Cases71 cases

26 to 30 of 71

  1. Symptoms

    At 20:31 UTC on 15 November 2023, some GPU virtual machines in us-northcentral1-a became unavailable. One row of servers in a Crusoe Cloud data center in the us-northcentral1 region had lost power, and every server in the row powered off together with the VMs running on it.

    Trigger

    While the row's UPS was in bypass mode for routine maintenance, power switched from the primary source to a backup source for reasons unrelated to the maintenance.

    Root cause
    Component
    Contributing factor
    Detection

    The power failure happened at 20:31 UTC. The first status post, at 21:07 UTC, said certain VMs in us-northcentral1-a were unavailable, and at 21:31 UTC the status page said the affected VMs had been identified.

    Remediation
    • identified the VMs on the row that lost power
    • restarted the affected VMs after power was restored
    Action items
    • Review the standard operating procedures for UPS maintenance to minimise customer impact during future maintenance
    • Build future data centers with redundant UPSs
    • Improve recovery procedures to reduce mean time to resolution
    Lessons

    When the only UPS for a row is in bypass for maintenance, the row is exposed to any power event during that window, even one unrelated to the work. Crusoe Cloud's response is redundant UPSs in future data centers, a review of maintenance procedures, and faster recovery of VMs after power returns.

  2. Symptoms

    Between 5:42 AM and 7:16 AM PT on 8 November 2023 a large share of requests to OpenAI failed with 502 or 503 errors. Every model and API endpoint saw significant failures.

    Trigger

    A morning with dramatically more completions than any previous day pushed the routing layer nodes, which already had a chronic memory problem, past their memory limits.

    Root cause
    Component
    Contributing factor
    Remediation
    • limited incoming traffic
    • redeployed the routing service en masse
    • ramped traffic back up slowly
    Action items
    • Pre-allocate the responseBuffer and reuse it instead of allocating a new one in a loop (3X improvement in memory and CPU usage)
    • Adjust the configured memory limits to an appropriate level so the service has significant headroom
    • Add rate limit controls to shed traffic more gracefully
    • Increase the service's capacity
    • Change alerting to catch the underlying memory behaviour before it escalates into service issues
    • Configure autoscaling for the service, which was not possible before because added capacity could hurt an upstream service
  3. Symptoms

    Standard alerting paged Honeycomb's on-call engineers about the performance and stability of event ingestion, and the automated load-shedding mechanisms tripped and sent further notifications. The status page described a higher than normal error rate and response time on the ingestion service.

    Trigger

    An abnormally large number of queries arrived from many separate connections within a few minutes.

    Root cause
    Component
    Contributing factor
    Detection

    Standard alerting notified the on-call engineers about ingestion performance and stability, and the automated load-shedding mechanisms added notifications when they tripped. The first status post, about alerts on a higher than normal error rate and response time, went up at 18:28 PST (02:28 UTC), 13 minutes after the 02:15 UTC start.

    Remediation
    • Scaled the ingest fleet up manually and aggressively
    • Cut off most ingest for a few minutes so the ingest hosts could come back with enough capacity
    • Temporarily lowered the rate limits for the most aggressive traffic sources until their traffic subsided
    Action items
    • Keep the ingest fleet scaled up to prevent a repeat while longer-term fixes are worked on
    • Decide on the projects that will address these failure paths
    Lessons

    Load shedding and auto-scaling were in place, yet a burst that arrived faster than the cache could spread its writes still took the ingest hosts down. During recovery, Kubernetes' crash loop back-off worked against the operators: the hosts that had failed stayed offline while the fleet needed every host. Clients that retry whole OTel batches after a partial drop can multiply traffic many times over, so per-source rate limits were what finally stabilised ingest.

  4. Symptoms

    Customers of DigitalOcean Managed Kubernetes (DOKS) saw worker nodes go NotReady between 06:00 and 07:00 UTC and stay unavailable, taking down the services on them, until the nodes were replaced or rebooted; some nodes needed several replacements or reboots. The first sporadic reports on October 8 said replacing the node fixed it. The same thing happened again around 06:00 UTC on October 9, more widely and across many regions, and again on October 10. Only clusters on versions 1.27.6-do.0 and 1.28.2-do.0 were affected.

