  1. Symptoms

    From 11:45 UTC on 30 July 2024, a subset of customers got intermittent connection errors, timeouts and latency spikes when connecting to Microsoft services that use Azure Front Door (AFD) and Azure Content Delivery Network (CDN). The Azure Portal team saw the first service degradation at 11:47 UTC.

    Trigger

    Around 11:45 UTC the Azure network DDoS protection service was disengaging after a routine DDoS mitigation and returning traffic to its default routing to AFD, but the routes at one site in Europe could not be updated because the network control plane could not reach that site during a local power outage.

    Root cause
    Component
    Contributing factor
    Detection

    The Azure Portal team detected service degradation at 11:47 UTC and began to investigate. At 12:10 UTC network monitoring correlated the Portal incident to a network issue at one site in Europe, and networking engineers joined.

    Remediation
    • Rerouted traffic under the standard congestion playbook, which removed most of the impact by 13:58 UTC
    • Ordered the network control plane to reissue its commands to the misbehaving device, which could not be reached
    • Removed the device that kept attracting traffic from the network and scanned the network for other issues
    Action items
    • Add the missing configuration on network devices so a DDoS mitigation issue in one geography cannot spread to another
    • Improve validation and monitoring in the Azure network to detect invalid configurations
    • Improve monitoring for when the DDoS protection service is unreachable from the control plane but still serving traffic
  2. Symptoms

    From 15:22 US/Pacific on 16 May 2024, new VMs and other new instances across Google Cloud came up without network programming, so the new instances could not open network connections, and VMs that were migrated or restarted lost connectivity. Changes to virtual network configuration, such as firewall rules and load balancers, were not applied. Internal monitoring alerted Google engineers at 15:41.

    Trigger

    Google's infrastructure team ran a routine maintenance action meant to shut down one unused VPC Controller in a single Google Cloud zone, and the automation shut down VPC controllers in all zones where the controllers were still in use.

    Root cause
    Component
    Contributing factor
    Detection

    Internal monitoring alerts reached Google engineers at 15:41 US/Pacific, and the investigation started immediately.

    Remediation
    • Paused maintenance operations to prevent the shutdown from repeating
    • Brought the affected VPC Controllers back into a serving state in every zone
    • Stopped the automation responsible for the shutdown until safeguards are in place
    • Recovered partial Apigee proxy deployments by hand
    • Cleaned up VMs left behind by failed Dataproc cluster deletions
    Action items
    • Add safety measures that check that maintenance operations carry correctly scoped zone information
    • Make the underlying tools reject maintenance operations that do not specify zones
    • Tighten on-demand access control so one maintenance invocation cannot work across multiple zones
    • Add safety checks, testing and validation for maintenance operations, including positive and negative test cases for the new safety measures
  3. Symptoms

    On 5 October 2023 in us-central1, newly created VMs waited a long time before their networking worked, and VMs that had been live migrated lost connectivity for a long time after the migration. Networking telemetry showed cross-region packet loss to and from us-central1 from 03:08 US/Pacific. Health check state of VMs reached load balancers late.

    Trigger

    A management plane behaviour change, meant to decouple the processing of API updates to Instance Groups and Network Endpoint Groups used as load balancer backends, was deployed in us-central1 after rolling out to several other regions without incident.

    Root cause
    Component
    Contributing factor
    Detection

    Engineers were alerted to slowness in the virtual network control plane in us-central1 at 21:45 US/Pacific on 4 October, before the packet loss started, and to controller failures from memory exhaustion at 02:11 on 5 October. Networking telemetry showed cross-region packet loss from 03:08.

    Remediation
    • Increased the memory allocated to the virtual network router controllers
    • Rolled back the management plane change in us-central1
    • Restarted by hand the routers that were still not accepting updates
    Action items
    • Alert proactively on memory risks and unexpected memory increases
    • Refactor the deployment configuration so engineers can reallocate memory much faster
    • Re-evaluate existing practices and add safety mechanisms for API reconciliation
    • Make management plane changes more visible across teams so the changes can be correlated faster
    • Adjust the deployment footprint so a regional API change is less likely to exhaust memory across the region at once
    • Optimise memory use in the traffic routers and their controllers
  4. Symptoms

    On Sunday 2 June 2019, with user impact beginning between 11:47 and 11:49 US/Pacific, Google Cloud projects in several US regions saw elevated packet loss from network congestion, and some regions became unreachable. Customers saw higher latency, intermittent errors and lost connectivity to instances in us-central1, us-east1, us-east4, us-west2, northamerica-northeast1 and southamerica-east1, while us-west1, Europe and Asia had no regional congestion.

