Cases21 cases

14 to 18 of 21

  1. Symptoms

    On 25 October 2021 from about 11:16, traffic to the DNS servers in KT's network rose sharply, and then KT's internet service failed across the whole country. KT recognised the internet outage at 11:20, and the outage lasted about 89 minutes until KT finished recovery at about 12:45.

    Trigger

    During the replacement of an enterprise network router at KT's Busan office, worked on remotely from the Busan communication center, a worker entered a routing configuration script that lacked the 'exit' command that should have ended the IS-IS part of the configuration.

    Root cause
    Component
    Contributing factor
    Detection

    KT recognised the internet outage at 11:20, four minutes after DNS traffic began to surge at 11:16. The Ministry of Science and ICT saw the traffic increase in its own monitoring, and KT reported the outage to the ministry at 11:40.

    Remediation
    • Isolated the router where the faulty routing configuration was entered
    • Logged in to each regional router, deleted the faulty processes and restarted them
    Action items
    • Check the network management of major carriers, including their work procedures and the systems that stop technical errors from spreading
    • Consider having major carriers introduce simulation systems that diagnose errors from network work in advance
    • Have the NMS center and network operations center of each major carrier check technically that approved work plans are followed
    • Strengthen safeguards in routing work, such as limiting the number of route entries updated at once below a set level
    • Strengthen the monitoring of carriers' outages and develop technology, including AI-based preventive diagnosis, for network stability and resilience
    • Prepare structural measures for a stable network architecture and network survivability
    • Let carriers notify users of outages through SNS, text messages and other means, not only the website
    Lessons

    The investigation named management problems and technical problems. On the management side, work approved for the night was done during the day, partner company workers did the routing work without a work manager, and the work was done with the network still connected. On the technical side, the two pre-verification steps were people reading the script and missed the missing 'exit', there was no virtual testbed for trying the work on a disconnected network, and nothing stopped an error in one region from spreading to the whole country.

  2. Symptoms

    At 09:20 CET on 13 October 2021, during a planned change on a router, IPv4 traffic across OVHcloud's whole network stopped being routed, while all IPv6 traffic stayed reachable. The team detected a problem with the router's performance at 09:21 CET and escalated at once.

    Trigger

    A planned change to a router in the Vint Hill datacentre in the United States, meant to strengthen anti-DDoS protection, included a command to regulate the redistribution of BGP into OSPF, and the router did not interpret that command correctly.

    Root cause
    Component
    Contributing factor
    Detection

    At 09:21 CET the team detected a problem with the router's performance and started the escalation process.

    Remediation
    • Disconnected the optical equipment to isolate the router's connectivity
    • Powered off the faulty router
    • Stabilised connectivity to restore the remaining services
    Action items
    • Re-evaluate the change procedure for this type of equipment, which applies the command line natively
    • Strengthen the related change process
  3. Symptoms

    On 4 October 2021 Facebook's platforms went down worldwide: every connection in Facebook's global backbone network was lost, and the data centers were cut off from each other and from the internet. The rest of the internet could no longer find Facebook's servers, because Facebook's authoritative DNS servers had become unreachable.

    Trigger

    During routine maintenance of the backbone, a command was issued to assess the availability of global backbone capacity, and it unintentionally took down all connections in the backbone network.

    Root cause
    Component
    Contributing factor
    Remediation
    • Sent engineers onsite to the data centers to debug the issue and restart systems
    • Brought the backbone network back online across the data center regions
    • Brought services back gradually, managing the rising load to avoid crashes from a traffic surge
    Action items
    • Find ways to simulate the global backbone being taken offline in storm drills
    • Strengthen testing, drills and overall resilience
    Lessons

    The hardening that protects Facebook's data centers against unauthorized access slowed recovery from an outage caused by Facebook's own error, and the author judges that tradeoff worth keeping. Storm drills prepared the teams to bring load back safely, although no drill had yet simulated the global backbone going offline.

  4. Symptoms

    At 11:59AM CDT on Friday 28 August 2020, Basecamp's Ops team received a flood of alerts from PagerDuty, Nagios and Prometheus. Monitoring showed that the newer of the two metro links between the data centers in Ashburn, VA and Chicago, IL had been lost for about 20-30 seconds, and BC3 kept responding slowly after the link came back.

    Trigger

    Both redundant metro links between Basecamp's Ashburn and Chicago data centers dropped for short periods; monitoring showed the newer link down for about 20-30 seconds.

    Root cause
    Component
    Contributing factor
    Detection

    A flood of alerts from PagerDuty, Nagios and Prometheus, with monitoring showing the lost metro link. A lingering alert for one Redis DB instance later pointed to the replication problem.