    Trigger

    A systemd timer in the DigitalOcean Debian image started apt upgrade daily at 06:00 UTC, with a random delay of up to 60 minutes.

    Root cause
    Component
    Contributing factor
    Detection

    Sporadic customer reports of failed worker nodes arrived at 07:43 UTC on October 8; internal incident response started at 07:10 UTC on October 9 after broader impact across regions.

    Remediation
    • Advised customers to replace or reboot affected worker nodes
    • Arranged SSH and console access to worker nodes while they were healthy, and live-debugged an affected node on October 10
    • Released a DaemonSet to all affected clusters that disables the apt upgrade systemd timer on every worker node
    • Released new node images without the auto-update process
    Action items
    • Disable the timer during node provisioning, then remove the DaemonSet from all clusters
    • Add a check to the internal conformance test suite for new cluster versions that the auto-upgrade process and other unwanted timers stay disabled
    • Support logging into worker nodes even when normal access paths are broken
    Lessons

    An operating system auto-update timer left enabled in a node image can change the kernel and systemd underneath Kubernetes, and a timeout that kills the upgrade half-way can leave a node without networking. Failures that start at the same time every day point to a scheduled job on the nodes, and systemd timers belong on that list next to cron jobs. When the failure takes out a node's network, an investigation that depends on logging into the node stalls; access paths that work while the node is broken shorten diagnosis.

  5. Symptoms

    From about 10:30 UTC on 30 August 2023, customers had trouble accessing or using Azure, Microsoft 365 and Power Platform services in Australia East. The affected Azure services included Azure Kubernetes Service (AKS) along with storage, SQL Database, Cosmos DB, virtual machines and Azure Resource Manager.

    Trigger

    At 08:41 UTC a lightning strike on electrical infrastructure about 18 miles away caused a utility voltage sag that shut down the cooling chillers of datacenters in one Australia East availability zone; 13 chillers failed to restart automatically and five could not be restarted, so two data halls overheated and their infrastructure was shut down.

    Root cause
    Component
    Contributing factor
    Detection

    Cosmos DB impact was detected by monitoring at 10:47 UTC, first automated communications went to Azure Service Health at 10:48 UTC, the public Azure Status page was updated at 11:30 UTC, and all subscriptions in Australia East were sent portal communications at 11:36 UTC.

    Remediation
    • shut down the remaining networking, compute and storage in the two affected data halls so the chilled water loop could cool down
    • restarted the five chillers manually at 12:12 UTC
    • restored power to all hardware by 15:10 UTC and brought infrastructure back in phases
    • restored AKS operations through the recovery of the SQL Database operation queue, with no other mitigation
    Action items
    • AKS: convert all operation queue SQL Database databases to be zone redundant (estimated September 2023)
    • AKS: replace all cross-region SQL Database queue usage with zone-redundant Service Bus queues (estimated September 2023)
    • Change the control timing logic of the Chiller Management System so chillers do not fail to restart after voltage fluctuations
    • Change the emergency procedure for manual restarts of simultaneous chiller failures from an adjacent sequence to a load-based sequence per data hall
    • Increase technician staffing at the datacenter as a temporary measure for manual chiller restarts
    • Storage: optimise the large-scale recovery process and update troubleshooting guides (estimated December 2023)
    • Azure Service Fabric: improve reliability of SQL Database tenant ring recovery (estimated December 2023)
    • SQL Database: review the trigger criteria of auto-failover groups (estimated October 2023)
    • SQL Database: upgrade internal tooling to enable mass migration of databases (estimated December 2023)
    • Cosmos DB: optimise Service Managed Failover for single-region-write accounts (estimated November 2023)
    • ARM: complete the migration of its storage layer to the zonally redundant architecture (estimated December 2023)
    • Incident management: harden readiness, process and playbook for power-down scenarios (estimated October 2023)
    Lessons

    A control plane spread across availability zones still fails with a zone when one of its dependencies, here the SQL Database operation queue, is not zone redundant. When a second region uses the same database, the failure crosses into that region as well. Workloads already running were not expected to be affected; what stopped was everything that needs the managed service's control plane, such as scaling and cluster changes.

Check your cluster for this

These 71 cases involve Node pool and Ingress controller. kubegap audits a Kubernetes cluster for gaps like these, read-only, from Claude Code or Codex; its checks cite public reports like the ones in this library.

