  1. Symptoms

    In January 2022 an etcd memory spike overloaded the Kubernetes control plane of one of Render's clusters in Frankfurt. At first only operations that need the control plane failed: new deploys and cron job runs.

    Trigger

    A memory spike in etcd overloaded the cluster's control plane.

    Root cause
    Component
    Contributing factor
    Action items
    • Run CoreDNS on data plane nodes instead of control plane nodes
    • Run etcd on dedicated nodes
    Lessons

    CoreDNS can keep answering from its in-memory cache while the API server is down, but it cannot initialise without it. With CoreDNS on the control plane nodes, a reboot or restart during a control plane outage turned a failure of deploys and cron jobs into a failure of requests to services that were already running. The core problem was that the data plane was not isolated enough from the control plane: even without the reboot, the etcd memory spike alone could have forced CoreDNS to restart.

  2. Symptoms

    When traffic changed sharply, CoreDNS came under heavy load, and the cluster saw network problems and a sudden rise in latency. The horizontal pod autoscaler then added pods, database connections surged, and the impact spread to the whole service.

    Trigger

    Sharp changes in traffic loaded the small number of CoreDNS pods beyond what they could handle.

    Root cause
    Component
    Contributing factor
    Remediation
    • Set up the Cluster Proportional Autoscaler for CoreDNS with nodesPerReplica and coresPerReplica chosen for the instance types in use
    • Spread CoreDNS with soft topologySpreadConstraints (ScheduleAnyway) instead of anti-affinity so Karpenter could consolidate nodes
    • Added alert thresholds on CoreDNS error rate, panics, request duration and request rate
    • Deployed NodeLocal DNSCache so each node answers DNS from a local cache and forwards misses to the main CoreDNS
    Lessons

    A fixed, small number of CoreDNS pods cannot follow a cluster whose nodes and pods change quickly with traffic, and the damage spreads: DNS latency triggers autoscaling, which in turn floods the database with connections. Simply adding many CoreDNS replicas created a different problem, because with tainted nodes and a maxSkew: 1 spread constraint the pods piled onto a few nodes and blocked Karpenter consolidation. Scaling CoreDNS in proportion to the cluster and putting a DNS cache on every node handled both.

  3. Symptoms

    At 10:01 UTC on 2024-03-13 a Kubernetes node entered NotReady state, with CPU requests at 78% and memory requests at 82%. An alert fired in Slack at 10:03 and was picked up at 10:05. An attempt to SSH into the node at 10:13 failed because it was unresponsive; it started responding again at 10:19.

    Trigger

    Pods of a dev container that used Hangfire to trigger jobs failed with OOM and crash-looped on a node where a Grafana Agent pod was already using a lot of memory.

    Root cause
    Component
    Contributing factor
    Detection

    A Slack alert fired two minutes after the node went NotReady and was picked up two minutes later; the second node's NotReady at 15:03 also raised a Slack alert.

    Remediation
    • marked the EC2 instance unhealthy so a new node started
    • cordoned and force-drained the NotReady node and terminated its EC2 instance
    • removed the new LimitRange from the Grafana Agent namespace and restarted the Grafana Agent pod
    • scaled the dev container to 0 replicas, after which EC2 network traffic returned to normal
    • after the second NotReady, scaled the dev container to 0 replicas again and added a new node
    • emailed the team that owns the dev container, which confirmed it was working on a fix
    Action items
    • Move grafana-agent to the monitoring node group
    • Add alerts for when bandwidth across the cluster reaches a certain threshold
    • Investigate whether memory limits can be set on the grafana-agent Helm chart
    • Investigate grafana-agent memory usage
    • Ask Grafana support whether grafana-agent should use a PVC
    • Consider pushing node logs to Loki with limited retention
    • Create a wiki page with common metrics and log queries to check when investigating issues with Kubernetes nodes
    Lessons

    Dev workloads mixed with production let one crash-looping dev container take down nodes that production also used, and a monitoring agent outside its dedicated node group added to the memory pressure. Scaling the suspect container back up before its owners had fixed it brought the failure back on the replacement node. The team also noted that action items from earlier post-mortems need follow-up, and that knowledge of useful CloudWatch metrics had not been shared, which made the diagnosis harder.

  4. Symptoms

    At around 2 AM ICT on 2023-04-09 the team saw unusual CPU use on one cluster node, which throttled every other service on it and made them fail. They presumed an upstream container runtime bug in containerd and runc and decided to fully reboot the affected nodes, taking the cluster down for maintenance on the assumption that it was not in active use.

    Trigger

    A full cold reboot of the nodes that showed unusual CPU use, followed by upgrades and cold reboots of the other nodes.

    Root cause
    Component
    Contributing factor
    Detection

    The team saw unusual CPU use on a node around 2 AM ICT and failing services on the rebooted nodes around 2:30 ICT; developers reported the Terra repositories down at 6:31 ICT.