    Remediation
    • Turned chat off at the load balancer layer so the rest of BC3 could stabilise
    • Restarted Redis on the replica that was stuck in the resynchronization loop
    Action items
    • Make the documented Redis configuration changes for the known replication issue
    • Make concrete plans to remove the shared physical path under the two metro links
    • Prove the failover systems in production at peak load
    • Make explicit room for post-incident follow-up work and push other work out
    Lessons

    Planned redundancy and live testing had given Basecamp a false sense of security, especially at peak load: moving between redundant network links or shifting load across data centers should work without issue, and Basecamp would rather find out in a controlled test with the full team ready. The follow-up from an outage needs urgency and explicitly cleared time, not just a place on a list.

  5. Symptoms

    On 16 July 2020 between 13:26 and 13:48 UTC, DNS queries to two nodes of Gandi's LiveDNS platform failed with a timeout, and retries against the other name servers of a domain failed as well. The status page reported impact for FR customers.

    Trigger

    A software bug in Gandi's DNS server software triggered a fault and stopped the server on two LiveDNS nodes.

    Root cause
    Component
    Contributing factor
    Detection

    Monitoring alerts fired on the DNS servers, but they were first read as false positives among the noise from an earlier internal network incident.

    Action items
    • Fix the way a node is disabled when its DNS server is not working correctly
    • Fix the node configuration and add monitoring so that no node announces several clusters
    • Rework monitoring and internal training and organisation
    • Deploy the fix for the bug in the DNS server software
Check your cluster for this

These 21 cases involve BGP routing and Backbone network (WAN). kubegap audits a Kubernetes cluster for gaps like these, read-only, from Claude Code or Codex; its checks cite public reports like the ones in this library.

By root cause6

Configuration change6 cases

  1. IL-0400 Public sector sites across Wales lost connectivity for over 8 hours as a PE router wrongly advertised a default route
    PSBA2026
  2. IL-0394 A Cloudflare router in Miami leaked IPv6 BGP routes to peers and providers for 25 minutes, congesting the backbone
  3. IL-0225 An IGP purge command made every Microsoft WAN router recompute routes, causing global latency, timeouts and packet loss
  4. IL-0266 Eqiad routers looped traffic between each other after a BGP MED change and could not reach other sites' public IPs
  5. IL-0539 KT's internet service failed nationwide for about 89 minutes as wrong routes spread from one router in Busan
    KT2021
  6. IL-0228 IPv4 routing across OVHcloud's global network broke after a router change put the full internet routing table into OSPF

Capacity exhaustion3 cases

  1. IL-0350 Hosts in an IONOS TXL cluster lost connectivity when an InfiniBand fabric resweep failed on a full multicast table
  2. IL-0564 Linode's Miami, Milan and Sao Paulo data centers had packet loss as traffic moved onto congested alternate paths
    Linode2025
  3. IL-0341 Traffic between Cloudflare and AWS us-east-1 had high latency, packet loss and origin failures for almost four hours

Faulty deployment1 case

Contributing factor
Organisation
  1. IL-0563 Linode servers lost connectivity in all data centers as route servers built incomplete BGP route tables
    Linode2025

Software defect5 cases

  1. IL-0233 A VPC control plane release broke IP alias routes in Nebius eu-west1, and Managed Kubernetes pods lost connectivity
    Nebius2025
  2. IL-0347 About 25% of Scaleway FR-PAR-1 hypervisors lost VPC connectivity when both VPC BGP route reflectors got stuck
  3. IL-0342 DigitalOcean's AMS3, LON1 and SFO2 data centers lost Internet connectivity in repeated waves as edge routers failed
  4. IL-0359 Queries to Gandi LiveDNS timed out when two crashed anycast DNS nodes kept announcing all three name server addresses
    Gandi2020
  5. IL-0222 Google Cloud US regions had heavy packet loss and some went unreachable after the network control plane was descheduled

Dependency failure5 cases

  1. IL-0509 SourceHut was down for 170 hours after a DDoS led its upstream network to null-route the PHL datacenter's subnet
  2. IL-0267 Wikimedia's eqsin cache site went unreachable when both of its transport links to the core data centers were down
  3. IL-0255 Basecamp's two redundant links between data centers dropped together and a Redis replica resync loop stalled chat
  4. IL-0358 Packet Public Cloud locations had high latency and unreachable paths from routing loops and blackholed traffic
    Packet2019
  5. IL-0258 FastMail was unreachable for almost two hours when the GRE tunnels carrying its traffic from Level 3 went down

Operator error1 case

Organisation
  1. IL-0221 A backbone maintenance command disconnected all Facebook data centers, and its DNS servers withdrew their BGP routes
    Meta2021