service discovery used Kubernetes DNS, the control plane was carrying load for product traffic even though the data plane was meant to be independent of it.

  4. Symptoms

    Jetstack was upgrading the master of a development cluster that many teams use to test their apps during the working day, a regional Google Kubernetes Engine (GKE) cluster in europe-west1. The upgrade ran through Jetstack's GKE Terraform pipeline and did not finish before the 20-minute Terraform timeout, while the GKE console still showed the cluster as upgrading.

    Trigger

    A planned master upgrade of the shared development cluster. The same upgrade had been done on another pre-production environment earlier that day, and no API downtime was expected.

    Root cause
    Component
    Contributing factor
    Detection

    The first sign was the master upgrade missing the 20-minute Terraform timeout; re-running the pipeline returned the kube-apiserver unhealthy error. The cause was identified with the help of Google Support.

    Remediation
    • Deleted the OPA ValidatingAdmissionWebhook resource during a window of API server access
    Action items
    • Limit the OPA webhook to the namespaces where the policy applies and development teams have access
    • Enable the webhook only for Ingress and Service resources, the only resources the policy validates
    • Add a liveness probe so OPA is restarted when it stops responding, and update the OPA documentation
    • Follow the open upstream Kubernetes issue about this behaviour
    Lessons

    With alerting on API server response times, the team might have seen CREATE and UPDATE requests slow down across the board as soon as the OPA-backed webhook was first deployed. Every workload needs probes: OPA looked so simple to deploy that the team skipped the Helm chart, which adds a livenessProbe for the admission controller containers among other adjustments to the tutorial configuration. Others had hit the same problem, and an upstream issue to improve it was still open.

  5. Symptoms

    After Civis released its new script infrastructure on Kubernetes internally in September 2018, developers reported that kubectl commands were slow, and users intermittently could not start notebooks and services.

    Trigger

    Migrating clients' Python, R and container scripts from the in-house Bocce system to Kubernetes (the project called Croquet) pushed the cluster to about 290 EC2 instances under a large script load.

    Root cause
    Component
    Contributing factor
    Detection

    Developer reports of slow kubectl commands and user reports of notebooks and services failing to start, then high CPU on the master nodes.

    Remediation
    • moved internal users back to the old Bocce infrastructure
    • resized the three master nodes from m4.large to m4.4xlarge
    • changed the Datadog setup so per-node agents no longer polled the API server for service metadata
    • raised max-requests-inflight for non-mutating requests from 400 to 1200
    • grew the etcd EBS volumes from 20 to 100 GB (100 to 300 IOPS)
    • switched client scripts from the ClusterFirst DNS policy to Default
    Action items
    • Upgrade etcd from 2.2.1 to 3.x once Kops supports a safe migration
    • Solve the in-cluster DNS timeouts so client scripts can talk to other workloads in the cluster
    Lessons

    Kubernetes can reach thousands of nodes only after tuning, and third-party DaemonSets are a common cause of control plane load: an agent on every node that polls or watches the API server multiplies with the cluster size. Datadog, kube2iam and the fluentd metadata filter all showed this. A small configuration change often fixes it, but finding it took load testing and the API server access logs.

Check your cluster for this

These 6 cases involve Kubernetes API server and etcd. kubegap audits a Kubernetes cluster for gaps like these, read-only, from Claude Code or Codex; its checks cite public reports like the ones in this library.

By root cause5

Dependency failure1 case

Organisation
  1. IL-0133 A storm shut down cooling at Nebius's us-central1 data center, and a disk hot-plug bug kept Managed Kubernetes control planes down for hours after power returned
    Nebius2026

Software defect1 case

Organisation
  1. IL-0138 A failed Nvidia driver build left broken kernel packages on the only Kubernetes master node, which hit a kernel panic on reboot after a power outage and took the homelab cluster down for six days

Configuration change2 cases

Organisation
  1. IL-0005 A new telemetry service overloaded the Kubernetes API servers of large clusters and broke DNS-based service discovery for all OpenAI services
    OpenAI2024
  2. IL-0008 An unresponsive OPA validating webhook crash-looped the API server during a GKE master upgrade, and node auto-repair then recreated every node

Capacity exhaustion1 case

Organisation
  1. IL-0075 Kubernetes API servers pegged on CPU when the cluster grew to about 290 nodes, traced to Datadog agents polling the API

unknown1 case

Organisation
  1. IL-0059 Single-master Kubernetes control plane kept dying because the kubelet restarted a healthy etcd on a failing kubeadm liveness probe