  1. Symptoms

    On 10 March 2025 at 16:22 UTC, public internet connectivity in Scaleway's FR-PAR region broke for all products. Most internet traffic between the FR-PAR-2 availability zone and the rest of the PAR region was blackholed for about five minutes, while VPC traffic and Dedibox RPN kept working.

    Trigger

    While Scaleway's network team connected a new data center to the FR-PAR backbone, a human mistake in a router configuration rerouted more than 1 Tbps of traffic between OpCore DC3 and DC5 through a single 100 Gbps link.

    Root cause
    Component
    Contributing factor
    Detection

    The router configuration error was detected quickly and rolled back within four minutes.

    Remediation
    • Rolled back the router configuration, restoring the correct configuration at 16:27 UTC
    Action items
    • Harden the peer review and production communication process for changes
    • Add failsafes and tests before network configuration is applied at backbone level
    • Deploy the fix for the Object Storage synchronisation software issue
  2. Symptoms

    On 12 November 2024, after a new version of Canva's editor was deployed at 8:47 AM UTC, the editor's object panel stayed in a perpetual loading state for many users, particularly in Asia. Then from 9:08 AM UTC to about 10:00 AM UTC canva.com was unavailable and all requests to it failed.

    Trigger

    At 8:47 AM UTC a new version of the Canva editor page was deployed, and client devices began fetching its new static assets through Cloudflare while the network path between Cloudflare's Singapore and Ashburn locations was losing packets.

    Root cause
    Component
    Contributing factor
    Remediation
    • Added a temporary Cloudflare firewall rule at 9:29 AM UTC that blocked all traffic at the CDN so new API Gateway tasks could start
    • Redirected canva.com to the status page
    • Restored traffic gradually, starting with Australian users under strict rate limits
    Action items
    • Write a runbook for rerouting, blocking and progressively restoring traffic
    • Show users a more informative error page when canva.com is unavailable
    • Raise the baseline number of API Gateway tasks and the memory of each task
    • Add load shedding rules to the API Gateway for similar traffic patterns
    • Load test the API Gateway regularly
    • Deploy the patch for the thread-locking bug in the telemetry library
    • Add multithreaded tests for the contended code path to the telemetry library microbenchmark suite
    • Use page load completion events as a second canary indicator for page asset releases
    • Experiment with adding another rollout stage to the canary to give more time to detect issues
    • Add timeouts so user requests do not wait excessively long for assets
    • Work with Cloudflare to understand the system interactions behind the incident
  3. Symptoms

    On 18 October 2024, from 7:50 to 8:01 UTC, about 25% of the hypervisors in Scaleway's FR-PAR-1 availability zone lost VPC connectivity with the rest of the region, and products that use VPC failed with them. Public internet connectivity and Elastic Metal VPC connectivity were not affected.

    Trigger

    At 6:20 UTC a Top of Rack switch in FR-PAR-1 had a software crash. One of the two BGP route reflectors for VPC ran on a hypervisor in that rack and was left in an abnormal state.

    Root cause
    Component
    Contributing factor
    Detection

    Health-check monitoring on both route reflectors detected the anomaly, and the Scaleway Customer Excellence and SRE teams detected the customer impact and opened an incident.

    Remediation
    • Fixed both VPC route reflectors by manual action
    Action items
    • Fixed the autohealing mechanism that had failed to fix route reflectors stuck in a stale state; the fix is https://github.com/FRRouting/frr/pull/17163
    • Run different software versions on the route reflectors so a single bug cannot stop several instances
    • Investigate the software issue that left the route reflectors in a stale state
  4. Symptoms

    A team using Neco, the Kubernetes platform run by Cybozu's Cloud Platform team, reported what looked like a performance problem in the cluster DNS servers. An application in a pod that resolved cluster Services at hundreds of requests per second frequently got `no such host` and `i/o timeout` errors.

    Trigger

    The number of MySQL clusters watched by the monitoring application increased, and after that the name resolution errors became frequent.

    Root cause
    Component
    Contributing factor
    Detection

    A team using the platform contacted the Cloud Platform team, describing the errors as a performance problem in the cluster DNS server.

    Remediation
    • Raised the kernel parameter netdev_max_backlog on the nodes
    • Set up alerts on softnet
    • Wrote a runbook for the softnet alerts
    Action items
    • Evaluate Cilium's netkit device so pod packets bypass the backlog queue
    Lessons

    Raising netdev_max_backlog makes the same failure less likely and the new alerts catch it early, but it is not a root fix: a pod that sends more packets can fill the backlog queue again. Cybozu sees replacing the veth interface with netkit, which skips the backlog queue, as the root fix.

  5. Symptoms

    From 11:45 UTC on 30 July 2024, a subset of customers got intermittent connection errors, timeouts and latency spikes when connecting to Microsoft services that use Azure Front Door (AFD) and Azure Content Delivery Network (CDN). The Azure Portal team saw the first service degradation at 11:47 UTC.

