Incident Library
Applied filters ComponentObject storageFactorAutomation amplificationClear allEvery case under the filters, with no sentence; newest first.
Suggested filters Search, and the values found in your words appear here.

Graph

  • Root cause
  • Component
  • Symptom
  • Contributing factor
  • Case

Cases4 cases

1 to 4 of 4

  1. Symptoms

    On 10 March 2025 at 16:22 UTC, public internet connectivity in Scaleway's FR-PAR region broke for all products. Most internet traffic between the FR-PAR-2 availability zone and the rest of the PAR region was blackholed for about five minutes, while VPC traffic and Dedibox RPN kept working.

    Trigger

    While Scaleway's network team connected a new data center to the FR-PAR backbone, a human mistake in a router configuration rerouted more than 1 Tbps of traffic between OpCore DC3 and DC5 through a single 100 Gbps link.

    Root cause
    Component
    Contributing factor
    Detection

    The router configuration error was detected quickly and rolled back within four minutes.

    Remediation
    • Rolled back the router configuration, restoring the correct configuration at 16:27 UTC
    Action items
    • Harden the peer review and production communication process for changes
    • Add failsafes and tests before network configuration is applied at backbone level
    • Deploy the fix for the Object Storage synchronisation software issue
  2. Symptoms

    From 2:45 PM PDT on July 30th, 2024, several AWS services in the Northern Virginia (US-EAST-1) Region had higher latency and error rates: CloudWatch Logs, Amazon Data Firehose, the event framework that publishes Amazon S3 events, Amazon ECS, AWS Lambda, Amazon Redshift and AWS Glue. All of them used one internal cell of Amazon Kinesis Data Streams, whose requests had started to see elevated latency and errors.

    Trigger

    At 9:09 AM PDT on July 30th a routine deployment started in one Availability Zone of the Kinesis cell, and taking hosts in and out of service during the deployment set off the failure.

    Root cause
    Component
    Contributing factor
    Remediation
    • Deployed a change that shed load by reducing incoming stream volume from less time-sensitive internal workloads
    • Added capacity to the subsystem that provisions secure connections for Kinesis requests
    • Added more capacity at 6:32 PM PDT to further improve connection provisioning
    Action items
    • Keep the added connection provisioning capacity, load-shedding tooling and changed connection limits in place in US-EAST-1
    • Apply the same changes in every other region that has cells with the new Kinesis Data Streams architecture
    • Update the cell management system to better manage the workload that triggered the issue
  3. Symptoms

    In the week of 10 October 2022, Linode Object Storage in Newark had two incidents of reduced performance and availability, on 10 and 16 October, and in some cases the front-end gateways returned 504 gateway timeouts to customers. The second incident began while the first was still being investigated.

    Trigger

    One back-end Object Storage node had a hardware problem that was not an outright failure, so the node kept going up and down.

    Root cause
    Component
    Contributing factor
    Remediation
    • Removed the failed back-end infrastructure from the Object Storage cluster
    Action items
    • Improve detection so subtle problems with failing or misbehaving hardware are found and triaged before they affect the wider cluster
    • Describe Ceph-related events more accurately to on-call administrators and define alerts more clearly
    Lessons

    Hardware that misbehaves without failing outright can cause service-wide problems, and Linode's internal monitoring had gaps in spotting such subtle issues before they affected the wider cluster.

  4. Symptoms

    On 22 June 2021, within minutes of an update released at 8:25 AM UTC, bunny.net's global fleet of close to 100 DNS servers kept crashing and restarting, more than 60% of traffic was lost, hundreds of Gbits of throughput disappeared, and over 750,000 websites were affected. After 10 minutes the team realised that the DNS servers were restarting and dying and that nothing could bring them back up in that state.

    Trigger

    At 8:25 AM UTC bunny.net released an update meant to reduce the download size of the SmartEdge optimization database, and it uploaded a corrupted file to Edge Storage.

    Root cause
    Component
    Contributing factor
    Detection

    About 10 minutes after the release, the team realised that the DNS servers were restarting and dying.

    Remediation
    • Deployed by hand an update that disabled the SmartEdge system on the DNS nodes
    • Routed all requests through Frankfurt instead of Madrid on a couple of DNS servers
    • Migrated the deployment systems and files to a third-party cloud storage service
    • Rewired the deployment system and DNS software to the new storage and deployed
    • Synced the databases and deployed the newest file sets through the third-party service
    Action items
    • Phase out the BinaryPack library as a hot-fix
    • Test third-party libraries more extensively
    • Migrate the internal APIs to an independent third-party service
    • Find how to stop non-critical software from becoming a single point of failure across clusters
    • Make the DNS system keep a local copy of all backup data with automatic failure detection
    Lessons

    bunny.net had built its systems to rely on each other, including the critical parts of its internal infrastructure, so one corrupted file brought down several layers of redundancy with no way back. A part of the infrastructure treated as non-critical turned out to be a single point of failure for several clusters at once, which canary deployments did not catch. Building infrastructure inside its own ecosystem lets one failure cascade through all of it. In the rush to fix the outage the team made typos and mistakes, and the final deployment came after it calmed down and double-checked everything.

Check your cluster for this

These 4 cases involve Object storage and Authoritative DNS servers and records. kubegap audits a Kubernetes cluster for gaps like these, read-only, from Claude Code or Codex; its checks cite public reports like the ones in this library.