By root cause11

Capacity exhaustion13 cases

  1. IL-0102 CoreDNS pods on a production EKS cluster ran out of memory under a burst of new pods, endpoints and nodes, taking down the Buildkite web UI, APIs and job dispatch
  2. IL-0067 Redis filled its persistent volume, corrupted its append-only file and crash-looped on every restart
  3. IL-0080 kube-dns on Mercari's GKE clusters could not keep up with peak-hour DNS query rates, and a Sev1 production outage followed when several services failed DNS resolution
  4. IL-0082 Losing one CoreDNS pod during a planned EKS node reroll overloaded the remaining CoreDNS pods, causing DNS timeouts and errors across multiple services at RebelMouse
  5. IL-0170 During a Lunar New Year event, traffic more than three times normal filled the nf_conntrack table on the EKS node running the Istio ingress gateway, dropping packets and taking down Backpackr's web and app services
  6. IL-0027 All CoreDNS pods landed on one node, the node ran out of memory, and DNS for the whole service went down
  7. IL-0085 A control plane node of Magic Pages' Kubernetes cluster on Hetzner Cloud ran out of memory, the cluster's own calls then used up the Hetzner API rate limit, and all customer websites were down for about 7.5 hours
  8. IL-0202 A burst of queries and database writes exhausted connection pools and memory on Honeycomb's ingest hosts, and Kubernetes crash-loop back-off kept failed hosts offline so ingest capacity stayed too low to recover
  9. IL-0094 Student pods filled the shared nodes of a JupyterHub cluster and starved the hub's core pods, freezing the hub
    2i2c2020
  10. IL-0037 Image registry rate-limited a whole region after a crash-looping DaemonSet with imagePullPolicy Always pulled through three NAT instances
  11. IL-0064 CPU-heavy pods packed onto one Google Cloud node drove it to kernel panics, and the crash moved from node to node until the site was down
  12. IL-0036 A reindex Job that kept failing exhausted one node after another until the whole cluster was down
  13. IL-0040 Parallel Helm installs saturated small gp2 root volumes on a kops cluster and left all three workers NotReady with the kubelet or Docker down

Dependency failure3 cases

  1. IL-0133 A storm shut down cooling at Nebius's us-central1 data center, and a disk hot-plug bug kept Managed Kubernetes control planes down for hours after power returned
    Nebius2026
  2. IL-0187 A brief Spring Cloud Config Server downtime failed every client application's liveness probe, because the actuator health check included the config server, and Kubernetes restarted the pods in a kill loop
  3. IL-0135 A power source switch during UPS maintenance cut power to a row of GPU servers and shut down Crusoe Cloud VMs in us-northcentral1

Breaking change in an upgrade7 cases

  1. IL-0092 Upgrading ingress-nginx from 1.12.0 to 1.14.3 brought a newer ModSecurity and OWASP Core Rule Set whose false positives blocked HMPPS Auth, so users could not sign in to their applications
  2. IL-0101 After Google forced a GKE control plane upgrade to 1.33.2 at a deprecation deadline, no new node could initialise, so autoscaling and spot node replacement stopped for 15 hours
  3. IL-0079 A GKE node auto-upgrade to an ubuntu_containerd image with a kernel regression left kube-proxy unable to apply its ip6tables rules, so load balancer health checks failed and several clusters lost all ingress traffic
  4. IL-0203 A routine Kubernetes cluster system update made the AWS Load Balancer Controller fail, so new pods were never registered with the ALB and Honeycomb's EU1 ingest and UI went down once the last old pods were replaced
  5. IL-0180 A GKE control plane auto-upgrade from 1.22 to 1.23 removed the v1beta1 Ingress and ValidatingWebhookConfiguration APIs that Istio 1.7.4 still used, and Istio stopped working in production
  6. IL-0060 Kubernetes 1.24 upgrade removed the master node label that Calico route reflectors selected on, dropping all pod routes and taking Reddit down for 314 minutes
    Reddit2023
  7. IL-0198 An automatic Ubuntu security update restarted systemd-networkd, which flushed the IP rules Cilium relied on and cut more than 60 percent of Datadog's Kubernetes nodes off the network across regions and cloud providers

