  1. Symptoms

    Customers using Linode's US-MIA (Miami) and IT-MIL (Milan) data centers saw packet loss and brief performance problems on 14 September 2025 from 17:42 to 18:43 UTC. BR-GRU (Sao Paulo) had the same packet loss on 15 September 2025 from 01:44 to 04:22 UTC.

    Trigger

    A gradual increase in prefixes pushed the routing between the core router and the edge router past the maximum number of permitted prefixes.

    Root cause
    Component
    Contributing factor
    –
    Remediation
    • Raised the prefix limit on all the data center routers
    Action items
    • Raise the thresholds of the sessions between Akamai's backbone and the data center ECOR routers
    • Improve the existing alerting and check its severity before limits are reached, with escalation to the right team for immediate action
  2. Symptoms

    From 16:27 UTC on 21 August 2025, users connecting to Cloudflare from servers in AWS us-east-1, or receiving connections from Cloudflare there, saw high latency, packet loss and failures to reach origins. Cloudflare's network team was alerted to internal congestion in Ashburn (IAD) at 16:44 UTC.

    Trigger

    At about 16:27 UTC a single customer began sending many requests from AWS us-east-1 to Cloudflare for objects in Cloudflare's cache, doubling the total traffic from Cloudflare to AWS.

    Root cause
    Component
    Contributing factor
    Detection

    Cloudflare's network team was alerted to internal congestion in Ashburn (IAD) at 16:44 UTC, and an incident was raised for customer impact at 17:45 UTC.

    Remediation
    • Rate limited the single customer whose traffic caused the surge
    • Took further traffic engineering actions that fully resolved the congestion
    • Asked AWS to revert its BGP prefix withdrawals, which AWS finished at 20:07 UTC
    Action items
    • Build a mechanism to deprioritise a customer's traffic when it congests the network enough to affect others
    • Speed up the Data Center Interconnect upgrades to add network capacity
    • Work with AWS so the two companies' BGP traffic engineering actions do not conflict
    • Build a traffic management system that gives each customer a network resource budget and automates the manual actions used here
    Lessons

    Cloudflare concludes that it must isolate customers better so that no single customer can take over shared network resources and degrade the platform for others, and that its network needs enough capacity to meet demand. It describes the outage as the result of insufficient network congestion management during an unusual high-traffic event.

  3. Symptoms

    On 10 March 2025 at 16:22 UTC, public internet connectivity in Scaleway's FR-PAR region broke for all products. Most internet traffic between the FR-PAR-2 availability zone and the rest of the PAR region was blackholed for about five minutes, while VPC traffic and Dedibox RPN kept working.

    Trigger

    While Scaleway's network team connected a new data center to the FR-PAR backbone, a human mistake in a router configuration rerouted more than 1 Tbps of traffic between OpCore DC3 and DC5 through a single 100 Gbps link.

    Root cause
    Component
    Contributing factor
    Detection

    The router configuration error was detected quickly and rolled back within four minutes.

    Remediation
    • Rolled back the router configuration, restoring the correct configuration at 16:27 UTC
    Action items
    • Harden the peer review and production communication process for changes
    • Add failsafes and tests before network configuration is applied at backbone level
    • Deploy the fix for the Object Storage synchronisation software issue
  4. Symptoms

    On 12 November 2024, after a new version of Canva's editor was deployed at 8:47 AM UTC, the editor's object panel stayed in a perpetual loading state for many users, particularly in Asia. Then from 9:08 AM UTC to about 10:00 AM UTC canva.com was unavailable and all requests to it failed.

    Trigger

    At 8:47 AM UTC a new version of the Canva editor page was deployed, and client devices began fetching its new static assets through Cloudflare while the network path between Cloudflare's Singapore and Ashburn locations was losing packets.

    Root cause
    Component
    Contributing factor
    Remediation
    • Added a temporary Cloudflare firewall rule at 9:29 AM UTC that blocked all traffic at the CDN so new API Gateway tasks could start
    • Redirected canva.com to the status page
    • Restored traffic gradually, starting with Australian users under strict rate limits
    Action items
    • Write a runbook for rerouting, blocking and progressively restoring traffic
    • Show users a more informative error page when canva.com is unavailable
    • Raise the baseline number of API Gateway tasks and the memory of each task
    • Add load shedding rules to the API Gateway for similar traffic patterns
    • Load test the API Gateway regularly
    • Deploy the patch for the thread-locking bug in the telemetry library
    • Add multithreaded tests for the contended code path to the telemetry library microbenchmark suite
    • Use page load completion events as a second canary indicator for page asset releases
    • Experiment with adding another rollout stage to the canary to give more time to detect issues
    • Add timeouts so user requests do not wait excessively long for assets
    • Work with Cloudflare to understand the system interactions behind the incident
  5. Symptoms

    On 18 October 2024, from 7:50 to 8:01 UTC, about 25% of the hypervisors in Scaleway's FR-PAR-1 availability zone lost VPC connectivity with the rest of the region, and products that use VPC failed with them. Public internet connectivity and Elastic Metal VPC connectivity were not affected.