    Remediation
    • uninstalled Multus and Calico and replaced them with the Cilium CNI
    • rolled back most cluster settings except the CNI
    Lessons

    Rebooting nodes to clear one problem can expose another; here a CNI chain could not reach the API server after a cold start. Repeating the same reboot on more nodes while the first failure was not understood spread the outage from a few nodes to the whole cluster. The team also found that Cilium's real resource use in their cluster was acceptable, contrary to the benchmark they had relied on.

  5. Symptoms

    At 09:33 UTC on 14 February 2023 end users told the platform team that Kubernetes logs were not arriving in CloudWatch as expected. The investigation went through fluentd and found that the nodes were running containerd as their container runtime instead of docker-shim. A scheduled node rollover the day before, at 07:30 UTC on 13 February, had set containerd as the default runtime by accident.

    Trigger

    A scheduled node rollover had accidentally made containerd the default container runtime, which stopped log shipping to CloudWatch; the unscheduled rollover to revert it timed out, and the pipeline run that followed reduced the Auto Scaling group from 30 to 15 instances.

    Root cause
    Component
    Contributing factor
    Detection

    End users reported the missing CloudWatch logs that started the work. The postmortem lists 2 minutes as the time to detection of the node failure.

    Remediation
    • ran the node rollover script to add new nodes, which failed on a timeout from Docker Hub
    • ran the node rollover script a second time, which added new nodes that the load balancer marked healthy at 11:01 UTC
    Action items
    • Document the rollover process, especially what can be done when it goes wrong
    • Investigate options for improving the rollover process
    • Add fluentd log collection to the QA test suite so logs are covered end to end
    • Add alarms for fluentd when too little or no log data is sent
    • Implement a staging environment
    • Implement guards against selecting an invalid container runtime
    Lessons

    When a change goes wrong, rolling back to a known working configuration is safer than rushing a fix, which can make the damage worse. Launching new worker nodes depends on the cloud-init script not failing in any way. The QA configuration differed from production, there was no staging environment, the QA tests did not cover fluentd log collection, and the rollover process had no documentation for when it fails.

Check your cluster for this

These 13 cases involve etcd and Kubernetes API server. kubegap audits a Kubernetes cluster for gaps like these, read-only, from Claude Code or Codex; its checks cite public reports like the ones in this library.

By root cause5

Software defect2 cases

  1. IL-0058 Argo CD deleted namespaces shared by several applications, leaving about 97 applications stuck Missing and OutOfSync
  2. IL-0003 linkerd lost Kubernetes service discovery after an etcd reconfiguration, and restarting every linkerd instance turned failed payments into a full platform outage
    Monzo2017

Capacity exhaustion7 cases

  1. IL-0006 VPC subnets ran out of IP addresses because the AWS VPC CNI kept IPs on full nodes, and WARM_IP_TARGET changes then blocked pod starts after every pod deletion
    Neon2025
  2. IL-0204 An etcd memory spike overloaded the control plane of a Render Frankfurt cluster, and DNS then failed because CoreDNS ran on the rebooted control plane nodes and could not start without the API server
    Render2024
  3. IL-0182 Too few CoreDNS replicas on EKS were overloaded during traffic spikes, raising latency and cutting the network for task pods, and the over-provisioned, tightly spread CoreDNS pods added later blocked Karpenter consolidation
  4. IL-0110 A Grafana Agent pod's high memory use and crash-looping Hangfire pods drove a Kubernetes node into system OOM and NotReady, twice in one day
    DFDS2024
  5. IL-0093 Ingress controller pods crash-looped one after another because the leader pod had exhausted its shared memory
  6. IL-0076 Kubernetes masters went down after Dex filled etcd with AuthRequest objects and deleting its namespace started an endless list-and-timeout loop
  7. IL-0037 Image registry rate-limited a whole region after a crash-looping DaemonSet with imagePullPolicy Always pulled through three NAT instances

unknown2 cases

  1. IL-0087 After a cold reboot of RKE2 nodes, pods could not get IP addresses because Multus could not reach the Kubernetes API, and further reboots spread the failure to every node
  2. IL-0059 Single-master Kubernetes control plane kept dying because the kubelet restarted a healthy etcd on a failing kubeadm liveness probe

Configuration change1 case

Organisation
  1. IL-0109 A retried node rollover on a DFDS EKS cluster set the Auto Scaling group back to 15 instances, and the default termination policy removed every healthy worker node, leaving the cluster with no nodes
    DFDS2023

DNS or network fault1 case

Organisation
  1. IL-0199 A non-essential container exceeding its memory limit made GitHub's production pods unavailable, and their restarts failed because a DNS maintenance change had left the clusters unable to reach the image registry
    GitHub2020