Configuration change17 cases

  1. IL-0063 VPN outage after recreating a Redis StatefulSet restarted the whole Redis cluster without readiness checks
  2. IL-0192 A Crossplane composition merge-policy change for a TLS policy update switched Kubernetes Services from LoadBalancer to ClusterIP and deleted the load balancers behind about 25% of Grafana Cloud services
  3. IL-0005 A new telemetry service overloaded the Kubernetes API servers of large clusters and broke DNS-based service discovery for all OpenAI services
    OpenAI2024
  4. IL-0114 An unpinned AWS VPC CNI plugin was updated automatically during a capacity expansion, leaving new pods Pending without IP addresses and stopping CoW Protocol settlements for about 3.5 hours
  5. IL-0153 DOKS worker nodes went NotReady at 06:00 UTC on three days because a systemd timer in the Debian image ran apt upgrade and killed it mid kernel upgrade, breaking node networking
  6. IL-0091 Changing the worker node instance type through Terraform recycled all nodes at once and deleted users' production pods together
  7. IL-0109 A retried node rollover on a DFDS EKS cluster set the Auto Scaling group back to 15 instances, and the default termination policy removed every healthy worker node, leaving the cluster with no nodes
    DFDS2023
  8. IL-0116 A CNI configuration change incompatible with a hardware variant that exists only in production cut network connectivity in an OpenAI GPU cluster and took text-davinci-003 fully down
    OpenAI2023
  9. IL-0191 A label selector accidentally added to the Loki distributor Service matched only the new pods of a rollout, which took all write traffic, were OOM-killed and stalled the rollout
  10. IL-0009 A duplicated generated name made Argo CD replace the InfluxDB Cloud production Application and delete the whole production environment
  11. IL-0111 Switching the main Kubernetes ingress controller from Traefik v1 to v2 stopped X-Forwarded headers being passed, which broke the Okta login flow for every service using Okta and stopped DFDS online bookings for over an hour
    DFDS2021
  12. IL-0010 A templating change that dropped its {{ }} delimiters made Argo CD delete all 478 Skyscanner services in every region
  13. IL-0105 Replacing the AWS VPC CNI during a Terraform refactoring detached the ALB target groups, and every service in the Kubernetes cluster returned 503
    DFDS2021
  14. IL-0008 An unresponsive OPA validating webhook crash-looped the API server during a GKE master upgrade, and node auto-repair then recreated every node
  15. IL-0004 A new default pod priority let a new Cortex cluster preempt every production ingester in a cascade, taking Grafana Cloud Hosted Prometheus down
  16. IL-0066 Broken ConfigMap change lay dormant for weeks, then took down Pusher's edge proxy when a cluster upgrade replaced its pods
    Pusher2019
  17. IL-0055 A failing CronJob with the default concurrency policy piled up thousands of restarting pods and took down a cluster
    Target2018

Faulty deployment4 cases

  1. IL-0188 Rolling updates on EKS returned 502 errors for about 30 seconds because Kubernetes deleted old pods as soon as new pods passed readiness, before the ALB had marked the new pod targets healthy
  2. IL-0020 During an EKS 1.30 upgrade the descheduler tried to reschedule every pod on the cordoned nodes at once and production workloads went down
  3. IL-0086 A deployment meant for a CircleCI test Kubernetes cluster also removed Traefik and Calico resources from the production cluster, taking down the CircleCI UI and runner.circleci.com
  4. IL-0034 A crashing stats agent sidecar marked every pod unready and the service mesh pulled all services out of traffic
    Airbnb2019

Operator error5 cases

  1. IL-0095 An engineer deleted the prod namespace of the LEAP JupyterHub while believing the kubeconfig pointed at a new cluster, and the hub was down for about an hour
    2i2c2025
  2. IL-0207 A routine task run from an engineer's local environment switched to production and deleted GitLab.com's Consul release, so Patroni lost Consul and GitLab.com returned 5xx errors to all traffic
    GitLab2022
  3. IL-0115 One of OpenAI's three production AKS clusters went offline through a human error, and rebuilding it took 10½ hours because an AKS Kubernetes upgrade broke the ingress and AKS cannot be downgraded
    OpenAI2022
  4. IL-0089 A test cluster deletion script run with the kube context pointing at the live-1 production cluster deleted its ingress controller, monitoring, logging, cert-manager, kiam and external-dns
  5. IL-0054 All ingress traffic lost while draining a GKE node pool because the load balancer only targeted new nodes without ingress-nginx pods