    Trigger

    At 11:45 US/Pacific a relatively rare type of datacenter maintenance event started in one physical location, and the automation that runs it descheduled logical clusters that also held network control plane jobs in other physical locations.

    Root cause
    Component
    Contributing factor
    Detection

    Google engineers were alerted to the failure two minutes after it began and started the incident process used for the most serious production incidents. The first customer notice appeared on the status page at 12:53 US/Pacific.

    Remediation
    • Lowered the priority of less critical network traffic classes to reduce congestion
    • Halted the datacenter automation software responsible for the maintenance event
    • Rescheduled the network control plane and its supporting infrastructure in each location
    • Rebuilt and redistributed the lost network control plane configuration, rolling it out from 14:03
    • Directed service traffic away from the affected regions
    • Moved the Cloud VPN control plane in three regions out of its fail-safe state
    Action items
    • Keep the maintenance automation off until safeguards stop it descheduling jobs in several physical locations at once
    • Harden the cluster management software to reject such requests whatever their origin
    • Reconfigure the network control plane to reject maintenance requests of the type involved
    • Make the network control plane in each location persist its configuration
    • Let the network stay in fail static mode longer when the control plane is lost
    • Review, update and test emergency response tooling and procedures, including customer communication tooling, for such network failures
    • Extend continuous disaster recovery testing to this and similarly catastrophic failures
  5. Symptoms

    At about 08:49 UTC on 2 June 2019, Packet's internal network monitoring alerted on serious reachability and performance problems in several of Packet's global datacenter locations. The first investigation found routing loops and traffic being blackholed to specific internal and Internet destinations.

    Trigger

    A trans-continental US backbone link in the network of Packet's upstream provider Zayo had a hardware failure and blackholed IP traffic routed over it.

    Root cause
    Component
    Contributing factor
    –
    Detection

    Packet's internal network monitoring alerted at 08:49 UTC on reachability issues in several global datacenter locations, and engineers confirmed them at 08:52.

    Remediation
    • Migrated traffic to an alternative network and removed Zayo from the provider mix
    • Applied route filters to return service to normal
    • Optimised specific routing policies to improve latency across the backbone with the new traffic mix
    Action items
    • Expand internal connectivity monitoring and alerting of on-call operations teams
    • Expand network automation and routing so traffic can be balanced across all available backbone paths and an operator can trigger automated re-routes across all Packet datacenters in a major provider incident
    • Make Packet's provisioning systems less dependent on third party network providers and inter-datacenter connectivity
Check your cluster for this

These 12 cases involve Network control plane (SDN) and BGP routing. kubegap audits a Kubernetes cluster for gaps like these, read-only, from Claude Code or Codex; its checks cite public reports like the ones in this library.

By root cause5

Faulty deployment4 cases

  1. IL-0356 Every domain hosted on Railway returned HTTP 404 to new connections for five minutes because route lookups failed
  2. IL-0354 Fly.io private networking (6PN) broke for some machines after edges received gateway /80 routes
    Fly.io2026
  3. IL-0563 Linode servers lost connectivity in all data centers as route servers built incomplete BGP route tables
    Linode2025
  4. IL-0530 Virtual router controllers in us-central1 ran out of memory in a loop, cutting networking for new and migrated VMs

Capacity exhaustion1 case

Organisation
  1. IL-0350 Hosts in an IONOS TXL cluster lost connectivity when an InfiniBand fabric resweep failed on a full multicast table

Software defect5 cases

  1. IL-0233 A VPC control plane release broke IP alias routes in Nebius eu-west1, and Managed Kubernetes pods lost connectivity
    Nebius2025
  2. IL-0347 About 25% of Scaleway FR-PAR-1 hypervisors lost VPC connectivity when both VPC BGP route reflectors got stuck
  3. IL-0529 New Google Cloud VMs and other instances came up without network connectivity in all zones after VPC controllers stopped
  4. IL-0222 Google Cloud US regions had heavy packet loss and some went unreachable after the network control plane was descheduled
  5. IL-0396 New or live-migrated GCE instances, VPN tunnels and network load balancers were unreachable on public IPs for over 2h

Configuration change1 case

Organisation
  1. IL-0339 Azure Front Door and Azure CDN users saw intermittent connection errors, timeouts and latency spikes for hours

Dependency failure1 case

Contributing factor
–
Organisation
  1. IL-0358 Packet Public Cloud locations had high latency and unreachable paths from routing loops and blackholed traffic
    Packet2019