    Trigger

    Around 11:45 UTC the Azure network DDoS protection service was disengaging after a routine DDoS mitigation and returning traffic to its default routing to AFD, but the routes at one site in Europe could not be updated because the network control plane could not reach that site during a local power outage.

    Root cause
    Component
    Contributing factor
    Detection

    The Azure Portal team detected service degradation at 11:47 UTC and began to investigate. At 12:10 UTC network monitoring correlated the Portal incident to a network issue at one site in Europe, and networking engineers joined.

    Remediation
    • Rerouted traffic under the standard congestion playbook, which removed most of the impact by 13:58 UTC
    • Ordered the network control plane to reissue its commands to the misbehaving device, which could not be reached
    • Removed the device that kept attracting traffic from the network and scanned the network for other issues
    Action items
    • Add the missing configuration on network devices so a DDoS mitigation issue in one geography cannot spread to another
    • Improve validation and monitoring in the Azure network to detect invalid configurations
    • Improve monitoring for when the DDoS protection service is unreachable from the control plane but still serving traffic
Check your cluster for this

These 24 cases involve BGP routing and Backbone network (WAN). kubegap audits a Kubernetes cluster for gaps like these, read-only, from Claude Code or Codex; its checks cite public reports like the ones in this library.

By root cause9

Configuration change5 cases

  1. IL-0394 A Cloudflare router in Miami leaked IPv6 BGP routes to peers and providers for 25 minutes, congesting the backbone
  2. IL-0339 Azure Front Door and Azure CDN users saw intermittent connection errors, timeouts and latency spikes for hours
  3. IL-0225 An IGP purge command made every Microsoft WAN router recompute routes, causing global latency, timeouts and packet loss
  4. IL-0461 Every rollout of Datadog's metrics query service on Kubernetes raised errors that the logs blamed on DNS
  5. IL-0361 Job searches on seek.com.au failed for 16 minutes as a Transit Gateway silently dropped 9001-byte packets
    SEEK2021

Capacity exhaustion5 cases

  1. IL-0564 Linode's Miami, Milan and Sao Paulo data centers had packet loss as traffic moved onto congested alternate paths
    Linode2025
  2. IL-0341 Traffic between Cloudflare and AWS us-east-1 had high latency, packet loss and origin failures for almost four hours
  3. IL-0440 Pods on Cybozu's Neco Kubernetes platform got frequent no such host and i/o timeout DNS errors from dropped packets
    Cybozu2024
  4. IL-0386 After a move to Google Cloud, Postgres connection timeouts and memcached i/o timeouts spiked on GKE nodes
  5. IL-0537 Sakura Cloud host servers repeatedly lost their storage connection, about five minutes per port switchover

Operator error1 case

Contributing factor
Organisation
  1. IL-0348 Scaleway's FR-PAR region lost public internet connectivity when one 100 Gbps backbone link was saturated

Dependency failure2 cases

Organisation
  1. IL-0257 canva.com went down for about 50 minutes when 1.5 million requests per second OOM-killed every API Gateway task
    Canva2024
  2. IL-0358 Packet Public Cloud locations had high latency and unreachable paths from routing loops and blackholed traffic
    Packet2019

Software defect4 cases

  1. IL-0347 About 25% of Scaleway FR-PAR-1 hypervisors lost VPC connectivity when both VPC BGP route reflectors got stuck
  2. IL-0529 New Google Cloud VMs and other instances came up without network connectivity in all zones after VPC controllers stopped
  3. IL-0336 AWS Direct Connect traffic into the Tokyo Region had packet loss and intermittent connectivity for about six hours
  4. IL-0222 Google Cloud US regions had heavy packet loss and some went unreachable after the network control plane was descheduled

Faulty deployment3 cases

  1. IL-0293 Cloud Bigtable in us-central1 had higher latency and connection errors for about 32 hours from low-rate packet loss
  2. IL-0530 Virtual router controllers in us-central1 ran out of memory in a loop, cutting networking for new and migrated VMs
  3. IL-0532 Azure Software Load Balancer sent packets of one flow to different backends, dropping Firewall and Private Link traffic

Hardware failure1 case

  1. IL-0540 Korea's local government administrative services and Government24 went down as a router port dropped most large packets

Cloud provider outage1 case

Organisation
  1. IL-0220 An overloaded AWS Transit Gateway dropped packets on 4 January 2021, and Slack's web tier saturated and went down
    Slack2021

DNS or network fault2 cases

  1. IL-0240 Cloudflare API requests failed and the dashboard slowed for hours after the authentication database lost its replicas
  2. IL-0590 F5 load balancers cached a path MTU of 296 after Rackspace reboots, and Mailgun connections failed intermittently