Software defect12 cases

  1. IL-0078 Enabling EKS secrets encryption with KMS through Terraform removed worker node IAM permissions and took down all ZenML Pro workspaces
    ZenML2025
  2. IL-0157 After a release, new nodes could not join Linode Kubernetes Engine clusters with IP ACL enabled, so autoscaling failed on about 20 to 25 clusters
    Linode2025
  3. IL-0138 A failed Nvidia driver build left broken kernel packages on the only Kubernetes master node, which hit a kernel panic on reboot after a power outage and took the homelab cluster down for six days
  4. IL-0024 Expensive cache-backed API calls and uncancelled database requests overloaded MongoDB and took the Hugging Face Hub down three times
  5. IL-0123 A response buffer allocated anew in a loop made OpenAI's routing layer nodes hit their memory limits and fail readiness checks on a morning with more completions than any day before, causing 502 and 503 errors across all models
    OpenAI2023
  6. IL-0132 A faulty resource cleanup process marked Vertex AI prediction endpoints as deleted worldwide, undeploying customers' models and failing predictions for 4 hours 20 minutes
  7. IL-0106 A malformed Traefik IngressRoute triggered a Traefik v2 bug once a node rollover restarted every Traefik pod, and all Kubernetes services returned 404
    DFDS2021
  8. IL-0196 Adding a second Redis replica and lowering memory limits in one RedisFailover change restarted the only Redis pod that held data, and Sentinel promoted the empty new replica, erasing the data
    Palark2020
  9. IL-0051 A third-party log shipping client leaked file descriptors with every new container until nodes failed with too many open files
  10. IL-0074 All AirMap platform services down as worker nodes went NotReady and pods crash-looped on network and DNS failures
    AirMap2018
  11. IL-0072 High etcd write latency made the API servers return stale data, and the production cluster flipped between two views of its state
  12. IL-0003 linkerd lost Kubernetes service discovery after an etcd reconfiguration, and restarting every linkerd instance turned failed payments into a full platform outage
    Monzo2017

Cloud provider outage6 cases

  1. IL-0084 Packet drops on a bare metal provider's vSwitch forced Namespace to rebuild its fra3 region and left global capacity short, and the next day slow NVMe writes on a control plane node drove the Kubernetes API server to very high CPU
  2. IL-0145 A power sag and chiller failure in one Australia East availability zone took down the AKS control plane's compute and its non-zone-redundant SQL Database operation queue, blocking AKS create, update and delete operations in Australia East and Australia Southeast
  3. IL-0096 A GKE node pool pinned to the europe-west2-b zone could not scale for 6.5 hours because Google ran out of resources in that zone (ZONE_RESOURCE_POOL_EXHAUSTED)
    2i2c2022
  4. IL-0172 An AWS Tokyo data centre cooling failure took down 6 of 60 CockroachDB nodes on Kubernetes within 22 minutes, and ranges lost quorum because the Helm-deployed cluster had no availability zone locality configured
  5. IL-0193 A GCP persistent disk degradation took down a Cassandra StatefulSet whose OrderedReady policy blocked recovery, and Metrictank could not reconnect to the recreated pods, causing a 23-hour Graphite query outage
  6. IL-0014 A GKE upgrade to a withdrawn version stalled on slow drains and a stuck node pool, then broke an ingress and confused the HPA

unknown2 cases

  1. IL-0087 After a cold reboot of RKE2 nodes, pods could not get IP addresses because Multus could not reach the Kubernetes API, and further reboots spread the failure to every node
  2. IL-0059 Single-master Kubernetes control plane kept dying because the kubelet restarted a healthy etcd on a failing kubeadm liveness probe

Certificate or credential expiry1 case

Organisation
  1. IL-0113 The managed GKE control plane of Webhook Relay's main cluster failed because its API server certificates had never been rotated, and a manual credential rotation reported success without taking effect

DNS or network fault1 case

Organisation
  1. IL-0199 A non-essential container exceeding its memory limit made GitHub's production pods unavailable, and their restarts failed because a DNS maintenance change had left the clusters unable to reach the image registry
    GitHub2020