    Trigger

    At 6:20 UTC a Top of Rack switch in FR-PAR-1 had a software crash. One of the two BGP route reflectors for VPC ran on a hypervisor in that rack and was left in an abnormal state.

    Root cause
    Component
    Contributing factor
    Detection

    Health-check monitoring on both route reflectors detected the anomaly, and the Scaleway Customer Excellence and SRE teams detected the customer impact and opened an incident.

    Remediation
    • Fixed both VPC route reflectors by manual action
    Action items
    • Fixed the autohealing mechanism that had failed to fix route reflectors stuck in a stale state; the fix is https://github.com/FRRouting/frr/pull/17163
    • Run different software versions on the route reflectors so a single bug cannot stop several instances
    • Investigate the software issue that left the route reflectors in a stale state
Check your cluster for this

These 24 cases involve BGP routing and Backbone network (WAN). kubegap audits a Kubernetes cluster for gaps like these, read-only, from Claude Code or Codex; its checks cite public reports like the ones in this library.

By root cause9

Configuration change5 cases

  1. IL-0394 A Cloudflare router in Miami leaked IPv6 BGP routes to peers and providers for 25 minutes, congesting the backbone
  2. IL-0339 Azure Front Door and Azure CDN users saw intermittent connection errors, timeouts and latency spikes for hours
  3. IL-0225 An IGP purge command made every Microsoft WAN router recompute routes, causing global latency, timeouts and packet loss
  4. IL-0461 Every rollout of Datadog's metrics query service on Kubernetes raised errors that the logs blamed on DNS
  5. IL-0361 Job searches on seek.com.au failed for 16 minutes as a Transit Gateway silently dropped 9001-byte packets
    SEEK2021

Capacity exhaustion5 cases

  1. IL-0564 Linode's Miami, Milan and Sao Paulo data centers had packet loss as traffic moved onto congested alternate paths
    Linode2025
  2. IL-0341 Traffic between Cloudflare and AWS us-east-1 had high latency, packet loss and origin failures for almost four hours
  3. IL-0440 Pods on Cybozu's Neco Kubernetes platform got frequent no such host and i/o timeout DNS errors from dropped packets
    Cybozu2024
  4. IL-0386 After a move to Google Cloud, Postgres connection timeouts and memcached i/o timeouts spiked on GKE nodes
  5. IL-0537 Sakura Cloud host servers repeatedly lost their storage connection, about five minutes per port switchover

Operator error1 case

Contributing factor
Organisation
  1. IL-0348 Scaleway's FR-PAR region lost public internet connectivity when one 100 Gbps backbone link was saturated

Dependency failure2 cases

Organisation
  1. IL-0257 canva.com went down for about 50 minutes when 1.5 million requests per second OOM-killed every API Gateway task
    Canva2024
  2. IL-0358 Packet Public Cloud locations had high latency and unreachable paths from routing loops and blackholed traffic
    Packet2019

Software defect4 cases

  1. IL-0347 About 25% of Scaleway FR-PAR-1 hypervisors lost VPC connectivity when both VPC BGP route reflectors got stuck
  2. IL-0529 New Google Cloud VMs and other instances came up without network connectivity in all zones after VPC controllers stopped
  3. IL-0336 AWS Direct Connect traffic into the Tokyo Region had packet loss and intermittent connectivity for about six hours
  4. IL-0222 Google Cloud US regions had heavy packet loss and some went unreachable after the network control plane was descheduled

Faulty deployment3 cases

  1. IL-0293 Cloud Bigtable in us-central1 had higher latency and connection errors for about 32 hours from low-rate packet loss
  2. IL-0530 Virtual router controllers in us-central1 ran out of memory in a loop, cutting networking for new and migrated VMs
  3. IL-0532 Azure Software Load Balancer sent packets of one flow to different backends, dropping Firewall and Private Link traffic

Hardware failure1 case

  1. IL-0540 Korea's local government administrative services and Government24 went down as a router port dropped most large packets

Cloud provider outage1 case

Organisation
  1. IL-0220 An overloaded AWS Transit Gateway dropped packets on 4 January 2021, and Slack's web tier saturated and went down
    Slack2021

DNS or network fault2 cases

  1. IL-0240 Cloudflare API requests failed and the dashboard slowed for hours after the authentication database lost its replicas
  2. IL-0590 F5 load balancers cached a path MTU of 296 after Rackspace reboots, and Mailgun connections failed intermittently