  1. Symptoms

    On 3 March 2026, during a scheduled maintenance to replace a faulty switch in a cluster in IONOS Cloud's TXL data center, monitoring alerts fired and the hosts in that cluster lost network connectivity. Customers saw intermittent network degradation or outages, and the Data Center Designer (DCD) web frontend and the AI Model Hub became unreachable.

    Trigger

    During a scheduled maintenance to replace a faulty switch, Topology 2 of 2 in the affected cluster was disabled as planned, and a link flap on a switch in Topology 1 then flooded the InfiniBand control plane with alerts and started a fabric resweep.

    Root cause
    Component
    Contributing factor
    Detection

    IONOS began investigating monitoring alerts in TXL; the first status update was posted at 11:36 UTC.

    Remediation
    • Switched from the affected control plane to its standby
    • Rebooted the locked-up gateways
    • Recovered Topology 1 from the scheduled maintenance
    • Paused provisioning in the cluster that had a backlog of queued jobs
    • Re-enabled provisioning once network connectivity improved and watched job execution
    • Re-established connectivity for the systems that support the DCD
    Action items
    • Adjusted the control-plane configuration to use less aggressive failover timers and reduced heavy sweep activity, lowering the load on the forwarding table
    • Reduced the number of multicast group memberships to relieve the forwarding table
    • Set up continuous monitoring of forwarding table use and control-plane memory with alerts before capacity limits are reached
    • Move the control plane to dedicated high-performance servers, separate from data-plane traffic
    • Audit IPv6 configurations and IPoIB driver settings
    • Modernise the interconnect fabric, including switches, gateways and drivers
    • Hardened IAM maintenance protocols so that critical identity services keep working when the primary Cloud APIs are temporarily unavailable
    • Move IAM to a dedicated platform without a dependency on the standard managed Kubernetes clusters
    • Introduce a dedicated provisioning provider for DBaaS and Managed Kubernetes
    • Add automated circuit breakers to the provisioning engine against overload and queue buildup from self-healing services
    • Improve visibility and control over job execution and prioritisation in the provisioning queue
    • Change the provisioning queue architecture to decouple services and reduce spillover
    Lessons

    IONOS identified the linking of services through the shared provisioning queue as a key reason the degradation lasted as long as it did. Alongside making each service more robust, it is decoupling the provisioning queue and addressing dependencies between services to reduce the blast radius of future incidents.

  2. Symptoms

    On 15 January 2026, network services for VMware-based Private Clouds in IONOS Cloud's Berlin location stopped working: customers lost management VPN access and traffic to and from their virtual machines. Inside IONOS, several management interfaces in the Berlin region could no longer be reached.

    Trigger

    During a planned maintenance window to add a new VLAN to the management devices, a human error in the command replaced the existing VLANs on the trunk between the core and management devices instead of adding to them, so only the new VLAN stayed active.

    Root cause
    Component
    Contributing factor
    Remediation
    • Restarted the affected storage services in the final stage of recovery, which caused a brief second outage
    Action items
    • Audit the management device architecture to segment it better (target Q3 2026)
    • Evaluate and implement ways to prevent unintended VLAN changes, such as improved configuration safeguards or automation scripts (target Q1 2026)